Sinexcel Uninterruptible Power Supply Brochure: Technical Specifications

Original title Sinexcel Uninterruptible Power Supply brochure, technical specifications, PDF p.7

Sinexcel

Sinexcel modular UPS brochure: 40 to 2400 kVA, 97 percent efficiency in double conversion, over 99 percent in Advanced ECO mode, typical 2 ms ECO-to-online switching, input THDi below 3 percent.

On this page

Overview

The document is the modular UPS brochure of China's Sinexcel Electric (stock code 300693), covering 40 kVA to 2400 kVA. The company states it provides low-voltage power quality solutions through a sales network in more than 50 countries. The UPS has two working modes: classic double-conversion online mode (97 percent efficiency) and Advanced ECO mode (99 percent efficiency); the switching time from ECO to online mode is given as at most 5 ms, typically 2 ms.

The brochure shows energy savings using a 300 kVA UPS: the 97 percent online mode saves 52,560 kWh per year against a legacy UPS at 95 percent efficiency, and ECO mode saves more. More than 90 percent of the loss is said to come from semiconductors (IGBT, diode, SCR) and the inductor; to cut it, fifth-generation low-loss IGBTs, SiC Schottky diodes, an optimized Vienna rectifier and a three-level topology are used.

Reliability features: dual controllers and dual auxiliary power supplies, automatic offline function for a failed power module, hot-swappable modules with mean time to repair close to zero, a wide 138 to 486 V input range, cold start, a battery management system (charge/discharge current, SOC, temperature-adjusted charging voltage) and recording of abnormal-event waveforms (export by USB). The technical table gives a rated voltage of 380/400/415 VAC, input THDi below 3 percent, input power factor above 0.99, frequency 40 to 70 Hz, output voltage accuracy ±1 percent and THDv below 1 percent on linear load.

Overload: the inverter takes 110 percent for 60 minutes, 125 percent for 10 minutes and 150 percent for 1 minute before switching to bypass; the bypass is continuous up to 135 percent (30 °C) or 125 percent (40 °C). The ordering code sets the battery type (lead-acid or lithium-ion), air duct direction and options such as the battery management card. The document is a product brochure; model-level dimensions and weights are not on this page.

Key points

  1. Capacity from 40 kVA to 2400 kVA; modular with hot-swappable power modules.
  2. Efficiency is 97 percent in double-conversion online mode (single module above 97.5 percent) and over 99 percent in Advanced ECO mode.
  3. ECO-to-online switching time is at most 5 ms, typically 2 ms.
  4. For 300 kVA, the 97 percent online mode saves 52,560 kWh per year against a 95 percent legacy UPS.
  5. Input voltage range 138 to 486 V (linear derating between 138 and 305 V), rated 380/400/415 VAC, 40 to 70 Hz.
  6. Input THDi below 3 percent, power factor above 0.99; output voltage accuracy ±1 percent, THDv below 1 percent (linear load).
  7. Inverter overload: 110 percent for 60 min, 125 percent for 10 min, 150 percent for 1 min.
  8. Dual controllers and dual auxiliary supplies; cold start; lithium-ion or lead-acid battery option.

Using it in design

  • Compare the ECO mode's transfer (at most 5 ms, typically 2 ms) with the critical load's ride-through; classify the load before making ECO the default mode.
  • Recalculate the annual energy saving with your own load level and tariff; the brochure figure rests on 300 kVA and a specific efficiency assumption.
  • State N+1 module redundancy and the hot-swap repair-time target in the specification for the modular design.
  • Consider the 138 to 486 V input range for reducing battery use on weak supplies, and reflect the 138 to 305 V derating in load capacity.
  • Put the battery type (lead-acid or lithium-ion) and the battery management card option into the ordering code.

Who should read it

Designers selecting modular UPS for medium and large data centres, and decision makers evaluating energy efficiency.

Document contents

  1. Company profile
  2. Unit layout and the two working modes
  3. Advanced ECO mode
  4. Online mode and loss analysis
  5. Product features: high reliability, modular design, analysis system, battery management, cold start
  6. Ordering information
  7. Technical specifications

Publication details

Authors
Sinexcel
Publisher
Sinexcel
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sinexcel Sinexcel Uninterruptible Power Supply brochure, technical specifications, PDF p.7. Sinexcel. https://en.sinexcel.com/power/ups/Sinexcel%20UPS%20brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.