SynQor Military Field-Grade UPS Trifold, Rev J 03/03/2026
Original title SynQor UPS trifold, Rev J 03/03/2026, PDF p.3
SynQor
SynQor's military field-grade on-line double-conversion 1U/2U rack UPS family delivers 1250 W/1500 VA and 2500 W/3000 VA, runs over 13-22 minutes at 80% power on lithium-ion batteries and gives full power from -20 to +55 C.
On this page
Overview
The brochure presents SynQor UPS products designed and made in the USA for military and aerospace applications. Units have a sealed, weather-proof die-cast aluminium chassis, true on-line double conversion, input power factor correction, and supply loads from 0.0 to 1.0 power factor and non-linear loads. Input is universal 80-265 VAC and 47-65 Hz, with options for 47-800 Hz, 3-phase input and a 28 VDC second source.
The AC-output base models are UPS-1500 (1250 W, 1500 VA, 1U) and UPS-3000 (2500 W, 3000 VA, 2U), each with three battery choices: S, H and M packs. Runtime at full power is over 10, 13.5 and 16 minutes respectively, and at 80% power over 13, 18 and 22 minutes. AC output is set to 115 or 230 Vrms at 50, 60 or 400 Hz. Optional DC1 (auxiliary up to 500 W) and DC2 (high power) outputs exist; the total of AC, DC1 and DC2 power is limited to 1250 W for UPS-1500 and 2500 W for UPS-3000.
Besides stand-alone use, the electronic breaker option allows up to 32 units in a fault-tolerant, glitch-free parallel system with N+M redundancy, and the floating-neutral option allows up to 3 units to be combined. Compliance targets are MIL-STD-461F, 704F, 810G, 1275D and 1399-300B. DC-output-only UPS-1250 models and high-voltage adjustable DC output models are also offered. The brochure describes a field and vehicle type solution, not a data-centre product.
Key points
- AC-output models: UPS-1500 (1250 W/1500 VA, 1U) and UPS-3000 (2500 W/3000 VA, 2U).
- Runtime at full power for S/H/M is >10, >13.5 and >16 min; at 80% power >13, >18 and >22 min.
- Size 17.00 x 21.60 x 1.73 in (1U) and 17.00 x 22.22 x 3.40 in (2U); weight 32-33.8 lb (1500) and 65-68.6 lb (3000).
- Operation: full power from -20 to +55 C, storage -40 to +65 C; the -40 C option gives >10 min at full power.
- Input 80-265 VAC, 47-65 Hz; options 47-800 Hz and 3-phase 85-140 VRMS L-N.
- AC output 115 or 230 Vrms, 50/60/400 Hz; DC1 up to 500 W, DC2 up to 1250 W for UPS-1500.
- Up to 32 units in parallel (N+M) with the electronic breaker; up to 3 with floating neutral.
- Cold start, hot-swappable lithium-ion battery pack, MIL-STD compliance.
Using it in design
- Total AC, DC1 and DC2 output power is a shared budget; in multi-output configurations keep the sum under 1250 W or 2500 W.
- Judge runtime at the real load fraction rather than full power; at 80% power runtime lengthens noticeably.
- If parallel or N+M redundancy is needed, order the electronic breaker (R) option and the configuration cable.
- For mobile or field critical equipment (edge sites, telecom, defence), evaluate the temperature range and the 400 Hz option.
- Not every part-number combination is valid, so confirm the code with the manufacturer.
Who should read it
Designers selecting small-capacity UPSs for military, aerospace and harsh-environment applications.
Document contents
- Product features and options
- Block diagram
- Specification compliance
- AC and DC output base models
- DC-output-only models
- High-voltage adjustable DC output
Publication details
- Authors
- SynQor
- Publisher
- SynQor
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
SynQor SynQor UPS trifold, Rev J 03/03/2026, PDF p.3. SynQor. https://s3.us-east-2.amazonaws.com/synqor/resources/UPS%20trifold.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.