Zhicheng Champion CPTH Series: Technical Parameters

Guangdong Zhicheng Champion

The Guangdong Zhicheng Champion CPTH-2010/2015/2020 are 10-20 kVA (8-16 kW) high-frequency on-line UPSs with three-phase input and single-phase output, 0.8 output power factor, 0.99 input power factor and 0 ms transfer.

On this page

Overview

The product page presents the CPTH series from 10 to 20 kVA as a high-frequency on-line UPS with 3/1 input/output. There are three models: CPTH-2010 (10 kVA/8 kW), CPTH-2015 (15 kVA/12 kW) and CPTH-2020 (20 kVA/16 kW). The units are true double conversion, DSP-controlled, with active power factor correction in all phases and a 0.8 output power factor, and offer ECO mode, dual-mains input, EPO, generator compatibility, adjustable battery count, maintenance bypass and optional N+X parallel redundancy.

Input is three-phase five-wire, 380 Vac; the voltage window is 195-520 Vac at 50% load and 305-478 Vac at 100% load, and frequency range is 46-54 Hz. Input power factor is 0.99 or better at full load and harmonic current is 5% or less. Output is single phase 220 Vac with crest factor 3:1; THD is under 2% on 100% linear load and under 4% on non-linear load. Transfer time is 0 ms on AC fault and on bypass-to-inverter change. Overload is tolerated at 105-130% for 10 minutes, 130-150% for 1 minute and 150% and above for 10 seconds.

Battery voltage is 192 or 240 Vdc, float charge voltage 220 or 274 Vdc, cyclic charge voltage 230 or 288 Vdc and maximum charge current 4.0 A +/-10%; rated discharge currents are 47/38 A, 71/57 A and 95/76 A. Efficiency is above 89-90% on AC and above 86-88% in battery mode. Net weight is 28, 40 and 42 kg, size 568 x 250 x 575 mm and 615 x 250 x 575 mm (L x W x H), IP20, operation -10 to +40 C and altitude 1000 m. The page does not state that an external battery bank is included in the weight; the values are for the UPS cabinet.

Key points

  1. Three models: CPTH-2010 10 kVA/8 kW, CPTH-2015 15 kVA/12 kW, CPTH-2020 20 kVA/16 kW.
  2. Input 380 Vac 3-phase 5-wire; window 195-520 Vac (50% load), 305-478 Vac (100% load); 46-54 Hz.
  3. Input PF >=0.99, harmonic current <=5%; output single phase 220 Vac, output PF 0.8, crest factor 3:1.
  4. THD <2% on linear load and <4% on non-linear load; transfer time 0 ms.
  5. Overload: 105-130% for 10 min, 130-150% for 1 min, 150% and above for 10 s.
  6. Battery voltage 192/240 Vdc; float 220/274 Vdc; charge current 4.0 A; rated discharge current 47/38, 71/57, 95/76 A.
  7. Efficiency: AC >90/89/89%, battery mode >86/87/88%.
  8. Net weight 28, 40, 42 kg; 568-615 x 250 x 575 mm; IP20; -10 to +40 C; noise <65 dB.

Using it in design

  • With a 0.8 output power factor the 20 kVA model gives 16 kW; select load in kW.
  • The wide input window varies with load; at 100% load the lower limit is 305 Vac, so check load factor on weak mains.
  • Set the battery string voltage (192 or 240 Vdc) and float voltage by cell count and battery type; maximum charge current is only 4 A, so calculate recharge time for large battery banks.
  • The external battery bank is not in the weight; calculate floor loading separately for the cabinet and the batteries.
  • If parallel redundancy is needed, state the N+X option in the order code.

Who should read it

Designers and suppliers selecting 10-20 kVA UPSs with three-phase input and single-phase output.

Document contents

  1. Features
  2. AC input
  3. AC output
  4. Battery
  5. General parameters
  6. Protection functions

Publication details

Authors
Guangdong Zhicheng Champion
Publisher
Guangdong Zhicheng Champion
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Guangdong Zhicheng Champion Zhicheng Champion CPTH Series: Technical Parameters. Guangdong Zhicheng Champion. https://en.zhicheng-champion.com/UPS_detail/979827966599389184.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.