Technical guideFree to read2022

Bicker UPS-1000-B1 User Manual, revision 1, 22 July 2022

Bicker Elektronik

A manual for Bicker Elektronik's 600 W / 1000 VA line-interactive UPS-1000-B1, covering technical data, installation, operation and temperature-dependent power derating.

On this page

Overview

The manual describes a small line-interactive UPS with sine output, AVR (buck/boost) and microprocessor control. Input is 230 V AC at 47-65 Hz (50/60 Hz auto-detect) with an input voltage range of -20 to +24 percent. Efficiency in mains operation is about 97 percent. The AVR has two buck and two boost steps (extended buck +15 percent, buck +8, boost -8, extended boost -12.5).

Output of 600 W / 1000 VA applies at up to +40 C ambient. From +40 to +60 C a derating of 10 W per K applies, so at +60 C the maximum permitted output load is 400 W. The safety instructions repeat that derating must be observed. Operating temperature is 0 to +60 C and transport and storage -15 to +60 C.

The battery is a single 24 V / 8 Ah (12 cell) Cyclon module. Typical backup times at +20 C are about 14 minutes at half power (500 VA / 300 W) and about 4.5 minutes at full power. Charging reaches 90 percent in about 5 hours at up to 2.5 A (230 V AC, +25 C). Transfer time is typically 3 ms on blackout and 1 ms on brownout.

The rest of the manual covers communication (RS232, USB, UPSilon 2000 software), the LCD, load sensor and green mode, cold start, self-test, alarms and timer, plus connectors and the connection diagram. It contains German and English parts, and the device is a small 24 V single-module system that should not be compared directly with data-hall UPS units.

Key points

  1. Rated output 600 W / 1000 VA at up to +40 C ambient; sine output, crest factor 3:1.
  2. 10 W/K derating between +40 and +60 C; maximum permitted load at +60 C is 400 W.
  3. Input: 230 V AC, 47-65 Hz, voltage range -20 to +24 percent; mains-mode efficiency about 97 percent.
  4. AVR: extended buck +15 percent, buck +8, boost -8, extended boost -12.5.
  5. Battery: 24 V / 8 Ah, 12 cells; backup at +20 C is about 14 min at 500 VA / 300 W and about 4.5 min at 1000 VA / 600 W.
  6. Charging: about 5 hours to 90 percent, maximum charge current 2.5 A.
  7. Transfer time is typically 3 ms on blackout and 1 ms on brownout; overload alarm at 100-120 percent, shutdown at 120-190 percent.
  8. Size 18 x 22 x 46 cm (W x H x D), weight 15 kg, noise 40 dBA or less at 1 m.
  9. Safety EN62040-1, EMC EN62040-2; RS232 and USB interfaces.

Using it in design

  • For edge or enclosed-cabinet use, compute derating from ambient temperature: P = 600 W - 10 W/K x (T - 40 C).
  • Check that 4.5 minutes at full load is enough for controlled shutdown.
  • Compare the input voltage range and AVR steps with local mains quality.
  • Confirm that RS232 or USB and the UPSilon 2000 software fit the monitoring network architecture.
  • Classify the unit as a small 24 V single-module system; do not use it for critical data-hall backup.

Who should read it

Designers and field engineers selecting AC UPS units for small cabinets, edge points and industrial use.

Document contents

  1. Technical data
  2. Introduction and description
  3. Safety instructions
  4. Drawing
  5. General data (assembly, convection, connectors, connecting diagram)
  6. Operating (on, off, cold start, self test, alarm, charging, settings, LCD)

Publication details

Authors
Bicker Elektronik
Publisher
Bicker Elektronik
Year
2022
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bicker Elektronik (2022). Bicker UPS-1000-B1 User Manual, revision 1, 22 July 2022. Bicker Elektronik. https://www.bicker.de/media/pdf/b8/f6/f5/en_user_manual_ups-1000-b1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.