HITZINGER NBDK Diesel Dynamic UPS manufacturer presentation
HITZINGER (hosted by Riello Delta Power)
The 119-page NBDK presentation from Austrian manufacturer HITZINGER introduces diesel dynamic UPS systems with kinetic energy storage in twelve standard models from 150 kVA to 2500 kVA, with total system efficiency of about 94-96%, system MTBF above 1,000,000 hours and a 25-year design life.
On this page
Overview
The 2015 presentation describes the diesel dynamic UPS (DDUPS) family of HITZINGER, a company founded in Linz in 1946, and is hosted on a distributor site. The opening part covers company history and production facilities. It then goes through the mechanical design of the NBDK system, its electrical operation and energy flow, control and monitoring, system configurations, maintenance and reference projects. The core argument is a move away from lead-acid batteries and power electronics towards kinetic energy storage and rotating electrical machines, with the diesel engine as the component common to both approaches.
An NBDK unit combines a radiator, diesel engine, electromagnetic clutch, synchronous machine and the kinetic energy module called KIN on one base frame. In normal operation the load is fed from the mains through a coupling choke and the synchronous machine runs as a motor. In the KIN module the inner rotor turns at 1500 rpm and the squirrel-cage outer rotor at 2700 rpm. When the mains fails, the magnetic field of the inner rotor brakes the outer rotor and holds the alternator speed constant, with a frequency variation of at most 1%. The diesel starts on its electric starter and the clutch closes at about 800 rpm.
The standard rating list has twelve steps: NBDK 1/10-150, 250, 350, 500, 625, 800, 1000, 1250, 1500, 1750, 2000 and 2500 kVA, in 50 Hz and 60 Hz versions and at voltages up to 11 kV. Guaranteed values include a static voltage tolerance of ±1% in mains operation and, for a change of nominal load at cos φ 0.8, a dynamic deviation of ±10% with a recovery time of 0.3 s. The choke limits fault current during an input short circuit, during which the output voltage drops by 10-15%.
The configuration section maps parallel, isolated, isolated parallel redundant and STS-based arrangements to Tier I-IV requirements and summarises end-user availability as 99.67% for Tier I, 99.75% for Tier II, 99.98% for Tier III and 99.99% for Tier IV. In the environmental comparison, a 2000 kVA static UPS is said to produce 3 x 33,000 kg of battery waste over 20 years for a 15-minute autonomy, against less than 100 kg of bearing steel for the dynamic system. The maintenance plan is divided into qualification levels M1, M2 and M3.
Key points
- Twelve standard models: NBDK 1/10-150, 250, 350, 500, 625, 800, 1000, 1250, 1500, 1750, 2000 and 2500 kVA; 50 Hz and 60 Hz.
- Voltage up to 11 kV; system MTBF above 1,000,000 hours; 25-year design life.
- Total system efficiency about 94-96%.
- KIN module: inner rotor 1500 rpm, outer rotor 2700 rpm; frequency variation at mains failure at most 1%; completely brushless design.
- Guaranteed values: static voltage tolerance ±1%; dynamic deviation ±10% at a change of nominal load, recovery time 0.3 s.
- Diesel start: electric starter, electromagnetic clutch closes at about 800 rpm; in the redundant procedure the KIN module accelerates the diesel to nominal speed.
- During an input short circuit the choke limits fault current; output voltage drop is 10-15%.
- Tier summary: Tier I 99.67% (28.8 h downtime), Tier II 99.75% (22.0 h), Tier III 99.98% (1.6 h), Tier IV 99.99% (0.8 h).
- Waste comparison: 3 x 33,000 kg of batteries over 20 years for a 2000 kVA static UPS; less than 100 kg of steel for the dynamic UPS.
- Replacing the KIN module inner bearings is an M3-level maintenance task with a theoretical interval of 5 years.
Using it in design
- When weighing a diesel dynamic UPS against a static UPS with batteries and a separate generator, count the removal of the battery room, battery cooling and battery replacement cost, and the fact that the diesel must take load within seconds at every outage.
- Choose unit ratings from the 150-2500 kVA steps; on large campuses, study isolated parallel bus arrangements with medium-voltage versions up to 11 kV.
- Compare the redundancy target with the Tier mapping in the presentation: N parallel for Tier I, N+1 parallel for Tier II, two-path isolated parallel arrangements for Tier III and above.
- Check the IT load's voltage tolerance against the ±10% dynamic deviation and 0.3 s recovery time, and its frequency tolerance against 1%.
- Design the machine room like a generator room for fuel, exhaust, ventilation and vibration; the unit is cooled by ambient air and needs no air conditioning.
- Define the M1, M2 and M3 levels and the bearing replacement interval in the maintenance contract.
Who should read it
Electrical designers choosing uninterruptible power architectures for large data centres and industrial plants, and managers making the investment decision.
Document contents
- Company History, Organisation, Profile and Global Network
- NBDK IT Power Systems: Mechanical, Features and Benefits
- Why DDUPS?
- Product Description and KIN module operation
- Standard Ratings
- Guaranteed values
- Kinetic Energy Module
- Electrical Operation and Energy Flow
- The Magic Choke
- Description of Operation
- Control and Monitoring
- System Configurations
- Hitzinger and on-site service, maintenance, repair
- Summary and references
Publication details
- Authors
- HITZINGER (hosted by Riello Delta Power)
- Publisher
- HITZINGER (hosted by Riello Delta Power)
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HITZINGER (hosted by Riello Delta Power) HITZINGER NBDK Diesel Dynamic UPS manufacturer presentation. HITZINGER (hosted by Riello Delta Power). https://www.riello-deltapower.pl/uploads/file/84/2084/DDUPS_Upower_ang.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.