Lever industrial AC UPS product information

Lever Srl

Lever Srl's heavy-duty industrial AC UPS family: DPS-TT three-phase output 5-600 kVA and DPS-TM single-phase output 5-160 kVA, VFI-SS-111 class, SCR rectifier and input/output isolation transformers.

On this page

Overview

Lever presents on-line heavy-duty UPS units designed for oil and gas and industrial engineering applications. The page shows two models: DPS-TT (three-phase input and output, 5-600 kVA) and DPS-TM (three-phase input, single-phase output, 5-160 kVA). The manufacturer states that the units are fully customisable and are configured to the project specification rather than sold as standard discrete order models, so the page defines the family scope.

The technical build consists of an SCR 6- or 12-pulse rectifier, an IGBT full-bridge inverter, dual-microprocessor digital control and an SCR static switch with a transfer time under 2 ms. The rectifier, inverter and bypass are designed as removable modular units. Battery voltage is 110, 220 or 360 Vdc, with three programmable charge levels (float, boost and commissioning). The UPS class is VFI-SS-111 and N+1 redundant configuration is available.

The manufacturer lists as advantages operation with all battery types, severe environmental conditions, third-party type testing to IEC 62040-1, -2, -3 and -4, high short-circuit capacity for selectivity of downstream protection, and full galvanic isolation through standard input and output transformers. There are three operating modes: manual bypass, on-line and line-interactive, offered to reduce operating cost and environmental impact. Output AC voltage THD is under 1% on linear load and DC output ripple under 1% RMS.

The cabinet is modular at 2200 mm height, protection goes up to IP65, ambient operating temperature reaches 55 C and explosion-proof (Ex) solutions are offered. Communication is Ethernet, Modbus and an SPDT dry-contact module configurable from a PC; an HMI display shows measurements, alarms and the synoptic diagram. Applications are offshore and onshore petrochemical plants, pipelines, power generation, water treatment and desalination, and process industries such as chemicals, mining, steel and paper.

Key points

  1. DPS-TT: three-phase output 5-600 kVA; DPS-TM: single-phase output 5-160 kVA.
  2. UPS class VFI-SS-111; N+1 redundant configuration available.
  3. SCR 6- or 12-pulse rectifier; IGBT full-bridge inverter; dual-microprocessor digital control.
  4. SCR static switch transfer time under 2 ms.
  5. Battery voltage 110, 220 or 360 Vdc; float, boost and commissioning charge programmable.
  6. Output AC THD under 1% on linear load; DC ripple under 1% RMS.
  7. Standard input and output isolation transformers; high short-circuit capacity for downstream selectivity.
  8. Three modes: manual bypass, on-line, line-interactive.
  9. 2200 mm modular cabinet, up to IP65, ambient up to 55 C, Ex options.
  10. Compliance with IEC 62040-1, -2, -3 and -4, third-party type tested.

Using it in design

  • In the project specification, state the UPS class VFI-SS-111 and the required redundancy level (N or N+1).
  • For downstream protection selectivity studies, request the UPS short-circuit capacity from the manufacturer.
  • Match battery voltage (110, 220, 360 Vdc) and battery type to the DC design of the heavy-duty project.
  • Tie ambient temperature, IP65 and Ex requirements to the hazardous-area and environment classification documents.
  • As there is no standard catalogue model, take capacity, size and weight from a project-specific manufacturer quotation.

Who should read it

Electrical engineers specifying heavy-duty UPS in oil and gas, power and process industries.

Document contents

  1. Heavy-duty AC UPS DPS-TT (three-phase output 5-600 kVA)
  2. Heavy-duty AC UPS DPS-TM (single-phase output 5-160 kVA)
  3. Product card, applications, advantages, technical characteristics

Publication details

Authors
Lever Srl
Publisher
Lever Srl
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lever Srl Lever industrial AC UPS product information. Lever Srl. https://www.lever.it/ups-ac-industriali-heavyduty

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.