RUSELT: Uninterruptible Power Supply Catalogue and IDP-3 10-120 kVA Model Table
Original title RUSELT: Источники бесперебойного питания; ИДП-3 10–120 кВА
RUSELT
RUSELT (Elektromash) catalogue: double-conversion UPS series from 1 kVA to 1 MW; the IDP-3 spans 10-120 kVA with 0.99 input power factor, 96 percent double-conversion and up to 98 percent Smart ECO efficiency.
On this page
Overview
The document is the uninterruptible power supply catalogue of the Russian RUSELT brand (manufacturer AO Elektromash). It introduces five double-conversion AC UPS series from 1 kVA to 1 MW, plus the AOUT and ShUOT series of operational DC current systems. The series include the IDP-2 (10 to 1000 kVA), IDP-3 (10 to 120 kVA) and modular IDP-4 (20 kVA to 1 MW). Reference projects cover energy, oil and gas, and nuclear-industry sites.
The IDP-3 page tabulates 10, 15, 20, 30, 40, 50, 60, 80, 100 and 120 kVA models. For every model active power equals the kVA rating (kW = kVA). Input is 220-240/380-415 Vac (-20/+15 percent, 3 phase + neutral), 50/60 Hz ±5 percent, with input power factor of 0.99 at 10 percent load and above; a 3-level IGBT rectifier is used and input THDi is about 1.0 to 1.5 percent at 100 percent load. Output voltage is ±1 percent static and ±2 percent dynamic (100-0-100 percent load step), with THDv below 0.5 percent on linear and below 1.5 percent on non-linear load.
Efficiency approaches 96 percent in double-conversion and reaches up to 98 percent in Smart ECO mode (supply through the static bypass, transfer time below 3 ms). Overload is 10 minutes at 125 percent, 5 minutes at 125-135 percent and 20 ms above 150 percent; the static bypass takes 400 percent for 10 seconds. The IDP-3 runs up to 16 units in parallel, can serve as a 50 to 60 Hz (or reverse) frequency converter, includes an integrated static and manual service bypass, and can be built in an IP54 enclosure on request.
The catalogue is a product introduction; it has no model-specific battery configuration, internal architecture detail or independent test report. The IDP-3 comes in two cabinet groups (460 × 805 × 1190 mm and 880 × 770 × 1660 mm); mass is not given in this table.
Key points
- IDP-3: 10, 15, 20, 30, 40, 50, 60, 80, 100 and 120 kVA models; active power equals kVA (kW = kVA).
- Input 220-240/380-415 Vac (-20/+15 percent), 50/60 Hz ±5 percent, input power factor 0.99 (load 10 percent and above).
- Input THDi: about 1.0 to 1.5 percent at 100 percent load; 5 to 6 percent at 10 percent load (depending on supply quality).
- Output voltage ±1 percent static, ±2 percent dynamic; THDv below 0.5 percent linear, below 1.5 percent non-linear.
- Overload: 10 min at 125 percent, 5 min at 125-135 percent, 20 ms above 150 percent.
- Battery-mode efficiency (100 percent linear load) runs from 94.5 percent (10 kVA) to 96.9 percent (80 kVA); Smart ECO mode 95.0 to 98.4 percent.
- Smart ECO transfer time below 3 ms; normal bypass transfer is 0 ms.
- Up to 16 units in parallel; frequency converter mode; optional IP54.
- Cabinet sizes 460 × 805 × 1190 mm and 880 × 770 × 1660 mm.
Using it in design
- With active power equal to kVA in these series, check load in kW; with a 0.99 power factor, calculate input current from the load.
- Compare the sub-3 ms transfer of Smart ECO mode with load tolerance; for critical data-hall load prefer normal double-conversion mode.
- For redundancy, use the parallel structure of up to 16 units and note that frequency converter mode disables the bypass functions.
- Add the IP54 option to the specification for harsh environments.
- Check input THDi at low load (about 5 to 6 percent) for generator compatibility.
Who should read it
Designers and specification engineers selecting 10-120 kVA double-conversion UPS in Russian and neighbouring markets.
Document contents
- About RUSELT and product series
- UPS topology and communication options
- IDP-3: general features and advantages
- IDP-3 functional features (Smart ECO, bypass, paralleling, frequency converter)
- IDP-3 technical specifications and configuration
- IDP-4 modular series
Publication details
- Authors
- RUSELT
- Publisher
- RUSELT
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
RUSELT RUSELT: Источники бесперебойного питания; ИДП-3 10–120 кВА. RUSELT. https://www.ruselt.ru/catalogs/ibp.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.