YorPower YP-Captuo RT 6-10 kVA UPS Datasheet
Original title YorPower YP-Captuo RT 6–10 kVA datasheet
YorPower
The YorPower YP-Captuo RT is a 6000-10000 VA single-phase rack UPS with equal kVA and kW, a 110-280 Vac input, up to 94% efficiency in VFI mode and 98% in ECO mode, and up to 4 units in 3+1 parallel redundancy.
On this page
Overview
The datasheet presents the YorPower (UK) Captuo RT family from 6000 VA to 10000 VA. The table has three model columns: 6000, C 6000 and 10000. In all three, power in VA and W is equal (6000/6000 and 10000/10000), so the output power factor is 1. Rated input voltage is 110-280 Vac, frequency 45-70 Hz and input power factor 0.99 or better. Output is selectable at 200/208/220/230/240 Vac and 50/60 Hz, with pure sine and a crest factor of 3:1.
Output voltage THD on linear load is 2% and voltage stability is +/-1%, with free-running frequency stability under 0.2%. Efficiency is up to 94% in VFI mode and up to 98% in ECO mode. Multi-mode operation covers VFI, ECO and constant voltage constant frequency (CVCF) output. With the parallel kit up to 4 units work together, giving 3+1 redundancy. The battery is 12 V VRLA AGM, charging time is 4 hours to 90%, runtime depends on external battery cabinets, and the C 6000 model has internal batteries while the other two need external batteries.
Physically the units have a 440 x 680 mm footprint with heights of 88, 132 and 176 mm; battery expansion modules are 440 x 685 mm with 88 or 132 mm height. Operation is 0-40 C, below 1000 m without derating and with 1% derating per 100 m above; noise is under 60 dBA at 1 m. Built-in ports are USB, EPO and a remote on/off contact, with slots for optional cards: SNMP, RS232, RS485 Modbus and dry relay contacts. Standards are IEC EN 62040-1, -2 and -3, and marking is CE and UKCA.
Key points
- Three columns: 6000, C 6000 and 10000; power 6000 VA/6000 W and 10000 VA/10000 W (PF 1).
- Input 110-280 Vac, 45-70 Hz, PF >=0.99; output 200/208/220/230/240 Vac selectable, 50/60 Hz.
- THD 2% on linear load, voltage stability +/-1%, crest factor 3:1, pure sine.
- Efficiency up to 94% in VFI mode and 98% in ECO mode; modes VFI, ECO and CVCF.
- Parallel kit allows up to 4 units, 3+1 redundancy; hot-swappable batteries; cold start.
- C 6000 has internal batteries and the other two need external batteries; charging time 4 hours to 90%.
- Operation 0-40 C; 1% derating per 100 m above 1000 m; noise <60 dBA.
- Standards IEC EN 62040-1/-2/-3; CE and UKCA; USB, EPO, remote on/off.
Using it in design
- With output PF 1, the 10 kVA model delivers 10 kW; size server load without a kVA/kW gap.
- Include the parallel kit and the 3+1 arrangement (up to 4 units) in the design for redundancy.
- Determine internal or external battery need by model; runtime depends on the number of external battery cabinets.
- Compare ECO mode, which gives up to 98% efficiency but runs the load with reduced conditioning, against load sensitivity.
- For installations above 1000 m, apply the 1% per 100 m derating.
Who should read it
Designers selecting 6-10 kVA rack UPSs for small data rooms and edge sites.
Document contents
- Product summary and additional information
- Input
- Output
- Efficiency
- General
- Battery
- Environmental parameters
- Connectivity
- Regulations
Publication details
- Authors
- YorPower
- Publisher
- YorPower
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
YorPower YorPower YP-Captuo RT 6–10 kVA datasheet. YorPower. https://yorpower.com/wp-content/uploads/2024/11/YP-Captuo-RT.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.