Technical guideFree to read2018

Alcad XHP range brochure: PDF p.4

Alcad

Alcad's 8-page XHP brochure (document X3.0.E.0117, January 2017 edition) presents low-maintenance nickel-cadmium cells built for UPS and engine-starting duty. The table on page 4 gives dimensions and weights for 23 cell types with C5 capacities from 11 Ah to 320 Ah.

On this page

Overview

The brochure covers Alcad's XHP range: vented Ni-Cd cells with sintered positive and plastic-bonded negative electrodes in alkaline electrolyte. The manufacturer positions the range for UPS, engine starting and emergency back-up duties and states a service life of more than 20 years. The topping-up interval is given as 10 years under single-rate charging. According to the text, AC ripple, over-discharge, voltage reversal and high overcharge currents do not harm the cell, and because no corrosive fumes are produced the cells can stand next to sensitive electronic equipment.

The capacity and dimensions table on page 4 is the core of the range. For 23 cell types from XHP 11 to XHP 320 it lists rated capacity (C5) at the 5-hour rate to an end voltage of 1.00 V per cell, length, width and overall height per cell, approximate weight, and the volume of free electrolyte above the plates. The values describe a single cell, not a battery string or cabinet. Nominal discharge voltage is 1.2 V per cell, so the number of cells for a given DC bus is calculated separately.

Charging data are defined for 20 °C to 25 °C. In systems that use boost charging, the maintenance float voltage is 1.40 ± 0.01 V and the boost voltage is 1.45 ± 0.01 V; in systems without boost, the float voltage is 1.41 ± 0.01 V. Standard constant-current charging is 0.2 × C5 amperes for 8 hours, and constant-voltage charging needs no current limit. The cell data also include DC internal resistance (40 / C5 mΩ) and a short-circuit current relation.

The following pages tabulate the current available for stationary applications at four end voltages (1.00, 1.05, 1.10 and 1.14 V per cell) for durations from 8 hours down to 1 second, and for engine starting at end voltages of 0.65 and 0.85 V per cell over seconds and minutes. The stationary tables show performance after prolonged float charge and apply at 20 °C ± 5 °C. The cells meet the requirements of IEC 60623. The usual operating range is -20 °C to +50 °C, with tolerance of -50 °C to +70 °C for short periods.

Key points

  1. 23 cell types from XHP 11 to XHP 320; rated capacity is the C5 value (5-hour discharge to 1.00 V per cell). Nominal discharge voltage is 1.2 V per cell.
  2. Example sizes: XHP 11 46.5 × 86 × 196 mm, 1.0 kg; XHP 100 78 × 166 × 339 mm, 6.1 kg; XHP 320 198 × 166 × 339 mm, 16.5 kg (length × width × height).
  3. Float voltage: 1.40 ± 0.01 V with boost, 1.41 ± 0.01 V without boost; boost voltage 1.45 ± 0.01 V (20 °C to 25 °C).
  4. Standard constant-current charge is 0.2 × C5 A for 8 hours; DC internal resistance is 40 / C5 mΩ.
  5. XHP 100 delivers 297 A for 15 minutes, 417 A for 5 minutes and 568 A for 1 minute to 1.00 V per cell; at an end voltage of 1.10 V per cell the 15-minute value falls to 193 A.
  6. Even partially discharged, the cells can supply repeated high currents of up to 20 times nominal capacity.
  7. Operating temperature is normally -20 °C to +50 °C, and -50 °C to +70 °C for short periods.
  8. Terminals: M10 for XHP 11 to XHP 80, M12 for XHP 90 to XHP 150, 2 × M12 for XHP 170 to XHP 320.
  9. The flame-retardant (F) option adds 1.5% to the dimensions; the cells comply with IEC 60623.

Using it in design

  • Calculate the cell count from the DC bus voltage window: 1.2 V per cell nominal, 1.40 to 1.41 V per cell on float and the chosen end voltage (1.00 to 1.14 V per cell) all have to fit the rectifier and inverter limits.
  • For UPS autonomy, select the cell type by comparing load current with the duration column in the table for the relevant end voltage; available current falls markedly as the end voltage rises.
  • Work out rack layout and floor loading from the per-cell dimensions and weight multiplied by the number of cells in the string, and add 1.5% to the dimensions for the F option.
  • If the battery room is outside 20 °C to 25 °C, take charging-voltage and performance corrections from the manufacturer's sizing software (BaSics).
  • Plan topping-up at a 10-year interval for single-rate charging in the maintenance schedule and keep the electrolyte level marks visible for service access.

Who should read it

Electrical designers sizing Ni-Cd batteries for UPS, generator starting and switchgear control systems, and engineers laying out battery rooms.

Document contents

  1. Low maintenance, high performance Ni-Cd batteries
  2. XHP Range
  3. Rapid charging characteristics, Capacity, Charging voltages, Cell data
  4. Capacity and dimensions
  5. Terminals
  6. Data for stationary applications (final voltage 1.00, 1.05, 1.10 and 1.14 V/cell)
  7. Data for engine starting applications (final voltage 0.65 and 0.85 V/cell)

Publication details

Authors
Alcad
Publisher
Alcad
Year
2018
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Alcad (2018). Alcad XHP range brochure: PDF p.4. Alcad. https://eurobathellas.gr/image/catalog/pdf/alcad/alcad-xhp.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.