CELNED CHL high-rate long-life VRLA: model table
CELNED
A product page from the Dutch supplier CELNED listing the CHL series of high-rate long-life VRLA monoblocs: five 12 V models, C20 capacities from 20 to 230 Ah, weights from 6.80 to 69 kg and gas recombination above 99%.
On this page
Overview
The page presents CELNED's CHL (High Rate Long Life) series through general features, applications and a model table. The series consists of valve-regulated lead-acid (VRLA) monoblocs with AGM separators. Positive and negative plates are lead-calcium alloy, and a radial grid design gives high energy density. Low-pressure gas recombination exceeds 99%. The case is flame-retardant ABS (UL 94-V0) and the product is a recognised component under UL 1778. Shelf life is six months.
The application list covers UPS and EPS systems, power systems, telecommunications, emergency lighting and control systems, and solar and wind storage. The model table has five products: CHL12V700-FR, CHL12V2500-FR, CHL12V3400-FR, CHL12V4400-FR and CHL12V6350-FR. Each row gives nominal voltage, nominal C20 capacity (Ah), length, width, height and total height in millimetres and inches, terminal type, and approximate weight in kilograms and pounds.
In three rows the capacity and length columns carry the same number: 91 Ah and 91 mm for CHL12V2500-FR, 110 Ah and 110 mm for CHL12V3400-FR, and 165 Ah and 165 mm for CHL12V4400-FR. In those rows the width column shows 258, 328.5 and 340 mm. The CHL12V700-FR row lists a length of 435 mm and a weight of 6.80 kg against a capacity of 20 Ah. Mechanical dimensions should therefore be confirmed from the model datasheet before ordering.
The numbers in the model names (700, 2500, 3400, 4400, 6350) are not explained in the table, and the page gives no constant-power discharge values, W/cell tables by duration, internal resistance, charging voltage or design life in years. The terminal is M5 on the smallest model and an M8 insert on the others. The page serves to establish the family's identity, C20 capacities and weights; a UPS runtime calculation requires the detailed datasheets.
Key points
- Series: CHL, high-rate long-life AGM VRLA; nominal voltage 12 V.
- CHL12V700-FR: 20 Ah (C20), 6.80 kg, M5 terminal.
- CHL12V2500-FR: 91 Ah (C20), 24.5 kg, total height 215 mm, M8 terminal.
- CHL12V3400-FR: 110 Ah (C20), 32.5 kg, total height 220 mm.
- CHL12V4400-FR: 165 Ah (C20), 41.5 kg, total height 286.5 mm.
- CHL12V6350-FR: 230 Ah (C20), 526 x 238 x 246 mm, 69 kg.
- Gas recombination above 99%; UL 94-V0 flame-retardant ABS case; UL 1778 recognised component.
- Six-month shelf life; lead-calcium plates with a radial grid.
- In three rows the length column shows the same number as the capacity (91, 110, 165).
Using it in design
- Use the C20 capacity in the catalogue entry and request the constant-power discharge table from the supplier for UPS sizing.
- Confirm length and width from the model datasheet before laying out battery cabinets; the table repeats the capacity figure in the length column in three rows.
- Use block weight for floor and rack loading: from 24.5 kg (91 Ah) to 69 kg (230 Ah).
- Write the UL 94-V0 case and UL 1778 component recognition into the specification as acceptance criteria.
- Reflect the six-month shelf life in the delivery and commissioning schedule, and plan a refresh charge for batteries held in storage.
Who should read it
Electrical designers selecting UPS battery strings, engineers laying out battery cabinets, and procurement teams.
Document contents
- General Features
- Application
- Model table
Publication details
- Authors
- CELNED
- Publisher
- CELNED
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CELNED CELNED CHL high-rate long-life VRLA: model table. CELNED. https://celned.com/celned-high-rate-long-life-chl
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.