Technical guideFree to readYear not stated

DELTA HRL 12-7.2 X technical information: p.2

DELTA Battery (ENERGON)

A two-page technical information sheet from DELTA Battery (ENERGON) for the HRL 12-7.2 X AGM VRLA battery: 12 V, 7.20 Ah at the 10-hour rate, 56.4 W per cell in a 5-minute constant-power discharge at 25 °C (1.60 V/cell), 22 mΩ internal resistance and a 12-year service life.

On this page

Overview

The sheet is in Russian and belongs to the HRL X series of DELTA industrial batteries, a brand sold on the Russian market since 2001. The series consists of sealed, maintenance-free lead-acid (VRLA) batteries with gas recombination, built with AGM technology. The first page lists applications: mobile operator and internet provider infrastructure, UPS systems, lifts, processing centres and data centres. Manufacturing techniques named include casting grids in an inert gas atmosphere, robotic welding, and additives in the paste and the electrolyte.

The second page gives the model's numerical data. Nominal voltage is 12 V with 6 cells. Nominal capacity at 25 °C is defined for three discharge durations: 7.20 Ah at 10 hours (0.72 A, 1.80 V/cell), 5.80 Ah at 5 hours (1.16 A, 1.75 V/cell) and 5.19 Ah at 1 hour (5.19 A, 1.65 V/cell). Internal resistance of a fully charged battery is 22 mΩ, and maximum discharge current is 108 A for 5 seconds. Self-discharge is 3% per month at 20 °C.

The constant-current and constant-power discharge tables cover durations from 5 minutes upward for five end voltages between 1.60 and 1.80 V/cell. At 1.60 V/cell the constant-power values are 56.4 W at 5 minutes, 37.8 W at 10 minutes, 32.4 W at 15 minutes, 17.6 W at 30 minutes and 10.4 W at 1 hour (per cell). At 1.80 V/cell the same durations give 47.4, 31.2, 27.5, 15.0 and 8.85 W. A note states that the values are averages over three control cycles and are not default nominal values.

Charging parameters: maximum charging current 2.16 A; 2.35 to 2.40 V/cell in cyclic use (temperature compensation 30 mV/°C) and 2.27 to 2.30 V/cell in float use (20 mV/°C). Service life is given as 12 years in the technical table, while the series introduction refers to a life of up to 15 years. Cycle life is 340 cycles at 100% depth of discharge, 630 at 50% and 1400 at 30%. The case measures 151 x 65 x 94 mm (100 mm total height), weighs 2.6 kg and has F2 terminals.

Key points

  1. Model HRL 12-7.2 X: 12 V, 6 cells, AGM VRLA; article number 4614010610012.
  2. Nominal capacity (25 °C): C10 7.20 Ah (1.80 V/cell), C5 5.80 Ah (1.75 V/cell), C1 5.19 Ah (1.65 V/cell).
  3. Constant-power discharge at 1.60 V/cell: 56.4 W at 5 min, 37.8 W at 10 min, 32.4 W at 15 min, 17.6 W at 30 min, 10.4 W at 1 hour (per cell).
  4. Constant-power discharge at 1.80 V/cell: 47.4 W at 5 min, 31.2 W at 10 min, 27.5 W at 15 min, 15.0 W at 30 min (per cell).
  5. Constant-current discharge at 1.60 V/cell: 30.1 A at 5 min, 19.8 A at 10 min, 17.6 A at 15 min.
  6. Internal resistance 22 mΩ (25 °C, fully charged); maximum discharge current 108 A (5 s); maximum charging current 2.16 A.
  7. Float voltage 2.27...2.30 V/cell (20 mV/°C); cyclic charge 2.35...2.40 V/cell (30 mV/°C).
  8. Service life 12 years; cycle life 340 cycles at 100% DOD, 630 at 50%, 1400 at 30%.
  9. Dimensions 151 x 65 x 94 mm (100 mm total height, ±2 mm); weight 2.6 kg (±3%); F2 terminal.
  10. Operating temperature: discharge -20...60 °C, charge -10...60 °C, storage -20...60 °C; self-discharge 3% per month at 20 °C.

Using it in design

  • Calculate UPS runtime from the constant-power table: divide load power by the number of cells and read the duration from the row matching the UPS end-of-discharge voltage.
  • Take into account that table values are averages over three cycles, and add design margin for ageing and temperature.
  • Set the charger to 2.27...2.30 V/cell in float use with 20 mV/°C temperature compensation, and limit charging current to 2.16 A.
  • Record the 22 mΩ internal resistance as the commissioning reference and compare periodic measurements against it.
  • Use the 12-year figure from the technical table for life planning, and keep battery-room temperature around 25 °C.
  • When replacing internal batteries in small UPSs, match the 151 x 65 x 94 mm size and F2 terminal to the existing blocks.

Who should read it

Electrical designers selecting batteries for small and medium UPSs, engineers calculating battery runtime, and maintenance teams.

Document contents

  1. Описание серии и сферы применения
  2. Технологии производства
  3. Преимущества
  4. Разряд постоянным током, А (при 25 °С)
  5. Разряд постоянной мощностью, Вт/эл-т (при 25 °С)
  6. Зарядные параметры
  7. Рабочий диапазон температур
  8. Габариты
  9. Технические характеристики
  10. Конструкция батареи

Publication details

Authors
DELTA Battery (ENERGON)
Publisher
DELTA Battery (ENERGON)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

DELTA Battery (ENERGON) DELTA HRL 12-7.2 X technical information: p.2. DELTA Battery (ENERGON). https://pim.energon.ru/storage/13052/TI_DELTA_HRL_X_HRL_12-7_2_X_RU.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.