Technical guideFree to readYear not stated

ECELL EC series specification table on EC12-7 product page

ECELL Batteries International

The EC12-7 product page from ECELL Batteries International publishes the 12 V 7 Ah (20-hour rate) sealed AGM battery together with a 48-model table of the EC series: 4, 6, 12 and 24 V monoblocs from 1.3 Ah to 28 Ah, with dimensions and weight for each model.

On this page

Overview

The page presents the EC12-7, the representative model of the EC series that ECELL uses for small-capacity UPS batteries. The EC12-7 is a valve-regulated lead-acid (VRLA) AGM monobloc with a 12 V nominal voltage and 7.0 Ah capacity at the 20-hour discharge rate. Internal resistance when fully charged is about 25 mΩ, the standard terminal is Faston 187 (F1) or 250 (F2), and the operating temperature in discharge runs from -15 °C to 50 °C. The page gives a body size of 151 x 65 x 94 mm, a total height of 100 mm and a weight of 2.05 kg.

The main value of the page is that it gathers the whole EC family in one table. The table has columns for model name, voltage, capacity at the 20-hour rate, dimensions with a ±1.5 mm tolerance and weight. The 4 V group has 4.5 and 7.5 Ah; the 6 V group runs from 1.3 Ah to 12 Ah; the 12 V group from 1.3 Ah to 28 Ah; and the 24 V group has 3.5, 4 and 5 Ah models. Weights range from 0.29 kg (EC6-1.3) to 8.2 kg (EC12-28). High-rate HR variants and L, A, B and H variants with different cases at the same capacity appear as separate rows.

On construction, the page states that 99.996% pure lead and lead-calcium grids are used, that self-discharge stays below 3% per month at 25 °C and that design life in float service is 5-10 years depending on capacity. The batteries are sealed and maintenance-free; they need no water addition and the spill-proof build allows installation in different orientations. The page states that the EC12-7 is used in critical UPS systems and in security and access control panels and is engineered for good performance at high discharge rates.

The table gives only the C20 rated capacity; the constant-power (W per cell) discharge tables needed for UPS sizing, the 10 or 15 minute high-rate performance and the charge voltages are absent from this page. The series is offered as monobloc cells; no ready-made battery cabinet or rack solution is defined. In a data centre, batteries of this size serve rack-mount small UPSs, security panels and auxiliary systems more than the main UPS battery plant.

Key points

  1. EC12-7: 12 V, 7.0 Ah (20-hour rate), internal resistance about 25 mΩ fully charged, terminal Faston 187 (F1) / 250 (F2).
  2. EC12-7 dimensions 151 x 65 x 94 mm, total height 100 mm, weight 2.05 kg; dimensional tolerance ±1.5 mm.
  3. Operating temperature in discharge is -15 °C to 50 °C.
  4. The EC series table holds 48 models: 4 V (4.5 and 7.5 Ah), 6 V (1.3-12 Ah), 12 V (1.3-28 Ah) and 24 V (3.5-5 Ah).
  5. Largest 12 V models: EC12-24 at 7.6 kg, EC12-26 at 7.9 kg, EC12-28 at 8.2 kg; the EC12-28 case is 166 x 175 x 125 mm.
  6. Self-discharge is below 3% per month at 25 °C.
  7. Design life in float service is 5-10 years depending on capacity.
  8. All models are VRLA AGM.

Using it in design

  • When planning battery replacement in small rack-mount UPSs, match the case size (for example 151 x 65 x 94 mm) and terminal type (F1 or F2) from the table.
  • Do not calculate autonomy from the C20 capacity; for a 5-30 minute UPS discharge, request the constant-power table from the manufacturer's model datasheet.
  • Tie the battery life assumption to the lower end of the 5-10 year range and to a 25 °C ambient, and write the replacement interval into the maintenance plan.
  • For spare batteries held in storage, set the refresh-charge interval with the up to 3% per month self-discharge in mind.
  • Calculate battery tray and shelf loading from model weight times block count (for example 32.8 kg for 16 EC12-7 blocks).

Who should read it

Electrical designers selecting batteries for small UPSs and auxiliary systems, and operations and maintenance teams planning battery replacement.

Document contents

  1. EC12-7 product introduction
  2. Technical specifications
  3. Key features
  4. EC series model table
  5. FAQ

Publication details

Authors
ECELL Batteries International
Publisher
ECELL Batteries International
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ECELL Batteries International ECELL EC series specification table on EC12-7 product page. ECELL Batteries International. https://www.ecellbatteries.com/ecell-ec12-7-12v-7ah-sla-agm-battery-for-ups/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.