Technical guideFree to readYear not stated

GAZ Lomain Single Cell Ni-Cd Battery Range: KGM single cell table

Original title GAZ Lomain Single Cell Ni-Cd Battery Range: PDF p.5 / printed pp.8–9

GAZ Energy

The Lomain brochure from GAZ (Geräte- und Akkumulatorenwerk Zwickau) presents low-maintenance pocket-plate Ni-Cd single cells built to IEC 62259; the KGM range covers 11 Ah to 1560 Ah in 46 steps and needs at most one water top-up over a design life of more than 20 years.

On this page

Overview

The eight-page brochure describes Lomain, the single-cell nickel-cadmium battery family of German manufacturer GAZ. The cells use a pocket-plate electrode design and are built to IEC 62259 and EU battery regulations. With a low-pressure flame-arresting vent plug, a fleece separator and a large electrolyte reserve, the manufacturer expects zero or at most one water top-up over a design life of more than 20 years in normal operation. Typical applications listed include UPS systems, emergency lighting, communications, oil and gas facilities and railway signalling.

The family splits into two plate types. KGL has thicker plates for low-rate discharges longer than 3 hours and covers 10-1775 Ah in 96 steps. KGM is optimised for medium and mixed loads and offers 11-1560 Ah in 46 steps. The ideal discharge time for KGM is between 30 minutes and 3 hours, although the cell can also serve discharges as short as 1 minute. That window overlaps with most data-centre UPS autonomies.

The KGM table gives two capacity figures per cell: the 5-hour C5 capacity to IEC 62259 and the capacity to DIN 40771. The text states that the IEC figure is defined to an end voltage of 1.00 V per cell and the DIN figure to 1.15 V per cell, at 20 ± 5 °C, while both column headers in the table carry a 1.0 V label. For KGM 11 P the values are 12 and 11 Ah, and for KGM 1560 P they are 1735 and 1560 Ah. The table also lists cell dimensions, number of poles, electrolyte volume, filled weight and internal resistance.

Charging recommendations are given per cell: float 1.40-1.42 V, boost for KGM 1.44-1.46 V, single-level charging 1.43-1.44 V, with a current limit of 0.1 It A. Float current is 1 to 2 mA per Ah. The manufacturer reports that after an outage KGM cells regain 85 ± 5% of rated capacity in 8 to 9 hours at 1.46 ± 0.01 V per cell and 20 °C. The document is the manufacturer's brochure hosted on a distributor site, and it also includes temperature correction curves and an online sizing calculator.

Key points

  1. KGM range: 46 capacity steps, 11-1560 Ah; KGL range: 96 steps, 10-1775 Ah.
  2. The ideal KGM discharge time is 30 minutes to 3 hours; 1-minute discharges are also supported.
  3. Nominal C5 capacity: end voltage 1.00 V/cell to IEC 62259 and 1.15 V/cell to DIN 40771, at 20 ± 5 °C.
  4. Sample cells: KGM 11 P 12/11 Ah (IEC/DIN), 1.00 kg, 17.28 mΩ; KGM 250 P 275/250 Ah, 12.2 kg, 0.92 mΩ; KGM 1560 P 1735/1560 Ah, 71.7 kg, 0.18 mΩ.
  5. Float 1.40-1.42 V/cell with 1-2 mA/Ah float current; KGM boost 1.44-1.46 V/cell with a 0.1 It A current limit.
  6. Boost charging restores 85 ± 5% of rated capacity in 8-9 hours (1.46 ± 0.01 V/cell, 20 °C).
  7. Charging for the IEC 62259 capacity test: constant current 0.1 It A for 16 hours at 20 ± 5 °C.
  8. Design life exceeds 20 years, with zero or at most one water top-up in that period.
  9. Cells ship filled and charged and can be installed in racks, cabinets, compact blocks or crates.

Using it in design

  • When fixing cell count and capacity, keep the IEC (1.00 V) and DIN (1.15 V) capacities apart and use the definition that matches the UPS DC cut-off voltage.
  • Choose the KGM plate type for autonomies between 30 minutes and 3 hours and KGL for loads longer than 3 hours.
  • Verify the UPS rectifier float and boost settings by multiplying 1.40-1.42 V and 1.44-1.46 V per cell by the cell count.
  • Calculate battery-room floor loading from the filled cell weights in the table; KGM 1560 P weighs 71.7 kg per cell.
  • Use the internal resistance values in the table (mΩ at 100% state of charge) for short-circuit current and DC protection selection.
  • On sites with low ambient temperature, apply the brochure's temperature correction curves to the capacity calculation.

Who should read it

Electrical designers sizing UPS and DC systems with Ni-Cd batteries, and engineers choosing battery technology for heavy-industry or remote-site projects.

Document contents

  1. 140 Years of Excellence
  2. Superb Performance and Reliability with Minimal Maintenance
  3. Single Cell Construction
  4. KGL and KGM Ranges of the Lomain Battery
  5. Lomain KGL Battery Range
  6. KGL Single Cell Range Technical Specifications
  7. Lomain KGM Battery Range
  8. KGM Single Cell Range Technical Specifications
  9. Superb Chargeability
  10. High Performing Even at Extreme Temperatures
  11. Ni-Cd Calculator
  12. Configuration Forms

Publication details

Authors
GAZ Energy
Publisher
GAZ Energy
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GAZ Energy GAZ Lomain Single Cell Ni-Cd Battery Range: PDF p.5 / printed pp.8–9. GAZ Energy. https://infinitier.com.hk/file/SB-19%20GAZ%20Lomain%20(R3).pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.