Shimastu NPH65-12 is a 12 V 65 Ah high-rate AGM UPS monobloc: 260 W per cell for 15 minutes at 1.67 V per cell, up to 10 years float life, 22.5 kg, M6 bolt terminal.

On this page

Overview

The document is the two-page datasheet for the NPH65-12, from Shimastu Electronic Technology's NPH series of high-rate discharge batteries. The series consists of AGM blocks with strong grids and specially designed active material, stated to give 20 percent more power output than the standard range, for UPS, EPS and data-centre loads that need high current. The NPH65-12 has a nominal voltage of 12 V and a 10-hour capacity of 65 Ah.

Physical data: length 350 mm, width 167 mm, container and total height 173 mm, weight about 22.5 kg ±3 percent, with M6 bolt-and-nut terminals. Listed features are very low self-discharge from high-purity material, AGM separators with 99 percent gas recombination efficiency (no water replenishment), a design life of up to 10 years in float service at 25 °C and PbCaSn alloy grids.

Electrical data: 15-minute power is 260 W per cell at 1.67 V per cell; the 10-hour (6.5 A, 10.8 V) capacity is 65.0 Ah and the 20-hour (3.45 A, 10.8 V) capacity is 69.0 Ah. Capacity is 100 percent at 25 °C, 102 percent at 40 °C and 85 percent at 0 °C. Maximum discharge current is 715 A for 5 seconds, short-circuit current is 1640 A and internal resistance of a fully charged battery is 5 mΩ at 25 °C. Float voltage is 13.5 to 13.8 V at 25 °C (-20 mV/°C), cycle voltage is 14.1 to 14.4 V (-30 mV/°C) and initial charging current is below 16.2 A.

The document also gives constant-current (A) and constant-power (W per cell) discharge tables for end voltages of 1.60 to 1.80 V per cell and times from 3 to 60 minutes; at 1.67 V, for example, 15 minutes corresponds to 149.5 A or 260.0 W per cell. These cell-based tables can be used directly for UPS autonomy calculation.

Key points

  1. NPH65-12: 12 V, 10-hour capacity 65 Ah (6.5 A, 10.8 V), 20-hour 69.0 Ah.
  2. 15-minute power: 260 W per cell at 1.67 V per cell.
  3. Size 350 × 167 × 173 mm, weight about 22.5 kg ±3 percent, M6 bolt-and-nut terminal.
  4. Stated 20 percent more power output than the standard range; design life of up to 10 years in float service at 25 °C.
  5. Capacity is 85 percent at 0 °C, 100 percent at 25 °C and 102 percent at 40 °C.
  6. Maximum discharge current 715 A (5 s), short-circuit current 1640 A, internal resistance 5 mΩ (25 °C, fully charged).
  7. Float voltage 13.5 to 13.8 V (25 °C, -20 mV/°C); cycle voltage 14.1 to 14.4 V (-30 mV/°C).
  8. Initial charging current below 16.2 A; gas recombination efficiency 99 percent.

Using it in design

  • In UPS battery sizing, use the 15-minute W per cell figure (260 W) and remember it is per cell: multiply by the cell count of the string (a 12 V block is 6 cells).
  • Match the end voltage (1.60 to 1.80 V per cell) to the UPS cut-off and read the matching constant-power table.
  • Carry the float and cycle charge voltages, with their temperature coefficients (-20 and -30 mV/°C), into the charger settings.
  • Correct autonomy at low temperature (85 percent capacity at 0 °C).
  • Use the weight (22.5 kg) and size for rack layout and floor loading, and set M6 connection torque requirements.

Who should read it

Electrical designers sizing UPS battery banks and engineers writing battery specifications.

Document contents

  1. Physical specification
  2. Features
  3. Electrical specification: capacity, temperature effect, discharge currents, charge data
  4. Constant-current discharge ratings
  5. Constant-power discharge ratings (W per cell)

Publication details

Authors
Shimastu Electronic Technology
Publisher
Shimastu Electronic Technology
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shimastu Electronic Technology Shimastu NPH65-12 datasheet: pp.1–2. Shimastu Electronic Technology. https://af.shimastuelectronic.com/Content/upload/pdf/202237373/r202209231355307178012.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.