UNICOBA Série UP Technical Manual (VRLA Battery), rev. 050920
Original title UNICOBA Série UP: Manual Técnico, rev.050920
UNICOBA
UNICOBA's Série UP VRLA battery manual (rev. 050920) explains capacity definition, 2.25-2.30 V/cell float voltage, -3 mV/C/cell temperature compensation and a 10-12 year design life (30 Ah and above).
On this page
Overview
The distributor copy of the manufacturer's Portuguese technical manual describes the use of Unipower-brand sealed valve-regulated lead-acid (VRLA, AGM) batteries. The first section is devoted to the concept of capacity: Ah is discharge current times time, but a battery cannot be discharged to 0 V, so capacity must be stated with discharge time and cut-off voltage (for example 100 Ah C20 with 10.5 V cut-off). A 12 V battery operates from 13.8 V fully charged down to a 10.5 V cut-off. For comparison, temperature, cut-off voltage and discharge time must be the same.
The technical section covers the AGM system, 99% gas recombination efficiency, maintenance-free operation, terminals and use in any position except upside down. Float design life is 10-12 years for models of 30 Ah and above and 5-7 years below 30 Ah; operating temperature is -15 to 50 C, and monthly self-discharge at 20 C is about 3%. A discharge example is given for the UP1272: cut-off of 1.30 V/cell for 3C (21 A) and 1C (7.2 A), 1.55 V for 0.55C (3.85 A), and 1.75 V for 0.1C (0.70 A) and 0.05C (0.35 A).
The charging section recommends constant-voltage charging at 2.25-2.30 V/cell on float and 2.40-2.45 V/cell for cyclic use (25 C), with initial current limited to 0.1-0.25C. Temperature compensation is -3 mV/C/cell on float and -4 mV/C/cell for cyclic use (reference 20 C). Two-stage charging uses constant current up to 2.45 V/cell and then a 2.3 V/cell float voltage. The manual also covers cyclic and float life, end-of-life signs, recovery from deep discharge, tips to extend life, and monthly and six-monthly inspections. This document is not a model catalogue and creates no new nominal model rows.
Key points
- Capacity must be given with discharge time, cut-off voltage and temperature; example: 100 Ah C20, 10.5 V cut-off.
- 12 V batteries operate from 13.8 V fully charged down to a 10.5 V cut-off.
- Float voltage 2.25-2.30 V/cell (25 C); cyclic use 2.40-2.45 V/cell; initial current 0.1-0.25C.
- Temperature compensation: -3 mV/C/cell (float), -4 mV/C/cell (cyclic); reference 20 C.
- Float design life is 10-12 years for 30 Ah and above and 5-7 years below 30 Ah.
- Monthly self-discharge about 3% at 20 C; operating temperature -15 to 50 C.
- UP1272 discharge example: 1.30 V/cell at 3C/21 A and 1C/7.2 A; 1.55 V at 0.55C/3.85 A; 1.75 V at 0.1C/0.70 A and 0.05C/0.35 A.
- AGM construction, 99% gas recombination, maintenance-free; usable in any position except upside down.
Using it in design
- When selecting batteries, compare manufacturers at the same discharge time, cut-off voltage and temperature; the Ah figure alone is not enough.
- In UPS runtime calculations, use the cut-off voltage that matches short discharge times (1.30-1.75 V/cell).
- Set the charger float to 2.25-2.30 V/cell times the cell count and apply -3 mV/C/cell compensation with a temperature sensor.
- Design the battery room to stay around 20-25 C; high temperature shortens life.
- Add the manual's monthly and six-monthly inspections to the maintenance programme.
Who should read it
Engineers and maintenance teams working on VRLA battery care and UPS battery string design.
Document contents
- Concepts of capacity and use
- Technical characteristics
- Construction
- Terminals
- Self-discharge
- Storage
- Capacity measurement by open-circuit voltage
- Discharge
- Discharge vs temperature
- Constant-voltage charging
- Cyclic life
- Float life
- End of life
- Temperature compensation
- Constant-current charging
- Charging by rectifiers
- Two-stage constant-voltage charging
- Initial charging current limit
- Recovery after deep discharge
- Tips to maximise battery life
- Environment
- Monthly inspection
- Six-monthly inspection
Publication details
- Authors
- UNICOBA
- Publisher
- UNICOBA
- Year
- Year not stated
- Document number
- rev.050920
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
UNICOBA UNICOBA Série UP: Manual Técnico, rev.050920. UNICOBA. rev.050920. https://www.robocore.net/upload/ManualTecnicoBateriaUnipower.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.