A seven-page ATENCO datasheet for the three-phase on-line double-conversion TM33E UPS series: five ratings of 10, 15, 20, 30 and 40 kVA with output power factor 1 (10 kVA/10 kW to 40 kVA/40 kW), efficiency of at least 93.5% at 10 to 20 kVA and at least 94.5% at 30 to 40 kVA, and input THDi of at most 3%.

On this page

Overview

The TM33E is a tower VFI on-line UPS series with IGBT topology and DSP control, three-phase input and three-phase output. Models are named TM33E-[kVA]-[S/L]: S marks the version with internal batteries and L the long-backup version that works with external batteries only. Each rating comes in both versions, giving ten models. Nominal voltage is selectable at 380/400/415 V AC (three-phase, neutral, PE). Because output power factor is 1, kVA and kW values are equal. An optional dual input gives separate supplies for rectifier and bypass.

The operating input voltage range is 208 to 478 V AC on the 10 to 30 kVA models and 323 to 478 V AC on the 40 kVA model. Input power factor is at least 0.99 and current distortion at most 3% at 100% non-linear load. Output voltage regulation is ±1%, and voltage distortion is at most 2% on linear load and 5% on non-linear load. Transfer from utility to battery and from utility to bypass takes 0 ms. Overload capability in line mode is 60 minutes at 110%, 10 minutes at 125% and 1 minute at 150%; in battery mode these fall to 10 minutes, 1 minute and 10 seconds.

The battery side is defined flexibly. In the S version the internal batteries are 12 V 9 Ah blocks: 20 on the small models (40 maximum), 40 on the mid models and 60 on the large models, with weights in steps of 95, 147 and 225 kg. The L version weighs 42 to 73 kg and has a 10 A or 20 A built-in charger. All cabinets measure 250 x 868 x 900 mm (width, height, depth). The matching battery pack holds 80 blocks of 12 V 9 Ah and weighs 243 kg. The datasheet states that its data are for reference and that scope of supply is defined by the formal quotation.

Key points

  1. Ratings: 10 kVA/10 kW, 15 kVA/15 kW, 20 kVA/20 kW, 30 kVA/30 kW, 40 kVA/40 kW, each in S (internal battery) and L (external battery) versions.
  2. Efficiency: at least 93.5% at 10 to 20 kVA and at least 94.5% at 30 to 40 kVA; up to 99% in ECO mode.
  3. Input power factor at least 0.99; THDi at most 3% (100% non-linear load).
  4. Transfer time 0 ms from utility to battery and 0 ms from utility to bypass.
  5. Overload (line mode): 60 minutes up to 110%, 10 minutes up to 125%, 1 minute up to 150%.
  6. Bypass breaker ratings: 20 A at 10 kVA, 32 A at 15 kVA, 40 A at 20 kVA, 63 A at 30 kVA, 80 A at 40 kVA.
  7. Cabinet 250 x 868 x 900 mm (W x H x D); S version 95 to 225 kg, L version 42 to 73 kg; 80-block battery pack 243 kg.
  8. Parallel redundancy (N+X) of up to 4 units; built-in charger up to 20 A.
  9. Noise below 55 dB at 10 to 30 kVA and below 58 dB at 40 kVA; operating temperature 0 to 40 °C; derating required above 1500 m.

Using it in design

  • Thanks to unity power factor, select the UPS directly from the kW load; the 40 kVA model carries 40 kW.
  • Calculate heat load from the efficiency floor of the rating: about 2.3 kW of loss at 40 kW load and 94.5% efficiency.
  • Choose bypass line protection in line with the bypass breaker values in the datasheet (20 to 80 A) and check selectivity with the upstream device.
  • Pick the S or L version from the backup time target; on the L version define string voltage and block count together with the manufacturer.
  • For floor loading, assess the 225 kg internal-battery cabinet and the 243 kg battery pack on their narrow 250 mm wide footprint.
  • Confirm dimensions and weights against the current revision in the formal quotation before ordering.

Who should read it

Electrical engineers selecting 10 to 40 kVA three-phase UPS units for small and mid-size data rooms, and teams preparing product catalogue data.

Document contents

  1. Applications
  2. Key features
  3. Input and output
  4. Overload capability
  5. Battery and charging
  6. Protection and alarms
  7. Environmental and standards
  8. Options
  9. Rear panel layout
  10. Technical specifications table
  11. Standard unit, long backup unit and matching battery pack

Publication details

Authors
ATENCO
Publisher
ATENCO
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ATENCO ATENCO TM33E 10-40 kVA datasheet, technical specifications and battery variants. ATENCO. https://atenco.com.tw/wp-content/uploads/2026/06/ATENCO-TM33E-10-40kVA-20260213_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.