Beam Tech Galaxy Series technical specifications: sine wave double-conversion UPS, 1500 VA to 3000 VA
Original title Beam Tech Galaxy Series technical specifications pp.1-3; product page GR/GS identifiers
Beam Tech Electronics
A three-page specification sheet from Beam Tech Electronics for the Galaxy series of single-phase double-conversion UPSs: 1500 VA/1200 W, 2000 VA/1600 W and 3000 VA/2400 W, output power factor 0.8, AC-mode efficiency up to 92% on 230 V models.
On this page
Overview
The sheet presents the three Galaxy capacities, in tower and rack form, with their 115 V and 230 V market variants in a single table. The topology is double conversion with a common neutral; general features include a new full-bridge inverter design, input power factor correction and generator compatibility. Rack models have hot-swappable batteries. An LCD display is standard, while an LED display, SNMP, programmable receptacles and remote emergency power off (REPO) are options.
On the output side, voltage is selectable among 200/220/230/240 V on 230 V models (208 V optional) and 100/110/115/120 V on 115 V models, with ±2% regulation. The waveform is sinusoidal, crest factor is 3:1 and harmonic distortion is below 3% at full resistive load. Transfer from mains to battery is break-free; inverter to bypass takes 4 ms typically. Overload stages are 60 seconds at 100% to 115%, 10 seconds at 115% to 135% and 2 seconds above 135%, followed by transfer to bypass.
The input window is 100 to 285 V on 230 V models and 50 to 143 V on 115 V models, with an input power factor of at least 0.99. According to the footnotes, capacity is derated when the input is between 100 and 170 Vac (or 50 and 85 Vac), and it falls to 80% in frequency-converter mode. The battery string uses 12 V 7 Ah VRLA blocks (9 Ah optional): 36 Vdc for 1500 VA, 48 Vdc for 2000 VA and 72 Vdc for 3000 VA. Typical runtime is 9 minutes at half load and 4 minutes at 90% load.
Environmental limits are 0 to 40 °C operating temperature up to 1500 metres, 0 to 3000 metres operating altitude, 5% to 95% non-condensing humidity and at most 45 dBA at 1 metre. Net weight is 14, 17 and 23 kg for tower units and 18, 21 and 27 kg for rack units. Rack models are 2U high. The dimension row gives device and packaging sizes on the same line. The sheet is undated and publishes a single upper efficiency value, not a load curve.
Key points
- Capacities: 1500 VA/1200 W, 2000 VA/1600 W, 3000 VA/2400 W; output power factor 0.8.
- Topology: common-neutral double conversion; zero transfer time mains to battery, 4 ms typical inverter to bypass.
- AC-mode efficiency up to 90% on 115 V models and up to 92% on 230 V models.
- Input window 100...285 V on 230 V models, 50...143 V on 115 V models; input power factor at least 0.99.
- Output regulation ±2%, crest factor 3:1, THD below 3% at full resistive load.
- Overload: 60 s at 100...115%, 10 s at 115...135%, 2 s above 135%, then bypass.
- Battery voltage 36/48/72 Vdc (12 V 7 Ah blocks, 9 Ah optional); 9 minutes at half load, 4 minutes at 90% load; 7 hours to 90% recharge.
- Capacity derates to 80% in frequency-converter mode; frequency range 40...70 Hz.
- Net weight 14/17/23 kg tower, 18/21/27 kg rack; rack form is 2U.
- Green mode (auto-bypass at low load) is adjustable between 1% and 14% load and is off by default.
Using it in design
- Size the load against watts, not VA: the 3000 VA model supplies at most 2400 W.
- Apply the derating where site input voltage can fall into the 100...170 V band, and the 80% limit in frequency-converter mode.
- Compare the internal battery runtime (4 minutes at 90% load) with generator start time; ask the manufacturer about external battery options for longer autonomy.
- If green mode is enabled, assess the load's exposure to mains quality through bypass; keep the default off setting for critical loads.
- For cabinet layout use the 2U height, 43 or 51 cm depth and 18 to 27 kg weight of the rack models.
- Note that the 0...40 °C limit applies up to 1500 metres when designing for high-altitude sites.
Who should read it
Electrical designers and specification writers selecting 1 to 3 kVA double-conversion UPSs for edge cabinets, network rooms and small IT loads.
Document contents
- General Features
- Output
- Input
- Battery
- Communications & Management
- Environmental and Safety
- Physical
Publication details
- Authors
- Beam Tech Electronics
- Publisher
- Beam Tech Electronics
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Beam Tech Electronics Beam Tech Galaxy Series technical specifications pp.1-3; product page GR/GS identifiers. Beam Tech Electronics. https://beam-tech.com/093001/prd_pgs/spec/Sine-wave-Double-conversion-UPS-Galaxy-Series-1500VA-3000VA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.