Naicon ELSIST 2024 English catalogue, Polaris technical tables
Original title Naicon ELSIST 2024 English catalogue, Polaris technical tables, printed p.50
Elsist (Naicon)
Polaris section of the Naicon (Elsist) 2024 catalogue: 10 to 350 kVA, unity output power factor, input THDi below 2 percent, and efficiency from above 96.5 percent at 10 kVA to above 97.5 percent in mid-range models.
On this page
Overview
The catalogue covers Elsist and Naicon UPS, stabiliser and accessory products; the Polaris section describes the high-power three-phase series. Naicon states that it has built energy conversion systems since 1978 and offers Elsist UPS up to 800 kVA. Across the catalogue it explains that controlling the input sine waveform brings input harmonic distortion below 3 percent, with efficiency above 95 percent in normal operation and above 98 percent in power-save mode.
Main Polaris features are listed as input THDi below 2 percent, system efficiency above 97.5 percent, unity output power factor (kVA = kW), automatic circuit-breaker protection on input and output, MODBUS RS485, network monitoring through an SNMP card, generator operation support, battery charging with thermal compensation, four voltage-free contacts and an earthquake-resistance certification up to intensity level 9. Expected battery life is given as 10 to 12 years.
Parallel capability is the modular power technology the series is built on. The units detect an additional UPS on their own and set the output power accordingly; no separate parallel board or software setting is needed. The parallel control cables are shielded and double insulated and are connected in a ring between units. Up to four units can be paralleled on all models and up to six on the 60 kVA module only. Parallel groups require the same rating, the same bypass line and cables of equal length and specification.
The tables list single-unit models at 10, 15, 20, 30, 40, 60, 80 and 100 kVA, and models from 120 to 350 kVA as combinations of 2 to 4 units. The document dates from 2024. Efficiency values are published as lower bounds and do not form a load curve.
Key points
- Polaris models: 10, 15, 20, 30, 40, 60, 80 and 100 kVA single unit; 120, 160, 180, 200, 250, 300, 320 and 350 kVA multi-unit (2 to 4 units).
- kVA = kW on every model (unity output power factor); input power factor 0.99 or higher; input THDi below 2 percent (linear load).
- Output THDv below 1 percent on linear and below 3 percent on nonlinear load; output frequency 50/60 Hz ± 0.1 percent.
- Efficiency: above 96.5 percent at 10 kVA; above 97.5 percent for 15 to 40 kVA; above 94 percent for 60 kVA and up.
- Transfer time to battery and to bypass 0 ms; overload 110 percent for 60 min, 125 percent for 10 min, 150 percent for 1 min, bypass above that.
- Standard backup time is 10 minutes; battery cell count is configurable 16 to 20 (or 32 to 40) up to 40 kVA and 30 to 50 on larger models.
- 10-60 kVA models are 250 x 868 x 828 mm, 66-83 kg without batteries; 80 kVA and above are 442 x 1200 x 850 mm, 153 kg.
- Parallel: up to 4 units on all models, up to 6 on the 60 kVA module only.
- Standards EN/IEC 60951, 62040-1, 62040-2 and 62040-3; operating temperature 0 to 40 °C.
Using it in design
- Because output power factor is 1, take kW capacity directly from the kVA value, and still check load power factor compatibility.
- Write the parallel rules (same rating, common bypass line, equal cable length) into the site installation plan.
- Compare the 10-minute standard backup with the project requirement; assess battery cabinets and cell count options for longer runtime.
- Use the input THDi below 2 percent in generator sizing and in harmonic checks at the grid connection.
- Add Modbus RS485, SNMP and voltage-free contacts to the BMS and monitoring integration specification.
Who should read it
Electrical designers selecting three-phase UPS units and teams cataloguing the Elsist product family.
Document contents
- Company profile
- What is an UPS and how it works
- Electrical disturbances
- Single-phase range
- Tri-One range
- Three-phase range: Polaris
- Polaris features and modularized power technology
- Polaris technical tables
- Stabilizers
- Special products
- Optional attachments
- Warranty
Publication details
- Authors
- Elsist (Naicon)
- Publisher
- Elsist (Naicon)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Elsist (Naicon) Naicon ELSIST 2024 English catalogue, Polaris technical tables, printed p.50. Elsist (Naicon). https://www.naicon.com/company/wp-content/uploads/2024/09/catalogo-elsist-2024-eng-v10-web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
