ITAPOWER Ermes T IGPT 2025 datasheet

Original title ITAPOWER Ermes T IGPT 2025 datasheet, PDF p.3 (image table visually checked)

ITAPOWER

The Ermes T IGPT datasheet from Italian manufacturer ITAPOWER describes three-phase double-conversion UPSs with an output isolation transformer and IGBT rectifier in two series: EI from 100 to 600 kVA (90 to 540 kW) and EP from 100 to 800 kVA with kW equal to kVA; on-line efficiency reaches 95.5% and input current distortion is below 3%.

On this page

Overview

The five-page 2025 datasheet presents the Ermes T IGPT family made in Italy by Milan-based ITAPOWER. The units are true on-line double-conversion UPSs with a transformer for galvanic isolation, DSP control and an IGBT-based rectifier. The manufacturer stresses higher efficiency than conventional thyristor-rectifier systems, a compact footprint and easy maintenance access. Target uses are data centres, medical equipment, industry, sensitive IT loads, telecom and critical buildings. The cover carries the 100-600 kVA range and the statement kW=kVA.

The technical tables give two separate model series. The EI series has nine models (EI100, 120, 160, 200, 250, 300, 400, 500, 600) with active power at 0.9 times apparent power: 90 kW for 100 kVA and 540 kW for 600 kVA. The EP series has ten models (EP100 to EP800) with kW equal to kVA, and its table includes the EP800 at 800 kVA / 800 kW, above the range on the cover. The kW=kVA statement therefore holds for the EP series only.

The input is 380/400/415 V three-phase with a tolerance of 400 V ±20% at full load, 45-65 Hz, power factor above 0.99 and THDi below 3%; soft start is selectable from 0 to 100% in 120 seconds. The output is 3 phases plus neutral with static stability of ±1%, voltage distortion below 1% on linear load and below 3% on non-linear load, and a crest factor of 3:1. Overload is 110% for 60 minutes, 125% for 10 minutes and 150% for 1 minute. The classification to IEC 62040-3 is VFI-SS-111. Backfeed protection and a separable bypass line are standard.

On the battery side, VRLA AGM, gel, NiCd, lithium-ion and supercapacitor options are supported with one-level, two-level or cyclic recharge. Weights run from 700 to 2700 kg in the EI series and from 850 to 3950 kg in the EP series, and cabinets grow from 800 x 850 x 1900 mm to 3200 x 1000 x 1900 mm for the EP800. ECO-mode efficiency is given as up to 98% for EI and up to 99% for EP. Ambient temperature is 0-40 °C, the recommended temperature for battery life is 20-25 °C and the IP rating is IP20.

Key points

  1. EI series: 100, 120, 160, 200, 250, 300, 400, 500, 600 kVA; active power 90, 108, 144, 180, 225, 270, 360, 450, 540 kW.
  2. EP series: 100, 120, 160, 200, 250, 300, 400, 500, 600, 800 kVA; kW equals kVA.
  3. Input 380/400/415 V three-phase, 400 V ±20% at full load, 45-65 Hz; power factor above 0.99; THDi below 3%.
  4. Efficiency up to 95.5% in on-line mode; ECO mode up to 98% for EI and up to 99% for EP.
  5. Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute; crest factor 3:1.
  6. IEC 62040-3 class VFI-SS-111; safety IEC EN 62040-1, EMC IEC EN 62040-2.
  7. EI weights: 700, 755, 830, 956, 1060, 1500, 1720, 2525, 2700 kg; EP weights: 850, 850, 1010, 1065, 1300, 1520, 1670, 2500, 2830, 3950 kg.
  8. Cabinet dimensions (W x D x H): 800 x 850 x 1900, 1000 x 850 x 1900, 1500 x 1000 x 1900, 2100 x 1000 x 1900 mm; 3200 x 1000 x 1900 mm for the EP800.
  9. Noise at 1 m is 65, 68 or 72 dBA depending on rating; IP20; ambient 0-40 °C.
  10. Battery types: VRLA AGM, gel, NiCd, Li-ion, supercapacitors; separate or common battery arrangement in parallel systems.

Using it in design

  • Distinguish the series when selecting a model: at the same kVA an EI model delivers kW at 0.9 power factor and an EP model at 1.0; match the IT load in kW.
  • The output isolation transformer gives galvanic separation; use it in the earthing arrangement and neutral-forming design, and carry weights of up to 3950 kg into floor loading.
  • Base heat-load calculations on a maximum of 95.5% efficiency in on-line mode; use ECO-mode efficiency only where the load tolerates being fed through bypass.
  • For generator sizing, take advantage of THDi below 3%, input power factor above 0.99 and the soft start adjustable up to 120 seconds.
  • In parallel systems choose separate or common batteries according to the redundancy target; a common battery creates a single point of failure.
  • The cabinets are moved by pallet jack and stand 1900 mm high; check the delivery route and door openings.

Who should read it

Electrical designers selecting medium and large transformer-based UPSs, and teams cataloguing European UPS products.

Document contents

  1. Highlights
  2. Technical Specifications: EI models
  3. Technical Specifications: EP models
  4. Input
  5. Bypass
  6. Output
  7. Batteries
  8. Overall specifications
  9. Mains, Bypass and Load connections

Publication details

Authors
ITAPOWER
Publisher
ITAPOWER
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ITAPOWER ITAPOWER Ermes T IGPT 2025 datasheet, PDF p.3 (image table visually checked). ITAPOWER. https://itapower.it/wp-content/uploads/2025/03/ITAPOWER-ERMES-T-IGPT-datasheet-2025.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.