Lestar KP-261/PL MEPRT II-1000 product sheet
Original title Lestar KP-261/PL MEPRT II-1000 product sheet, PDF pp.1–2
Lestar
The Lestar MEPRT II-1000 ONLINE LCD RT is a 1000 VA / 900 W (PF 0.9) double-conversion UPS for rack or tower use, with 0 ms transfer, over 94% efficiency in ECO mode and 2 x 9 Ah internal batteries.
On this page
Overview
Lestar's Polish product sheet (KP-261/PL) describes the MEPRT II-1000 ONLINE LCD RT 6XIEC: 1000 VA / 900 W, output power factor 0.9, DSP-controlled double-conversion on-line topology, pure sine output, 0 ms transfer time and generator compatibility. The unit is recommended for mid-range servers, small networks (2-3 computers), telephone exchanges and modems. The sheet is an older public document; the model's current production status is not given in it.
On the input side nominal voltage is 200/208/220/230/240 V and the operating range 110-290 Vac, with the lower limit depending on load: 160-290 V at full load, 170-290 V at 70-80% load, 140-290 V at 40-60% load and 120-290 V below 30% load. Input power factor is above 0.98 and THDi below 7% at maximum non-linear load. Output voltage tolerance is +/-2%, frequency is 50/60 Hz auto-sensing on mains and +/-0.02 Hz on battery, THDu is below 3% linear and 5% non-linear, and crest factor is 3:1.
Efficiency is up to 89% in AC mode and above 94% in ECO mode. Transfer from mains to battery is 0 ms and to bypass under 4 ms. The internal battery is 24 Vdc, 2 x 9 Ah sealed lead-acid, with 5 hours to recover 90% of full capacity. Runtime is given as 5 minutes at full load and 12 and 30 minutes at 0.5 and 0.25 of load power; the sheet states these are measured values and that an extra load margin should be applied when sizing. ZMA external battery modules can be connected.
For protection, overload times in normal and battery mode are 30 seconds at 108-150%, 300 ms at 150-200% and 20 ms above 200%; in bypass mode 20 minutes at 100-130% and 2 minutes at 130-150%. Surge protection is 380 J. The case measures 430 x 440 x 86.5 mm (length x width x height) and weighs 15.7 kg net; there are 6 IEC C13 outlets (3 programmable), USB, RS-232, EPO, an RJ-45 filter and an intellislot for SNMP/Modbus/relay cards. Operation is 0-40 C, up to 95% humidity, noise up to 45 dB at 1 m; continuous temperatures above 25 C shorten battery life. Warranty is 24 months.
Key points
- Power 1000 VA / 900 W, output power factor 0.9; input power factor above 0.98.
- Input range 110-290 Vac; lower limit from 160 V (full load) to 120 V (below 30% load).
- Output +/-2%, THDu below 3% linear and 5% non-linear; crest factor 3:1.
- Efficiency up to 89% in AC mode, above 94% in ECO mode.
- Mains-to-battery transfer 0 ms, bypass transfer under 4 ms.
- Internal battery 24 Vdc / 2 x 9 Ah; 90% recharge in 5 hours.
- Runtime: 5 min at full load, 12 min at 0.5 load, 30 min at 0.25 load.
- Normal-mode overload: 30 s at 108-150%, 300 ms at 150-200%, 20 ms above 200%.
- Size 430 x 440 x 86.5 mm, 15.7 kg net; 6 x IEC C13 (3 programmable).
- Operation 0-40 C, up to 95% humidity; noise up to 45 dB at 1 m; 24-month warranty.
Using it in design
- Calculate runtime from the real load and, if needed, ZMA external battery modules, not from the sheet values; the sheet asks for an extra load margin.
- Compare load power with the 900 W limit; with output power factor 0.9 the VA rating is not the limiter.
- For rack use check 430 x 440 x 86.5 mm and 15.7 kg against the 19-inch rack; tower feet are supplied.
- As this is an older sheet, confirm model status and the current datasheet with the manufacturer before ordering.
- If ECO mode is used, assess the under-4 ms bypass transfer against sensitive loads.
Who should read it
Designers and IT managers looking for a rack or tower 1 kVA on-line UPS for small server and network loads.
Document contents
- Properties and functions
- Technical data (input, output, efficiency, battery, protection, indicators, physical)
- Logistics data
Publication details
- Authors
- Lestar
- Publisher
- Lestar
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lestar Lestar KP-261/PL MEPRT II-1000 product sheet, PDF pp.1–2. Lestar. http://www.lestar.pl/files/888336925/kp261pl_meprt_ii_1000_online_lcd_rt_6xiec.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.