Teletecnica Industrial UPS 3Ph/1Ph Technical Table
Original title Teletecnica Industrial UPS 3Ph/1Ph, PDF p.2 technical table
Teletecnica
Teletecnica's industrial double-conversion on-line UPS family covers 5-50 kVA with 400 V 3-phase input, 230 V single-phase output and 110 or 220 Vdc battery; output power factor is 0.8 and overload is 125% for 10 min.
On this page
Overview
The document gives the technical table for Italian company Teletecnica S.r.l.'s industrial UPS family with 3-phase input and single-phase output. The technology is double-conversion on-line with an SCR 6-pulse rectifier and an IGBT (PWM) inverter. Input is 380/400/415 Vac +/-10%, 3-phase, 50/60 Hz, with input power factor 0.8 at full load and THD typically 30% or less. Output is 230 Vac single phase 50/60 Hz and bypass input is 230 Vac +/-10%. Power is given in kVA at cos phi = 0.8.
The table has two DC link groups: 110 Vdc (90-150 Vdc) for 5, 10, 15, 20 and 25 kVA, and 220 Vdc (180-300 Vdc) for 5, 10, 15, 20, 30, 40 and 50 kVA. Charging current rises by model from 4-20 A at 110 Vdc and 2-20 A at 220 Vdc. Float, boost and equalising voltages are given separately for VRLA, VLA and Ni-Cd; VRLA float is 2.27 V/cell. Overload is 105% permanent, 125% for 10 min, 150% for 1 min and 200% for 100 ms. Static output stability is +/-1%, and dynamic stability is +/-5% for an 80% load step, recovering to 2% in 40 ms.
Mechanically it is a free-standing, front-access steel cabinet, IP20, painted RAL 7035; width is 800 to 1800 mm, depth 800 mm and height 1900 mm. Operation is 0-40 C, up to 1000 m without derating, and noise is 65-70 dB(A) at 1 m. Standards include IEC EN 62040-2, IEC EN 50178 and, for EMC, IEC EN 61000-6-2 and -6-4. The document is an older publication, uploaded in 2022.
Key points
- Power range 5-50 kVA (cos phi = 0.8); 5-25 kVA for 110 Vdc and 5-50 kVA for 220 Vdc.
- Input 380/400/415 Vac +/-10%, 3-phase; input PF 0.8 and THD typically <=30% (6-pulse SCR rectifier); 12-pulse option available.
- Output 230 Vac single phase; THD <2% on linear and <5% on non-linear load; crest factor 3:1 without derating.
- Overload: 105% permanent, 125% for 10 min, 150% for 1 min, 200% for 100 ms.
- Static stability +/-1%; dynamic +/-5% (80% load step), recovery to 2% in 40 ms.
- DC link 110 Vdc (90-150) or 220 Vdc (180-300); VRLA float 2.27 V/cell; temperature compensation available.
- Cabinet 800-1800 x 800 x 1900 mm (W x D x H), IP20; 0-40 C, up to 1000 m without derating.
- Standards: IEC EN 62040-2, IEC EN 50178, IEC EN 61000-6-2/-6-4; remote signalling by SPDT contacts.
Using it in design
- Output cos phi is 0.8, so use 0.8 when converting kVA to kW; the table does not give kW.
- Match the DC link voltage (110 or 220 Vdc) to the battery string design; cell count and float voltage follow from it.
- With input PF 0.8 and THD <=30%, consider the 12-pulse rectifier or a harmonic filter in generator sizing.
- Feed the overload curve into protection and selectivity studies.
- Because the document is older, confirm the current model code with the supplier.
Who should read it
Electrical engineers selecting 3-phase-input, single-phase-output UPSs for industrial plants and power stations.
Document contents
- Main features and options
- AC input
- AC output
- DC link
- Control and signalling
- Environmental conditions
- Mechanical characteristics
- Standards
Publication details
- Authors
- Teletecnica
- Publisher
- Teletecnica
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Teletecnica Teletecnica Industrial UPS 3Ph/1Ph, PDF p.2 technical table. Teletecnica. https://teletecnicaweb.it/wp-content/uploads/2022/03/ups_tm_uk.pdf