Teletecnica Industrial UPS 3Ph/1Ph Technical Table

Original title Teletecnica Industrial UPS 3Ph/1Ph, PDF p.2 technical table

Teletecnica

Teletecnica's industrial double-conversion on-line UPS family covers 5-50 kVA with 400 V 3-phase input, 230 V single-phase output and 110 or 220 Vdc battery; output power factor is 0.8 and overload is 125% for 10 min.

On this page

Overview

The document gives the technical table for Italian company Teletecnica S.r.l.'s industrial UPS family with 3-phase input and single-phase output. The technology is double-conversion on-line with an SCR 6-pulse rectifier and an IGBT (PWM) inverter. Input is 380/400/415 Vac +/-10%, 3-phase, 50/60 Hz, with input power factor 0.8 at full load and THD typically 30% or less. Output is 230 Vac single phase 50/60 Hz and bypass input is 230 Vac +/-10%. Power is given in kVA at cos phi = 0.8.

The table has two DC link groups: 110 Vdc (90-150 Vdc) for 5, 10, 15, 20 and 25 kVA, and 220 Vdc (180-300 Vdc) for 5, 10, 15, 20, 30, 40 and 50 kVA. Charging current rises by model from 4-20 A at 110 Vdc and 2-20 A at 220 Vdc. Float, boost and equalising voltages are given separately for VRLA, VLA and Ni-Cd; VRLA float is 2.27 V/cell. Overload is 105% permanent, 125% for 10 min, 150% for 1 min and 200% for 100 ms. Static output stability is +/-1%, and dynamic stability is +/-5% for an 80% load step, recovering to 2% in 40 ms.

Mechanically it is a free-standing, front-access steel cabinet, IP20, painted RAL 7035; width is 800 to 1800 mm, depth 800 mm and height 1900 mm. Operation is 0-40 C, up to 1000 m without derating, and noise is 65-70 dB(A) at 1 m. Standards include IEC EN 62040-2, IEC EN 50178 and, for EMC, IEC EN 61000-6-2 and -6-4. The document is an older publication, uploaded in 2022.

Key points

  1. Power range 5-50 kVA (cos phi = 0.8); 5-25 kVA for 110 Vdc and 5-50 kVA for 220 Vdc.
  2. Input 380/400/415 Vac +/-10%, 3-phase; input PF 0.8 and THD typically <=30% (6-pulse SCR rectifier); 12-pulse option available.
  3. Output 230 Vac single phase; THD <2% on linear and <5% on non-linear load; crest factor 3:1 without derating.
  4. Overload: 105% permanent, 125% for 10 min, 150% for 1 min, 200% for 100 ms.
  5. Static stability +/-1%; dynamic +/-5% (80% load step), recovery to 2% in 40 ms.
  6. DC link 110 Vdc (90-150) or 220 Vdc (180-300); VRLA float 2.27 V/cell; temperature compensation available.
  7. Cabinet 800-1800 x 800 x 1900 mm (W x D x H), IP20; 0-40 C, up to 1000 m without derating.
  8. Standards: IEC EN 62040-2, IEC EN 50178, IEC EN 61000-6-2/-6-4; remote signalling by SPDT contacts.

Using it in design

  • Output cos phi is 0.8, so use 0.8 when converting kVA to kW; the table does not give kW.
  • Match the DC link voltage (110 or 220 Vdc) to the battery string design; cell count and float voltage follow from it.
  • With input PF 0.8 and THD <=30%, consider the 12-pulse rectifier or a harmonic filter in generator sizing.
  • Feed the overload curve into protection and selectivity studies.
  • Because the document is older, confirm the current model code with the supplier.

Who should read it

Electrical engineers selecting 3-phase-input, single-phase-output UPSs for industrial plants and power stations.

Document contents

  1. Main features and options
  2. AC input
  3. AC output
  4. DC link
  5. Control and signalling
  6. Environmental conditions
  7. Mechanical characteristics
  8. Standards

Publication details

Authors
Teletecnica
Publisher
Teletecnica
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Teletecnica Teletecnica Industrial UPS 3Ph/1Ph, PDF p.2 technical table. Teletecnica. https://teletecnicaweb.it/wp-content/uploads/2022/03/ups_tm_uk.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.