Lento Zector series (1-3 kVA) UPS model technical specification table
Original title Lento Zector series model technical specification table
Lento Industries
Lento Industries's Zector 1, 2 and 3 kVA on-line UPS table: high-frequency double conversion, 110-300 Vac input, 0 ms transfer to battery mode and 95-97% efficiency in ECO mode.
On this page
Overview
The product page presents Zector 901, 902 and 903 (1 kVA/1 kW, 2 kVA/2 kW, 3 kVA/3 kW). The series is a DSP-controlled, high-frequency, true double-conversion on-line UPS; active power factor correction brings input power factor up to 0.99. The manufacturer highlights offices, hospitals, telecom and automation, and also lists data centres and server rooms among applications.
Input is 230 Vac nominal; there is no derating between 176 and 280 Vac, linear derating between 50% and 100% load from 110 to 176 Vac, and 50% derating from 280 to 300 Vac. Frequency range is 40-70 Hz and THDi 6% or less. Output voltage is set from the LCD at 208/220/230/240 Vac, with +/-1% regulation, THDv 2% on linear and 5% on non-linear load and crest factor 3:1. Overload is 1 minute at 105-125%, 30 seconds at 125-150% and 300 ms above 150%.
Efficiency is 90%, 91% and 92% in mains mode; 85%, 86% and 87% in battery mode; and 95%, 96% and 97% in ECO mode (for 1, 2 and 3 kVA). Mains-to-battery transfer is 0 ms and inverter-to-bypass typically 4 ms. Battery DC voltage is 24, 36, 48, 72 or 96 V depending on the model, and the built-in battery ranges from 2 x 9 Ah to 8 x 7 Ah. In the standard model charging current is up to 1 A and 90% capacity is restored in 3 hours; the long-time model uses 6 A and recharge time depends on battery capacity. Cold start, ABM battery management and programmable delayed restart are included.
The table lists output power factor as 0.9/1.0, while the feature list states output power factor up to 0.9. Standard (S) and long-time (H) battery configurations come in different cases: case sizes range from 144 x 312 x 216 mm to 191 x 419 x 335 mm (W x D x H) and net weights from 6 to 29.4 kg. Operating temperature is 0-40 C, altitude below 1000 m (1% derating per additional 100 m), noise 50 dB or less and protection IP20. Communication is RS232 as standard, with optional USB, RS485, dry contacts and SNMP.
Key points
- Models: Zector 901 (1 kVA / 1 kW), 902 (2 kVA / 2 kW), 903 (3 kVA / 3 kW).
- Input 230 Vac; no derating 176-280 Vac; linear derating 110-176 Vac; 50% derating 280-300 Vac.
- Input power factor 0.99 or higher; THDi 6% or less; frequency 40-70 Hz.
- Output voltage settable at 208/220/230/240 Vac; regulation +/-1%; crest factor 3:1.
- Efficiency 90-92% in mains mode, 85-87% in battery mode, 95-97% in ECO mode.
- Mains-to-battery transfer 0 ms, inverter-to-bypass typically 4 ms.
- Overload 1 min at 105-125%, 30 s at 125-150%, 300 ms above 150%.
- Battery DC voltage 24-96 V; standard model up to 1 A charge, 90% in 3 hours; long-time model 6 A.
- Operation 0-40 C, altitude below 1000 m, IP20, noise 50 dB or less.
- Net weight 6 to 29.4 kg depending on case and battery configuration.
Using it in design
- Confirm the kW capacity with the manufacturer, since the table (0.9/1.0) and the feature list (up to 0.9) differ on output power factor.
- Where input voltage can fall below 176 Vac, account for the linear derating that reduces available power.
- State the battery configuration (24-96 V, standard or long-time) in the order code; case size and weight change with it.
- If you use ECO mode, assess the 4 ms inverter-to-bypass transfer and the different protection against the load's sensitivity.
- Apply 1% derating per 100 m for sites above 1000 m altitude.
Who should read it
Designers and buyers comparing 1-3 kVA on-line UPS for small office, telecom and automation loads.
Document contents
- Overview
- Key Features
- Applications
- Available Variants
- Technical Specification (input, output, batteries, system, others)
- Product Catalog
Publication details
- Authors
- Lento Industries
- Publisher
- Lento Industries
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lento Industries Lento Zector series model technical specification table. Lento Industries. https://lentoindia.com/public/products/zector-series-1kva-10kva.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.