LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount: technical specifications

Original title LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount, technical specifications p.2

LTI Power Systems

LTI Power Systems's Series 1000 is a floor-mount industrial UPS family from 3 to 18.75 kVA (3-15 kW at PF 0.8, 60 Hz) with input-to-output isolation, a zero-break static switch and a 20-year design life.

On this page

Overview

Series 1000 has six models: LT1030 (3.75 kVA / 3 kW), LT1050 (6.25 / 5), LT1075 (9.375 / 7.5), LT1080 (10 / 8), LT1100 (12.5 / 10) and LT1150 (18.75 / 15 kW). Ratings are at 60 Hz and PF 0.8; at 50 Hz maximum real power drops to 2.4, 4, 6, 6.4, 8 and 12 kW. The unit is a true on-line industrial UPS with input-to-output isolation, pure sine wave output and a fully rated solid-state static transfer switch.

Input voltage range is +15% / -25% without using batteries, frequency range 45-65 Hz and power walk-in takes 5 seconds to full load. Output regulation is +/-1% steady state and +/-2% dynamic (100% load step), THD is under 1% on linear and 3% on non-linear load, frequency stability +/-0.01%, and maximum load crest factor 5:1. Efficiency is 81-86% depending on model and load. Overload at 0.8 PF is indefinite at 110%, 10 minutes at 125% and 1 minute at 150%; at 1.0 PF it is 15 seconds at 120% and 8 seconds at 125%.

Battery voltage is 120 Vdc (smaller models) or 360 Vdc (LT1100 and LT1150), with recharge to 90% in under 1 hour after complete discharge. Heat rejection is given as 2,100, 3,500 and 5,250 BTU/hr (by enclosure group) at 1.0 PF load; noise is under 50 dB(A) at 1 m, operating temperature 0-40 C and humidity 0-95% non-condensing. The enclosure is NEMA 1, ANSI 61 gray, forced-air cooled with rear cable entry; dimensions run from 13.3 x 31 x 27.2 in to 18 x 38.5 x 54 in and weight from 310 to 1,200 lb.

Options include multiple output voltages, 50/60 Hz models, an external maintenance bypass switch, Form C alarm contacts, a digital meter panel, extended-runtime battery packs, a surge suppression kit, EPO, a dual input kit and a network communications kit. Seismic Zone 4 construction and build to UL1778, NEMA, NEC, ANSI and FCC standards are stated. The document is the second-page technical table; enclosure grouping and battery inclusion are not resolved per model.

Key points

  1. Models (60 Hz, PF 0.8): LT1030 3.75 kVA / 3 kW, LT1050 6.25 / 5, LT1075 9.375 / 7.5, LT1080 10 / 8, LT1100 12.5 / 10, LT1150 18.75 / 15 kW.
  2. At 50 Hz maximum real power is 2.4, 4, 6, 6.4, 8 and 12 kW.
  3. Input range +15% / -25% (without batteries); 45-65 Hz; 5-second walk-in to full load.
  4. Output regulation +/-1% (steady) and +/-2% (dynamic); THD under 1% (linear), 3% (non-linear); crest factor 5:1.
  5. Efficiency 81-86%; overload at 0.8 PF 10 min at 125%, 1 min at 150%.
  6. Battery 120 Vdc or 360 Vdc; under 1 hour to 90% charge.
  7. Heat rejection 2,100, 3,500, 5,250 BTU/hr (at 1.0 PF load).
  8. Operation 0-40 C, humidity 0-95%, noise under 50 dB(A), NEMA 1.
  9. Size 13.3 x 31 x 27.2 in to 18 x 38.5 x 54 in; weight 310-1,200 lb.
  10. 20-year design life; Seismic Zone 4 construction; built to UL1778.

Using it in design

  • Compare capacity with the PF 0.8 kW value at 60 Hz or the derated kW value at 50 Hz; do not infer a kVA rating for 50 Hz.
  • Carry the low efficiency (81-86%) into the heat-load and cooling calculation; use the BTU/hr figures in the document.
  • For 480 Vac models, show on the drawing that a 208 or 240 Vac bypass input is required.
  • In seismic zones check cabinet anchorage and the 310-1,200 lb floor load.
  • Confirm current orderability and battery inclusion with the manufacturer.

Who should read it

Electrical designers and maintenance engineers seeking a robust isolated UPS for industrial facilities.

Document contents

  1. Series 1000 UPS features and options
  2. Technical specifications: input
  3. Technical specifications: output and efficiency
  4. Technical specifications: battery, environment and enclosure

Publication details

Authors
LTI Power Systems
Publisher
LTI Power Systems
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

LTI Power Systems LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount, technical specifications p.2. LTI Power Systems. https://ltipowersystems.com/files/Datasheet_3-18kva_UPS_Floor3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.