LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount: technical specifications
Original title LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount, technical specifications p.2
LTI Power Systems
LTI Power Systems's Series 1000 is a floor-mount industrial UPS family from 3 to 18.75 kVA (3-15 kW at PF 0.8, 60 Hz) with input-to-output isolation, a zero-break static switch and a 20-year design life.
On this page
Overview
Series 1000 has six models: LT1030 (3.75 kVA / 3 kW), LT1050 (6.25 / 5), LT1075 (9.375 / 7.5), LT1080 (10 / 8), LT1100 (12.5 / 10) and LT1150 (18.75 / 15 kW). Ratings are at 60 Hz and PF 0.8; at 50 Hz maximum real power drops to 2.4, 4, 6, 6.4, 8 and 12 kW. The unit is a true on-line industrial UPS with input-to-output isolation, pure sine wave output and a fully rated solid-state static transfer switch.
Input voltage range is +15% / -25% without using batteries, frequency range 45-65 Hz and power walk-in takes 5 seconds to full load. Output regulation is +/-1% steady state and +/-2% dynamic (100% load step), THD is under 1% on linear and 3% on non-linear load, frequency stability +/-0.01%, and maximum load crest factor 5:1. Efficiency is 81-86% depending on model and load. Overload at 0.8 PF is indefinite at 110%, 10 minutes at 125% and 1 minute at 150%; at 1.0 PF it is 15 seconds at 120% and 8 seconds at 125%.
Battery voltage is 120 Vdc (smaller models) or 360 Vdc (LT1100 and LT1150), with recharge to 90% in under 1 hour after complete discharge. Heat rejection is given as 2,100, 3,500 and 5,250 BTU/hr (by enclosure group) at 1.0 PF load; noise is under 50 dB(A) at 1 m, operating temperature 0-40 C and humidity 0-95% non-condensing. The enclosure is NEMA 1, ANSI 61 gray, forced-air cooled with rear cable entry; dimensions run from 13.3 x 31 x 27.2 in to 18 x 38.5 x 54 in and weight from 310 to 1,200 lb.
Options include multiple output voltages, 50/60 Hz models, an external maintenance bypass switch, Form C alarm contacts, a digital meter panel, extended-runtime battery packs, a surge suppression kit, EPO, a dual input kit and a network communications kit. Seismic Zone 4 construction and build to UL1778, NEMA, NEC, ANSI and FCC standards are stated. The document is the second-page technical table; enclosure grouping and battery inclusion are not resolved per model.
Key points
- Models (60 Hz, PF 0.8): LT1030 3.75 kVA / 3 kW, LT1050 6.25 / 5, LT1075 9.375 / 7.5, LT1080 10 / 8, LT1100 12.5 / 10, LT1150 18.75 / 15 kW.
- At 50 Hz maximum real power is 2.4, 4, 6, 6.4, 8 and 12 kW.
- Input range +15% / -25% (without batteries); 45-65 Hz; 5-second walk-in to full load.
- Output regulation +/-1% (steady) and +/-2% (dynamic); THD under 1% (linear), 3% (non-linear); crest factor 5:1.
- Efficiency 81-86%; overload at 0.8 PF 10 min at 125%, 1 min at 150%.
- Battery 120 Vdc or 360 Vdc; under 1 hour to 90% charge.
- Heat rejection 2,100, 3,500, 5,250 BTU/hr (at 1.0 PF load).
- Operation 0-40 C, humidity 0-95%, noise under 50 dB(A), NEMA 1.
- Size 13.3 x 31 x 27.2 in to 18 x 38.5 x 54 in; weight 310-1,200 lb.
- 20-year design life; Seismic Zone 4 construction; built to UL1778.
Using it in design
- Compare capacity with the PF 0.8 kW value at 60 Hz or the derated kW value at 50 Hz; do not infer a kVA rating for 50 Hz.
- Carry the low efficiency (81-86%) into the heat-load and cooling calculation; use the BTU/hr figures in the document.
- For 480 Vac models, show on the drawing that a 208 or 240 Vac bypass input is required.
- In seismic zones check cabinet anchorage and the 310-1,200 lb floor load.
- Confirm current orderability and battery inclusion with the manufacturer.
Who should read it
Electrical designers and maintenance engineers seeking a robust isolated UPS for industrial facilities.
Document contents
- Series 1000 UPS features and options
- Technical specifications: input
- Technical specifications: output and efficiency
- Technical specifications: battery, environment and enclosure
Publication details
- Authors
- LTI Power Systems
- Publisher
- LTI Power Systems
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LTI Power Systems LTI Series 1000 Industrial UPS 3 to 18kVA Floor Mount, technical specifications p.2. LTI Power Systems. https://ltipowersystems.com/files/Datasheet_3-18kva_UPS_Floor3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.