Solytec LYONN ULT-WI 1-3 kVA UPS Technical Datasheet
Original title Solytec LYONN ULT-WI 1-3kVA technical datasheet, p.1
LYONN (Solytec)
Solytec's LYONN-branded ULT-WI series covers 1000-3000 VA on-line UPSs with a 0.9 output power factor and pure sine output; capacity derates to 80% at 100/200/208 V output and in frequency-converter use.
On this page
Overview
The document is the one-page technical table for the ULT 1000 Wi, 1500 Wi, 2000 Wi and 3000 Wi, which Solytec sells under its own LYONN brand. Capacities are 1000 VA/900 W, 1500 VA/1350 W, 2000 VA/1800 W and 3000 VA/2700 W, so the output power factor is 0.9. Input is single phase with ground, frequency range 40-70 Hz, input power factor is 0.99 or better at full load, and input current THDi is 5% or less.
Output voltage is selectable at 200/208/220/230/240 VAC or 100/110/115/120/127 VAC; regulation in battery mode is +/-1% and frequency 50 or 60 Hz +/-0.1 Hz. Current crest factor is 3:1, THD is 2% or less on linear load and 4% or less on non-linear load. Transfer from AC to battery mode is zero, and inverter-to-bypass transfer is under 4 ms. Efficiency is 89% (1000 and 1500 VA) and 91% (2000 and 3000 VA) in AC mode, 96% in ECO mode and 88% and 90% in battery mode.
The battery is 12 V/9 Ah blocks, 2, 3, 4 and 6 of them by model. The internal battery recovers to 95% capacity in 3 hours at 2 A charging current; charging current defaults to 2 A and is adjustable up to 8 A. Net weight is 11.7, 14.6, 20.3 and 28.0 kg with battery and 6.6, 7, 9.9 and 12.3 kg without. Noise is under 50 dBA at 1 m. Communication is RS-232 or USB, with optional SNMP. A table footnote states that in frequency-converter mode and when output voltage is set to 100/200/208 VAC, capacity drops to 80%.
Key points
- Four models: 1000 VA/900 W, 1500 VA/1350 W, 2000 VA/1800 W, 3000 VA/2700 W.
- In frequency-converter mode and at 100/200/208 VAC output, capacity derates to 80%.
- Input power factor 0.99 or better at full load, THDi 5% or less; input frequency 40-70 Hz.
- Output regulation +/-1% in battery mode; THD 2% on linear and 4% on non-linear load; crest factor 3:1.
- AC-to-battery transfer is zero; inverter-to-bypass transfer is under 4 ms.
- Efficiency: 89% and 91% in AC mode, 96% in ECO mode, 88% and 90% in battery mode.
- Battery 12 V/9 Ah x 2, 3, 4 and 6; 95% in 3 hours at 2 A; charging current adjustable to 8 A.
- Net weight 11.7-28.0 kg with battery, 6.6-12.3 kg without; dimensions 397 x 145 x 220 mm and 421 x 190 x 318 mm (D x W x H).
Using it in design
- With a fixed 0.9 output power factor, compare the load in W; at 100/200/208 V output multiply usable power by 0.8.
- If frequency-converter use is planned, derate capacity to 80%.
- An input power factor of 0.99 and THDi under 5% help compatibility on small generator-fed systems.
- If runtime beyond the internal battery is needed, confirm external battery and charging current setting with the manufacturer.
- The brand belongs to Solytec; the actual manufacturer is not stated in the source, so treat Solytec as the contact for support and spares.
Who should read it
Electrical designers and equipment suppliers selecting an on-line UPS for small and medium loads.
Document contents
- Model and capacity
- Input
- Output
- Efficiency
- Battery
- Physical
- Environment
- Management
Publication details
- Authors
- LYONN (Solytec)
- Publisher
- LYONN (Solytec)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LYONN (Solytec) Solytec LYONN ULT-WI 1-3kVA technical datasheet, p.1. LYONN (Solytec). https://solytec.com.ar/descargas/ups/ups-lyonn-wi-series-1-a-3kva.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.