Mecer Offline Range VUVU technical specifications

Mecer (Mustek)

Mecer (Mustek) VUVU+ offline UPS range offers 600 VA/360 W, 800 VA/480 W, 1000 VA/600 W and 2000 VA/1200 W models with simulated sine output and a typical 2-6 ms transfer time (10 ms maximum).

On this page

Overview

Mecer's product page on its South African site gives the ME-650-VU, ME-850-VU, ME-1000-VU and ME-2000-VU in one table: capacity of 600 VA / 360 W, 800 VA / 480 W, 1000 VA / 600 W and 2000 VA / 1200 W respectively. They are offline (standby) UPS units; output in battery mode is a simulated sine wave and transfer time is typically 2-6 ms, 10 ms maximum.

Input voltage is 110/120 Vac or 220/230/240 Vac, with an operating range of 81-145 Vac or 162-290 Vac and 60/50 Hz auto-sensing frequency. Battery-mode output voltage regulation is +/-10% and frequency 60 or 50 Hz +/-1 Hz. The battery is 12 V 7 Ah: 1 unit for the 650 and 850 models and 2 units for the 1000 and 2000 models; typical recharge is 4-6 hours to 90% capacity.

Physical data list three dimension sets in D x W x H of 287 x 100 x 142 mm, 350 x 146 x 160 mm and 397 x 146 x 205 mm; net weights are 4.25, 4.9, 8 and 11.5 kg. Mecer is a proprietary brand of Mustek. The page includes no efficiency, full-load runtime curve or further safety standards.

Key points

  1. Models: ME-650-VU (600 VA / 360 W), ME-850-VU (800 / 480), ME-1000-VU (1000 / 600), ME-2000-VU (2000 / 1200).
  2. Offline topology; simulated sine output in battery mode.
  3. Input 110/120 Vac or 220/230/240 Vac; range 81-145 Vac or 162-290 Vac; 50/60 Hz auto.
  4. Battery-mode voltage regulation +/-10%; frequency +/-1 Hz.
  5. Transfer time typically 2-6 ms, 10 ms maximum.
  6. Battery 12 V 7 Ah; 1 unit (650 and 850) or 2 units (1000 and 2000).
  7. Recharge 4-6 hours to 90% capacity.
  8. Dimensions 287 x 100 x 142, 350 x 146 x 160, 397 x 146 x 205 mm; net weight 4.25, 4.9, 8, 11.5 kg.

Using it in design

  • Choose the offline topology and its 2-10 ms transfer only for loads that tolerate that interruption.
  • Verify compatibility of simulated-sine output with active-PFC power supplies and motor loads.
  • Compare actual load power with the watt rating (360-1200 W); the VA value is not the limit.
  • Order the input voltage version (110/120 V or 220-240 V) to suit the mains.
  • Calculate runtime for your own load from the one or two 7 Ah batteries.

Who should read it

Buyers seeking simple offline UPS for desktop computers, routers and small office loads.

Document contents

  1. Model and capacity
  2. Input
  3. Output
  4. Battery
  5. Physical

Publication details

Authors
Mecer (Mustek)
Publisher
Mecer (Mustek)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Mecer (Mustek) Mecer Offline Range VUVU technical specifications. Mecer (Mustek). https://mecer.co.za/offline-range-vuvu-me-650-vu-1/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.