Technical guideFree to readYear not stated

Reros N Series Offline UPS Product Specifications

Original title Reros N Series offline UPS product specifications

Reros (Changzhou) Electronics

Eight models of the Reros N series offline UPS, from 450 VA/300 W to 3000 VA/1800 W, with typical 2 to 6 ms transfer time and PWM output on battery; not an online system for data-centre duty.

On this page

Overview

The document is the N series offline UPS product page of the Chinese manufacturer Reros (Changzhou) Electronics. The table lists the N450, N650, N850, N1000, N1200, N1500, N2000 and N3000 models, with capacities from 450 VA/300 W to 3000 VA/1800 W. Every model carries a 0.6 power factor; for example the N1000 is rated 1000 VA/600 W.

The input voltage window is 90 to 132 Vac and 85 to 150 Vac for the 110 V version, and 175 to 265 Vac, 145 to 290 Vac and 175 to 275 Vac for the 220 V version; input frequency is 45 to 65 Hz. The N450 has no automatic voltage regulation (AVR); the other models have CPU-controlled AVR with 3 steps or 2 steps. In battery mode the output waveform is PWM, frequency is 50 or 60 Hz ±0.1 Hz (auto sensing) and transfer time is typically 2 to 6 ms, 10 ms at most.

Batteries are 12 V: one 4.5 Ah in the N450, 7 Ah in the N650, 9 Ah in the N850, two 7 Ah in the N1000 and N1200, two 9 Ah in the N1500 and N2000 (four 7 Ah optional for the N2000) and four 9 Ah in the N3000. Charging restores 90 percent of capacity in 4 to 6 hours. Net weight ranges from 3.8 to 20.4 kg. Communication is RJ45/11 and USB, with LCD or LED display optional.

The manufacturer names the device an offline UPS in the table. With PWM output on battery and a transfer interruption, the series fits desktop and small-office loads rather than serving as a substitute for a double-conversion online UPS for servers and network equipment.

Key points

  1. Eight models from N450 (450 VA/300 W) to N3000 (3000 VA/1800 W).
  2. Offline topology; transfer time typically 2 to 6 ms, 10 ms maximum.
  3. Battery-mode output is PWM, 50 or 60 Hz ±0.1 Hz (auto sensing).
  4. The N450 has no AVR; the others have CPU-controlled 3-step or 2-step AVR.
  5. 220 V version input windows are 175-265, 145-290 and 175-275 Vac; 110 V version 90-132 and 85-150 Vac.
  6. Batteries are 12 V: N450 1 × 4.5 Ah, N3000 4 × 9 Ah.
  7. Charging: 90 percent of capacity in 4 to 6 hours.
  8. Net weight 3.8 to 20.4 kg; sizes 258 × 101 × 141 mm to 412 × 145 × 223 mm.

Using it in design

  • Consider the offline topology for tolerant loads such as office and network edge, not for data-centre critical load; compare the 2 to 10 ms transfer window with load tolerance.
  • If server power supplies have active PFC, confirm compatibility with the stepped PWM battery output with the manufacturer.
  • The table gives kVA and kW separately (0.6 power factor); check the load list in kW.
  • Choose the input range and version according to a 220 V or 110 V local supply.
  • Take battery count and Ah from the table and verify autonomy by a separate calculation.

Who should read it

Designers needing low-capacity protection for small offices and network edges, and teams preparing catalogue data.

Document contents

  1. Model and capacity
  2. AVR
  3. Input features
  4. Output features
  5. Battery
  6. Management and physical size

Publication details

Authors
Reros (Changzhou) Electronics
Publisher
Reros (Changzhou) Electronics
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Reros (Changzhou) Electronics Reros N Series offline UPS product specifications. Reros (Changzhou) Electronics. https://www.rerospower.net/n-series/N%20Series.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.