Korea Sampoong Power On Line UPS catalogue: KSP600 series specifications
Original title Korea Sampoong Power On Line UPS catalogue, KSP600 specifications p.3
Korea Sampoong Power
The On Line UPS catalogue from Korea Sampoong Power describes nine single-phase on-line UPS models in the KSP600 series from 1 kVA to 15 kVA: output power factor 0.8, battery voltage 192 VDC, output THD below 3% on linear load and net weight without battery from 46 kg to 210 kg.
On this page
Overview
The eight-page catalogue presents the on-line UPS products of South Korean manufacturer Korea Sampoong Power; its third page shows the front control panel and the specification table of the KSP600 series. The series has nine models: KSP601 (1 kVA), KSP602 (2 kVA), KSP603 (3 kVA), KSP605 (5.5 kVA), KSP606 (6 kVA), KSP608 (8 kVA), KSP610 (10 kVA), KSP612 (12 kVA) and KSP615 (15 kVA). The KSP605 is explicitly printed as 5.5 kVA, not the 5 kVA its model code might suggest.
The input is single-phase with ground, with a voltage range of 180-260 VAC or 90-130 VAC and a frequency of 50/60 Hz ±5%. Maximum input current at 220 V runs from 6 A for 1 kVA to 84 A for 15 kVA. The output is 220 VAC or 110 VAC with a ±1% voltage tolerance and a frequency of 50/60 Hz ±0.5%. Output power factor is 0.8 and THD is below 3% on linear load. At 110-150% overload the unit transfers to bypass after 20 seconds and returns automatically when the load is back to normal.
The battery system is 192 VDC on all models and uses sealed, maintenance-free lead-acid batteries; charge current is 4 A on every model and charging to 90% capacity takes 8 hours. Noise is below 55 dB at 1 metre, operating temperature is 0-40 °C and humidity 0-95%. Net weights without battery are 46, 60, 75, 65, 69, 105, 115, 120 and 210 kg. The last table row gives packing dimensions: 200 x 600 x 550, 220 x 580 x 700, 310 x 560 x 870 and, for 15 kVA, 740 x 470 x 1180 mm. The catalogue is undated and publishes no kW rating.
Key points
- Nine models: KSP601, 602, 603, 605, 606, 608, 610, 612, 615; 1, 2, 3, 5.5, 6, 8, 10, 12 and 15 kVA.
- Input single-phase, 180-260 VAC or 90-130 VAC, 50/60 Hz ±5%.
- Output 220 VAC or 110 VAC ±1%; frequency 50/60 Hz ±0.5%; power factor 0.8; THD below 3% on linear load.
- Maximum input current at 220 V: 6, 10, 14, 24, 34, 45, 56, 68 and 84 A.
- Overload: transfer to bypass after 20 seconds at 110-150%, automatic return when the load is normal.
- Battery 192 VDC, sealed lead-acid; charge current 4 A; 8 hours to 90% charge.
- Net weight without battery: 46, 60, 75, 65, 69, 105, 115, 120 and 210 kg.
- Noise below 55 dB at 1 metre; operation 0-40 °C, 0-95% humidity.
Using it in design
- The catalogue gives no kW, so obtain the active power from the manufacturer in writing instead of assuming it; current IT loads have a power factor above 0.8, which makes kW the limiting figure.
- Select battery capacity around the 192 VDC string (16 blocks of 12 V) and the 4 A charge current, and allow for a recharge time longer than 8 hours on large-capacity strings.
- Net weights exclude the battery, so add battery weight separately to the floor-loading calculation.
- The dimensions in the table are packing dimensions; request the equipment dimensions from the manufacturer for layout.
- On the single-phase 15 kVA model, use the input current of up to 84 A at 220 V for supply cable and protection selection.
Who should read it
Electrical designers selecting small single-phase UPSs and teams cataloguing Korean UPS products.
Document contents
- KSP600 Series Online UPS
- KSP600 front control panel
- Specifications: Input, Output, Battery, Panel Indication, Communication, Protection, Audible Noise, Environment, General
Publication details
- Authors
- Korea Sampoong Power
- Publisher
- Korea Sampoong Power
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Korea Sampoong Power Korea Sampoong Power On Line UPS catalogue, KSP600 specifications p.3. Korea Sampoong Power. http://www.sampoong.com/catalogue/pdf/pdf_6.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.