Techfine CQ Series 1-10 kVA Online Double-Conversion UPS, PF 1.0 Data Sheet

Original title Techfine CQ Series Online UPS 1-10kVA, Data Sheet table

Guangdong Techfine Electronics

Guangdong Techfine's CQ single-phase on-line UPS series comes in eight columns from 1 to 10 kVA, with real power from 800 W to 10 kW depending on model and 0 ms transfer from mains to battery.

On this page

Overview

The data sheet gives Techfine Electronics' (Foshan, China) CQ series in one table: CQ1KJ(S), CQ1KH, CQ2KJ(S), CQ2KH, CQ3KJ(S), CQ3KH, CQ6K(S) and CQ10K(S). Units are single-phase with earth, double conversion with pure sine output. J models give 800, 1600 and 2400 W (1000, 2000, 3000 VA), H models 1000, 2000 and 3000 W; the 6K gives 6000 VA/6000 W and the 10K 10000 VA/10000 W.

Input voltage window depends on load: 110-300 VAC at 60% load (or 50%) and 160-300 VAC (or 176-300 VAC) at 100% load. Input frequency is 40-70 Hz and input power factor is 0.95, 0.97 or 0.99 and above by model. Output is 220 VAC +/-1%, selectable at 208/220/230/240 V on the panel. In battery mode frequency is 50 Hz +/-0.25 Hz (60 Hz optional), crest factor 3:1, and THD 3% on linear and 6% on non-linear load or less. Transfer from mains to battery is 0 ms and inverter to bypass 4 ms.

The standard battery is 2, 4, 6, 12 or 16 blocks of 12 V/7 Ah (3, 6, 8, 14 options on some models); the long-run configuration uses external batteries and raises charging current to between 4 A and 12 A. Standard models weigh 8.8 kg to 50.1 kg in the table; dimensions run from 352 x 145 x 213 mm to 450 x 192 x 345 mm and 384 x 192 x 730 mm with wheels. Operation is 0-40 C, noise under 50 dBA at 1 m, and communication is RS-232 (SNMP optional).

Key points

  1. Eight columns: CQ1KJ(S) 1000 VA/800 W, CQ1KH 1000 VA/1000 W, CQ2KJ(S) 2000 VA/1600 W, CQ2KH 2000 VA/2000 W, CQ3KJ(S) 3000 VA/2400 W, CQ3KH 3000 VA/3000 W, CQ6K(S) 6000 VA/6000 W, CQ10K(S) 10000 VA/10000 W.
  2. Input window 110-300 VAC (at reduced load) and 160-300 VAC or 176-300 VAC (at 100% load); 40-70 Hz.
  3. Output 220 VAC +/-1%, 208/220/230/240 V selectable; 50 Hz +/-0.25 Hz in battery mode.
  4. THD 3% on linear and 6% on non-linear load or less; crest factor 3:1.
  5. Transfer time is 0 ms mains to battery and 4 ms inverter to bypass under standard conditions.
  6. Standard battery 12 V/7 Ah, 2-16 blocks; long-run charging current 4 A, 4 or 8 A, 2 or 8 A, 1-12 A adjustable.
  7. Net weight 8.8-50.1 kg standard, 5.8-27.7 kg and 9.42-10.4 kg in the long-run configuration.
  8. RH 20-90%, 0-40 C, noise under 50 dBA; RS-232 and optional SNMP.

Using it in design

  • Separate the J and H columns: at the same VA, the J model has a 0.8 power factor and the H model 1.0; size the load in watts.
  • The wide input window suits generator and weak-mains operation, but at 100% load the lower limit is 160 or 176 VAC; evaluate by load factor.
  • Runtime depends on battery count, so choose the standard or long-run column explicitly and state it in the order code.
  • Check the +/-0.25 Hz battery-mode frequency tolerance for frequency-sensitive loads.
  • The wheeled model weighs over 40 kg; reflect this in layout and handling plans.

Who should read it

Designers and suppliers selecting single-phase double-conversion UPSs for small and medium loads.

Document contents

  1. General
  2. Input
  3. Output
  4. Battery (standard and long-run)
  5. Display and alarms
  6. Dimensions and weight
  7. Environment
  8. Control and management

Publication details

Authors
Guangdong Techfine Electronics
Publisher
Guangdong Techfine Electronics
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Guangdong Techfine Electronics Techfine CQ Series Online UPS 1-10kVA, Data Sheet table. Guangdong Techfine Electronics. https://techfinesolar.com/cq-series-online-ups.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.