Technical guideFree to readYear not stated

Zircon ZC-HIP 200 kVA/180 kW 3-Phase/3-Phase True Online UPS Specifications

Original title Zircon ZC-HIP 200kVA/180kW technical specifications

Zircon

The Zircon ZC-HIP 200 kVA/180 kW is a true on-line UPS with three-phase input and output, 0.9 output power factor, 0.99 input PF, 2% THDi, 0 ms transfer and over 93% efficiency in normal mode; backup is 15-30 minutes depending on load.

On this page

Overview

The product page presents the 200 kVA/180 kW tower-type three-phase-in, three-phase-out model from the ZC-HIP series by Zircon of Thailand. The unit is true double conversion and offers wide input voltage and frequency tolerance, LCD and LED display, pure sine output, 3:1 crest factor, automatic restart, battery cold start, advanced battery management, parallel redundancy and optional extension battery. The battery is maintenance-free lead acid. Backup time is given on the page as 15-30 minutes depending on load and is not a guaranteed runtime.

Input is 380/400/415 VAC (3Ph+N+PE) with an operating range of 208-478 VAC, frequency range 40-70 Hz, input power factor 0.99 and THDi of 2% at 100% non-linear load. The bypass voltage range is up to +15% (optional +10%, +25%) and down to -45% (optional -20%, -30%), and generator input is supported. Output is 380/400/415 VAC, output power factor 0.9, voltage regulation +/-2%, battery-mode frequency 50/60 Hz +/-0.1%, and THD under 2% on linear and under 5% on non-linear load. Efficiency is above 93% in normal mode.

Battery voltage is selectable from 384/408/432/456/480 VDC and maximum charge current is 36 A. Line-mode overload is allowed for 60 min below 110%, 10 min below 125% and 1 min below 150%, with immediate shutdown above 150%; in battery mode it is 10 min below 110%, 5 min below 125% and 5 s below 150%. Size is 780 x 600 x 1600 mm (D x W x H) and net weight 355 kg; the page does not say whether batteries are included. Operation is 0-40 C, altitude below 1500 m and humidity 0-95%. Communication is RS232, RS485, parallel, an intelligent slot and optional relay and SNMP cards. Standards are IEC/EN 62040-1, 62040-2 and IEC/EN 60950-1.

Key points

  1. Model ZC-HIP 200 kVA/180 kW; three-phase input, three-phase output, tower.
  2. Input 380/400/415 VAC, operating range 208-478 VAC, 40-70 Hz; input PF 0.99, THDi 2% (100% non-linear load).
  3. Output PF 0.9; regulation +/-2%; THD <2% (linear), <5% (non-linear); crest factor 3:1.
  4. Transfer time 0 ms; efficiency >93% in normal mode; pure sine.
  5. Battery voltage 384/408/432/456/480 VDC selectable; maximum charge current 36 A.
  6. Line-mode overload: <110% for 60 min, <125% for 10 min, <150% for 1 min; battery mode <110% for 10 min, <125% for 5 min, <150% for 5 s.
  7. Size 780 x 600 x 1600 mm (D x W x H); net weight 355 kg.
  8. Backup 15-30 min depending on load; parallel redundancy and extension battery options; operation 0-40 C, altitude <1500 m.

Using it in design

  • With a 0.9 output power factor, use the kW rating directly and size critical load against it.
  • Backup is a 15-30 min band that depends on load; for a target runtime calculate battery capacity and any extension battery need.
  • Match one of the battery voltage options (384-480 VDC) to the cell count of the battery string.
  • No preferred voltage is chosen among 380/400/415 V; set the site voltage at order stage.
  • With net weight of 355 kg and no explicit battery statement on the page, confirm floor loading separately together with the battery bank.

Who should read it

Electrical designers and suppliers selecting mid-size three-phase UPSs.

Document contents

  1. Product description
  2. Input
  3. Output
  4. Battery
  5. System features
  6. Environmental
  7. Physical
  8. Standards

Publication details

Authors
Zircon
Publisher
Zircon
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Zircon Zircon ZC-HIP 200kVA/180kW technical specifications. Zircon. https://zircon.co.th/en/products/product/20607-ZC-HIP-200kVA180KW-33-phase-True-Online-UPS

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.