ALLSAI W PRO 3:3 technical sheet, PDF pp.2–3 (printed 17–18)

ALLSAI LATAM

A Spanish-language technical sheet from ALLSAI LATAM giving eight models of the three-phase on-line double-conversion W PRO 3:3 UPS series: 10 kVA/9 kW to 100 kVA/90 kW, output power factor 0.9, line-mode efficiency of at least 93% on the 10 to 30 kVA models and up to 98% in eco mode, and 0 ms transfer time.

On this page

Overview

The W PRO 3:3 is a family of DSP-controlled on-line UPS units with input power factor correction (active PFC), three-phase input and three-phase output. The sheet groups eight models in two tables: W10kPro, W15kPro, W20kPro and W30kPro in the first; W40kPro, W60kPro, W80kPro and W100kPro in the second. Ratings are 10 kVA/9 kW, 15 kVA/13.5 kW, 20 kVA/18 kW, 30 kVA/27 kW, 40 kVA/36 kW, 60 kVA/54 kW, 80 kVA/72 kW and 100 kVA/90 kW. The unit has a dual input and can run as a 50/60 Hz frequency converter.

On the 10 to 30 kVA models nominal voltage is 360, 380, 400 or 415 V AC. The input runs without derating from 277 to 485 V; between 190 and 277 V the load is limited linearly from 100% to 50%. Input power factor is at least 0.99, output voltage regulation ±1%, and output voltage distortion at most 2% on linear load and 5% on non-linear load. On overload the unit transfers to bypass after 10 minutes at 102% to 125%, after 1 minute at 125% to 150% and after 0.5 seconds above 150%.

Each model comes in two versions. The standard version has internal batteries: 20 x 7 Ah at 10 kVA, 40 x 7 Ah at 15 kVA, 40 x 9 Ah at 20 kVA and 60 x 9 Ah at 30 kVA, recharged to 90% of capacity in 4 hours. The long-backup L version works with external batteries; on the 10 to 30 kVA models the battery count is selectable at 14, 16, 18 or 20, the cabinet measures 350 x 655 x 732 mm and weight is 55 to 65 kg. In parallel operation the 10 to 30 kVA models connect up to 6 units. The sheet notes that specifications can change without prior notice.

Key points

  1. Eight models: W10kPro 3/3 (10 kVA/9 kW), W15kPro (15 kVA/13.5 kW), W20kPro (20 kVA/18 kW), W30kPro (30 kVA/27 kW), W40kPro (40 kVA/36 kW), W60kPro (60 kVA/54 kW), W80kPro (80 kVA/72 kW), W100kPro (100 kVA/90 kW).
  2. Output power factor 0.9; input power factor at least 0.99; transfer time 0 ms; crest factor 3:1.
  3. Efficiency on the 10 to 30 kVA models: at least 93% in line mode, at least 93% in battery mode, at least 98% in eco mode.
  4. Input voltage range for 10 to 30 kVA: 277 to 485 V AC without derating, linear load limiting between 190 and 277 V AC.
  5. Internal batteries in the standard version: 20 x 7 Ah, 40 x 7 Ah, 40 x 9 Ah and 60 x 9 Ah; battery voltage 240 V DC; 90% recharge in 4 hours.
  6. Standard version weights (10, 15, 20, 30 kVA): 115, 155, 175 and 235 kg; cabinets 350 x 785 x 858 mm or 350 x 785 x 1078 mm.
  7. L version (10 to 30 kVA): 350 x 655 x 732 mm; 55, 60, 61 and 65 kg; battery voltage 192 V DC (168, 216 or 240 V optional).
  8. Operating temperature 0 to 40 °C; noise at 1 m at most 60 to 65 dB on the 10 to 30 kVA models; up to 6 units in parallel.

Using it in design

  • Match the load to the kW rating: at 0.9 power factor the 100 kVA model carries 90 kW.
  • Calculate heat load from line-mode efficiency (at least 93% for 10 to 30 kVA); the 98% eco figure applies only when running through the bypass.
  • Battery capacity in the standard version is limited to 7 or 9 Ah blocks; for long backup specify the L version with an external battery cabinet.
  • On the L version, settle the battery count (14 to 20) and charging current with the manufacturer against the chosen battery capacity.
  • Use the standard version's weight including batteries (235 kg at 30 kVA) for floor loading.

Who should read it

Electrical engineers selecting 10 to 100 kVA three-phase UPS units for Latin American projects, and teams preparing product catalogue data.

Document contents

  1. Principales características
  2. Especificaciones técnicas: W10kPro a W30kPro
  3. Entrada
  4. Salida
  5. Eficiencia
  6. Baterías
  7. Generalidades
  8. Comunicaciones
  9. Especificaciones técnicas: W40kPro a W100kPro

Publication details

Authors
ALLSAI LATAM
Publisher
ALLSAI LATAM
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ALLSAI LATAM ALLSAI W PRO 3:3 technical sheet, PDF pp.2–3 (printed 17–18). ALLSAI LATAM. https://allsai.com/wp-content/uploads/2019/03/Ficha-Te%CC%81cnica-UPS%C2%B4s-W-PRO-33.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.