A two-page Apollo datasheet, version V26.1, giving two models of the single-phase transformerless on-line AP9100S UPS series: the AP9106S at 6 kVA/6 kW and the AP9110S at 10 kVA/10 kW, with output power factor 1, efficiency of at least 94% at full load and at least 98% in ECO mode, and 0 ms transfer time.

On this page

Overview

The AP9100S is a true on-line UPS series with dual-core DSP control and three-level inverter technology. Input and output are single-phase three-wire (phase, neutral, PE); rated voltage is 208, 220, 230 or 240 V AC and frequency 50/60 Hz with auto-sensing. With active power factor correction the input power factor is at least 0.99 and input current distortion at most 5%. Output power factor is 1, with 0.9 applying only at 208 V output. The unit can also run in 50/60 Hz frequency conversion mode.

The input voltage range is 176 to 288 V AC at full load; between 90 and 176 V the load is limited linearly down to 30%. This arrangement delays the move to battery at low mains voltage and so reduces battery discharge time. Output voltage regulation is ±1%, and voltage distortion is below 1% at full linear load and below 4% at full non-linear load. Overload capacity is 10 minutes at 105% to 110%, 1 minute at 110% to 125% and 30 seconds at 126% to 150%. Up to 4 units can be connected in parallel.

The battery circuit defaults to 192 V DC and 16 blocks; the block count is settable from 10 to 22, and with 10 to 15 blocks the load is limited down to 50%. On the standard model the internal batteries are 16 x 12 V 7 Ah for the AP9106S and 16 x 12 V 9 Ah for the AP9110S, recharged to 90% capacity in 8 hours. On the long-time model charging current is 5 A, with 12 A optional. The cabinet is 191 x 500 x 515 mm on both models, and net weight is 51.5 kg and 60.5 kg.

Key points

  1. Models: AP9106S 6 kVA/6 kW and AP9110S 10 kVA/10 kW; output power factor 1 (0.9 at 208 V output).
  2. Efficiency: at least 94% at 100% load, maximum 95% at 60% load, at least 98% in ECO mode.
  3. Transfer time 0 ms; output voltage regulation ±1%; crest factor 3:1.
  4. Input voltage range 176 to 288 V AC at full load; linear load limiting down to 30% between 90 and 176 V AC; frequency range 40 to 70 Hz.
  5. Input power factor at least 0.99; THDi at most 5%; output THDv below 1% on linear load.
  6. Battery: default 192 V DC (120 to 264 V DC), 16 blocks (settable 10 to 22); internal 16 x 7 Ah or 16 x 9 Ah.
  7. Dimensions 191 x 500 x 515 mm (W x D x H); net weight 51.5 kg for the AP9106S and 60.5 kg for the AP9110S.
  8. Operating temperature 0 to 40 °C; noise below 58 dB at 1 m; IP20; up to 4 units in parallel.

Using it in design

  • Thanks to unity power factor, match the 10 kVA model to 10 kW of IT load, and allow for the 0.9 power factor at 208 V output.
  • Calculate heat load from the 94% full-load efficiency (about 0.64 kW of loss at 10 kW load).
  • Where the internal 7 or 9 Ah batteries give too little time, specify the long-time model with an external battery cabinet and choose the 5 A or 12 A charger from the battery capacity.
  • Add the parallel kit to the specification for N+1, keeping the limit of 4 units in mind.
  • For sites above 1000 m, apply the 1% power reduction per 100 m.

Who should read it

Electrical engineers selecting 6 to 10 kVA single-phase UPS units for small server rooms and edge sites, and teams preparing product catalogue data.

Document contents

  1. Apollo True online AP9100S Series UPS: features
  2. Rear panel connections
  3. Input
  4. Output
  5. Batteries
  6. System
  7. Others

Publication details

Authors
Apollo Vietnam (brand)
Publisher
Apollo Vietnam (brand)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Apollo Vietnam (brand) Apollo AP9100S 6–10kVA datasheet V26.1, PDF p.2. Apollo Vietnam (brand). https://www.apolloups.com/wp-content/uploads/2022/08/AP9100S-6-10kVA-Datasheet-V26.1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.