Ampace AIDC PU100 and PU200 battery systems
Ampace
Ampace's energy storage solutions page presents two lithium battery cabinets for data-centre UPS backup: the PU100 with twelve modules delivers 63.8 kWh nominal energy and 329 kW output power, and the PU200 with twelve modules 56.5 kWh and 462 kW; each cabinet weighs 900 kg and the solution is UL 9540A safety certified.
On this page
Overview
The page presents Ampace's energy storage products in three fields: data centre, commercial and industrial storage, and residential storage. The data-centre section is called the AIDC solution and targets uninterrupted power and redundant DC power backup. Four highlights are listed: UL 9540A safety certification with no electrolyte leakage over life, support for dynamic paralleling with a pluggable and replaceable battery management system (BMS), suitability for data-centre installation, and compatibility with both traditional and modular deployments.
Two cabinet types appear among the related products. The PU100 uses cells of 104 Ah nominal capacity and offers 63.8 kWh nominal energy over an operating voltage range of 537.6 to 662.4 V; with twelve modules output power is 329 kW, weight 900 kg, and the cabinet is 600 mm wide, 2000 mm high and 1000 mm deep. The PU200, at 92 Ah, gives 56.5 kWh and 462 kW with twelve modules over 518.4 to 662.4 V; its cabinet is 600 x 2050 x 890 mm (width, height, depth) and 900 kg. The page gives the operating voltage range only.
Comparing the two, the PU200 offers higher power from less energy and suits short, high-power discharge, while the PU100 carries more energy. The same section also lists a cell for in-rack battery backup units: 2.45 Ah, 3.20 V, 7.80 Wh. The page states that its data come from the Ampace laboratory and that actual usage conditions govern. Discharge time curves, short-circuit current and a UPS compatibility list are not on the page; they come from the manufacturer's product datasheets.
Key points
- PU100: nominal capacity 104 Ah, operating voltage 537.6 to 662.4 V, nominal energy 63.8 kWh, output power 329 kW (12 modules).
- PU100 cabinet W600 x H2000 x D1000 mm; weight 900 kg (12 modules).
- PU200: nominal capacity 92 Ah, operating voltage 518.4 to 662.4 V, nominal energy 56.5 kWh, output power 462 kW (12 modules).
- PU200 cabinet W600 x H2050 x D890 mm; weight 900 kg (12 modules).
- The solution is UL 9540A safety certified and supports dynamic paralleling and a pluggable BMS.
- In-rack backup (BBU) cell: 2.45 Ah, 3.20 V, 7.80 Wh.
Using it in design
- Choose the cabinet from the power to energy ratio: the PU200 with 462 kW and 56.5 kWh suits a few minutes of high-power backup, the PU100 with 63.8 kWh a longer duration.
- Compare the UPS DC bus voltage window with the cabinet's operating voltage range (537.6 to 662.4 V for the PU100).
- Calculate floor loading from the 900 kg cabinet mass on a 600 mm wide footprint, and check point loads on raised floors.
- For the fire safety assessment, ask the manufacturer for the UL 9540A test report and treat battery room layout together with the local code.
- For the required backup time, obtain constant-power discharge data and the end-of-life capacity margin from the manufacturer.
Who should read it
Electrical engineers designing data-centre UPS battery systems with lithium technology, and decision makers choosing battery technology.
Document contents
- AIDC Solution
- Solution Highlights
- Related Products: PU100, PU200, BBU CELL
- C&I Energy Storage Solution
- Residential Energy Storage
Publication details
- Authors
- Ampace
- Publisher
- Ampace
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ampace Ampace AIDC PU100 and PU200 battery systems. Ampace. https://en.ampace.com/solutions/energy-storage
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.