Dahua DHB Conventional: battery specification table
Dahua Battery (Fujian Quanzhou)
A product page from Dahua Battery (Fujian Quanzhou) listing the DHB conventional series of valve-regulated sealed lead-acid batteries in one table: 79 rows at 6 V and 12 V, C20 capacities from 0.8 to 200 Ah, C10 and C5 values, maximum discharge and charge currents, and internal resistance.
On this page
Overview
The page is on the Beijing branch site of Dahua Battery, founded in 1994, which presents itself as one of China's large manufacturers of lead-acid batteries and plates. The conventional DHB series is sealed and maintenance-free. The manufacturer states a life of up to 8 years in float service. Positive and negative plates are cast from a quaternary alloy of lead, calcium, tin and aluminium. Self-discharge is low: a battery can stand for six months at 20 °C without recharging.
Applications are electronic instruments, UPS and EPS systems, emergency lighting, and security and alarm systems. For each model the table gives voltage, the 20-hour, 10-hour and 5-hour capacities (Ah), length, width, height and total height (mm), weight (kg), terminal type, maximum discharge current, maximum charge current and internal resistance (mΩ). C20, C10 and C5 are in separate columns; for DHB12-100, for example, the values are 100, 93 and 85 Ah.
The table has 28 rows at 6 V (DHB610 to DHB6140, 1 to 14 Ah) and 51 rows at 12 V (DHB1208 to DHB12-200, 0.8 to 200 Ah). Values for the large models are: DHB12-100 at 328 x 172 x 222 mm, 30 kg, 500 A maximum discharge current and 5 mΩ internal resistance; DHB12-200 at 522 x 240 x 219 mm (240 mm total height), 66.4 kg, 1000 A maximum discharge current and 4 mΩ. Maximum charge current is 0.3 times the C20 capacity in every row.
Nine model codes appear in more than one row with different values: DHB610, DHB640, DHB6120, DHB1250, DHB1278, DHB12120, DHB12400, DHB12650 and DHB12900. DHB12400, for example, is listed in three rows at 13.9, 14 and 15.2 kg, and DHB12650 in two rows at 65 and 68 Ah. The page does not give the end voltage or temperature at which capacities are measured, constant-power discharge tables or charging voltages; those data belong to the model datasheets.
Key points
- Series: DHB conventional type, valve-regulated sealed lead-acid; life up to 8 years in float service.
- The table has 79 rows: 28 at 6 V (1...14 Ah) and 51 at 12 V (0.8...200 Ah); capacities are C20 based.
- Each row gives C20, C10 and C5 separately; DHB12-100: 100 / 93 / 85 Ah.
- DHB12-100: 328 x 172 x 222 mm, 30 kg, maximum discharge 500 A, maximum charge 30 A, internal resistance 5 mΩ.
- DHB12-200: 522 x 240 x 219 mm (240 mm total height), 66.4 kg, maximum discharge 1000 A, maximum charge 60 A, internal resistance 4 mΩ.
- DHB1270 (12 V 7 Ah): 151 x 66 x 95 mm (100 mm total height), 2.35 kg, maximum discharge 70 A, internal resistance 25 mΩ.
- Maximum charge current is 0.3 times the C20 capacity (30 A for 100 Ah, for example).
- Plates are a lead, calcium, tin and aluminium quaternary alloy; a battery can stand 6 months at 20 °C without charging.
- Nine model codes repeat across rows with different weight or capacity (DHB12400, for example: 13.9 / 14 / 15.2 kg).
Using it in design
- Pick the column that matches the discharge duration for runtime calculations; do not use C20 directly for short UPS discharges, and request the constant-power table from the manufacturer.
- For repeated model codes (such as DHB12400, DHB12650 and DHB12900), confirm the exact variant, weight and capacity with the manufacturer before ordering.
- Set the charger current limit from the maximum charge current in the table (0.3 x C20).
- Record the internal resistance as the baseline for commissioning measurements and follow the trend during maintenance.
- Use total height (including terminals) and block weight for cabinet layout; 240 mm and 66.4 kg for DHB12-200.
- Treat the maximum discharge current as the upper bound when selecting DC cables and the battery breaker.
Who should read it
Electrical designers selecting small and medium VRLA batteries for UPS and emergency power systems, engineers laying out battery cabinets, and maintenance teams.
Document contents
- 产品特点 (Product features)
- 应用范围 (Applications)
- 型号表: 电压, 容量 (20hr, 10hr, 5hr), 外形尺寸, 重量, 端子, 最大放电电流, 最大充电电流, 内阻 (Model table)
Publication details
- Authors
- Dahua Battery (Fujian Quanzhou)
- Publisher
- Dahua Battery (Fujian Quanzhou)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Dahua Battery (Fujian Quanzhou) Dahua DHB Conventional: battery specification table. Dahua Battery (Fujian Quanzhou). http://dahuabattery.net/pro_info1.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.