Microtex OPzS stationary battery brochure

Microtex

The Microtex OPzS series is a flooded tubular stationary cell of 100-3000 Ah (C10 to 1.85 V, 27 C) in transparent SAN containers with a 20-year float life, recommended for large UPS, power plants and telecom.

On this page

Overview

Bangalore-based Microtex offers its CALCIUM-Plus Standby-Power OPzS series in capacities from 100 Ah to 3000 Ah. The company says it has operated since 1969 and makes its lead alloys, oxides, grid castings, pasted plates, containers and separators in house. OPzS stands for Ortsfest (stationary), Pz (tubular plate) and S (flooded). The cells are recommended for nuclear and power generation plants, petrochemical, switchgear and control applications, wind, hydro and solar PV, large UPS systems, railway signalling and telecommunications.

Features include a calcium+ low-antimony selenium grid alloy, thicker spines for positive tubular plates, casting at 150 bar, high-impact transparent SAN containers, ABS covers with polarity indicators and hardened lead-alloy terminal posts with copper inserts. The manufacturer states a 20-year float life and seismic qualification, factory-preformed plates so no extra field cycling is needed, and reduced watering. Standards are DIN 40 736 part 1, IS 1651-1993, IEC 60896-11 tests and DIN EN 50272-2 ventilation safety; the company is ISO 9001:2015 and ISO 14001:2015 certified.

The tables list seventeen models from 2 OPzS 100 to 24 OPzS 3000. Capacity is given at the C10 rate to 1.85 V/cell final voltage at 27 C; discharge current (A) and discharge power (W) are also given from 1 minute to hours for final voltages of 1.70, 1.75, 1.80, 1.85 and 1.90 V/cell. For example the 1-hour current of the 2 OPzS 100 is 53.78 A at 1.70 V and 40.57 A at 1.85 V. Discharge current should not be used in place of capacity.

For charging, the IU characteristic is given with 2.23 V/cell +/-1% (between 10 and 55 C), float current of 15 mA per 100 Ah (30 mA at end of life), and boost charge of 2.35-2.40 V/cell (time limited). Normal depth of discharge is up to 80%. IEC 60896-11 cycles are above 1500, IEC 61427 cycles above 3000, self-discharge is about 3% per month at 20 C, operating temperature is -20 to 55 C (recommended 10-30 C) and the water refilling interval is more than 2-3 years at 20 C. Maintenance calls for checking battery and pilot cell voltage and temperature every 6 months and recording values every 12 months.

Key points

  1. OPzS series, 100-3000 Ah (C10 to 1.85 V, 27 C); seventeen models from 2 OPzS 100 to 24 OPzS 3000.
  2. Flooded tubular-plate stationary cells in transparent SAN containers; Calcium+ low-antimony selenium alloy.
  3. 20-year stand-by float life (27 C); IEC 60896-11 cycles above 1500; IEC 61427 cycles above 3000.
  4. Float charge 2.23 V/cell +/-1%; float current 15 mA/100 Ah (30 mA/100 Ah at end of life).
  5. Boost charge 2.35-2.40 V/cell; 6 hours to 88% (1.5 x I10, 2.23 V/cell).
  6. Discharge tables for 1.70, 1.75, 1.80, 1.85 and 1.90 V/cell as current and power (27 C).
  7. Normal depth of discharge up to 80%; deeper discharges are to be avoided.
  8. Self-discharge about 3% per month at 20 C; operation -20 to 55 C (recommended 10-30 C).
  9. Standards: DIN 40 736-1, IS 1651-1993, IEC 60896-11, DIN EN 50272-2; ISO 9001 and 14001.
  10. Water refilling interval more than 2-3 years at 20 C.

Using it in design

  • In large UPS battery sizing use the discharge current and power tables for the relevant final voltage (1.70-1.90 V/cell) and time, not the C10 capacity.
  • Set float voltage at 2.23 V/cell and apply 3 mV/C temperature correction outside 10-55 C.
  • For flooded cells design ventilation and hydrogen removal to DIN EN 50272-2 and plan access for water refilling.
  • Limit depth of discharge to 80% normally and tie the final voltage choice to the load profile.
  • For the life expectation (20 years at 27 C) add temperature control and the 6- and 12-month maintenance schedule to the operating plan.

Who should read it

Electrical designers sizing flooded OPzS battery banks for large UPS, substations and process plants.

Document contents

  1. OPzS series overview
  2. CALCIUM-Plus features and advantages
  3. Discharge current tables (1.70-1.90 V/cell, 27 C)
  4. Discharge power tables (1.70-1.85 V/cell, 27 C)
  5. Specifications: charging, discharge, maintenance, operational data
  6. Cell and connection layout

Publication details

Authors
Microtex
Publisher
Microtex
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Microtex Microtex OPzS stationary battery brochure. Microtex. https://microtex.com/wp-content/uploads/2026/10/Microtex-OPzS-Battery.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.