MIDAC OPzS Standby Specification 11/2024
Original title MIDAC OPzS standby specification 11/2024
MIDAC
A MIDAC specification for 22 models of vented tubular lead-acid OPzS cells, from 2 OPzS 100 to 24 OPzS 3000, with capacity, internal resistance, short-circuit current, dimensions and weights.
On this page
Overview
The specification presents the 2 V OPzS series for telecommunications, power plants, substations, emergency power, wind and solar generation, railways and UPS units. The manufacturer states 20 years design life, more than 1500 deep discharge cycles, extended topping-up intervals, high charging efficiency, minimal positive growth and improved safety against accidental contact. Referenced standards are the EUROBAT guide, EN 60896-11 and EN IEC 62485-2.
In the main table, actual 10-hour capacity (Ah) is a column separate from the model name; for example 113 Ah for 2 OPzS 100 and 3244 Ah for 24 OPzS 3000. The 120-hour capacity, internal resistance (mOhm), short-circuit current (kA), length, width and height, wet and dry weight, electrolyte weight and volume and number of terminals are also separate columns. Internal resistance spans 1.55 mOhm to 0.14 mOhm, short-circuit current 1.29 kA to 15.86 kA, and wet weight 16.3 kg to 226.3 kg.
The construction and operation section lists tubular positive plates (lead-selenium grid, Sb below 2%), flat pasted negative plates, microporous separators, a transparent SAN container (optional UL94 V0 flame-retardant PC), dilute sulfuric acid electrolyte at SG 1.240 plus or minus 0.01 at 20 degrees C and ceramic flame-arrestor vents. Float voltage is 2.22-2.23 V per cell, maximum float and boost current 0.15 C10, equalise voltage 2.35-2.45 V per cell, operating temperature minus 10 to plus 60 degrees C, self-discharge below 4% per month at 20 degrees C and connection bolt torque 22 plus or minus 1 Nm.
The document also shows curves for how capacity, float voltage, lifetime and cycle count vary with temperature and depth of discharge. It contains only published values; unpublished fields of each model should not be derived. The cells are vented, so the battery room needs ventilation and topping-up maintenance.
Key points
- 22 models: from 2 OPzS 100 to 24 OPzS 3000 (types with 2, 3, 4, 5, 6, 5, 6, 7, 6, 7, 8, 9, 10, 11, 12, 12, 13, 14, 15, 16, 20 and 24 positive plates in the order of the table).
- Actual 10-hour capacity is a column separate from the model name: for example 113 Ah for 2 OPzS 100, 1277 Ah for 12 OPzS 1200 and 3244 Ah for 24 OPzS 3000; 120-hour capacity is given separately.
- Internal resistance ranges from 1.55 mOhm (2 OPzS 100) to 0.14 mOhm (24 OPzS 3000); short-circuit current from 1.29 kA to 15.86 kA.
- Wet weight is 16.3 kg (2 OPzS 100) to 226.3 kg (24 OPzS 3000), dry weight 11.3 to 162.9 kg; electrolyte weight and volume are published in separate columns.
- Float voltage 2.22-2.23 V per cell; equalise voltage 2.35-2.45 V per cell; maximum float and boost current 0.15 C10.
- Operating temperature minus 10 to plus 60 degrees C; self-discharge below 4% per month at 20 degrees C; connection bolt torque 22 plus or minus 1 Nm.
- The manufacturer states 20 years design life and over 1500 deep discharge cycles; electrolyte SG 1.240 plus or minus 0.01 at 20 degrees C.
- Referenced standards are the EUROBAT guide, EN 60896-11 and EN IEC 62485-2.
Using it in design
- In battery sizing, use the actual 10-hour capacity column, not the number in the model name; check the 120-hour value only for long-duration backup.
- Use short-circuit current and internal resistance in battery breaker, fuse and DC busbar design; do not generalise a model's short-circuit value across a capacity class.
- Take wet weight and dimensions into rack and floor-loading calculations; reflect in the transport and commissioning plan that wet and dry weights are published separately.
- Set the charger or UPS rectifier to a float voltage of 2.22-2.23 V per cell and a maximum current of 0.15 C10, and use the temperature compensation curve.
- For vented cells, add battery room ventilation, topping-up interval and connection bolt torque (22 Nm) to the maintenance procedure.
Who should read it
Electrical engineers sizing batteries for UPS and DC power systems, and teams cataloguing battery models.
Document contents
- Advantages, main applications and standard references
- Model list and main technical table
- Construction and materials
- Operation parameters
- Performance curves: capacity, float voltage, lifetime, cycle count
Publication details
- Authors
- MIDAC
- Publisher
- MIDAC
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
MIDAC (2024). MIDAC OPzS standby specification 11/2024. MIDAC. https://midacbatteries.com/wp-content/uploads/2026/02/SPE-OPzS_STANDBY_EN-11_2024-5013999-0204-00.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
