Panna GSMF400 industrial stationary cell

Panna Battery

Panna Battery's GSMF400 is a 2 V, 400 Ah (C20) maintenance-free industrial cell: 211 x 176 x 367 mm (total height), M8 terminal, maximum charge current 80 A and 0.36 mohm internal resistance.

On this page

Overview

The page presents the GSMF400 cell from Bangladesh's Panna Battery. The cell has a nominal voltage of 2 V and a capacity of 400 Ah at the 20-hour rate (C20). The product is listed under forklift, tower and golf cart batteries and under industrial categories. The manufacturer highlights maintenance-free construction, long float design life, high safety, low self-discharge, low internal resistance, high-grade original lead and outstanding low-temperature performance.

The technical table gives dimensions and electrical values. Length is 211 mm, width 176 mm, height 329 mm and total height including terminals 367 mm. Terminal type is M8, maximum charge current is 80 A and internal resistance is written as 0.36 mohm. The page states no compatibility for a UPS string, cell count or float voltage.

The document is a product page; it contains no discharge table, cycle-life curve or certification detail. For a data-centre designer its value is the basic physical and electrical data of a 400 Ah class battery in 2 V single-cell form. Cell count and string voltage must be set by the designer from the UPS DC bus voltage.

Key points

  1. Model GSMF400; 2 V; nominal capacity 400 Ah (C20).
  2. Dimensions: length 211 mm, width 176 mm, height 329 mm, total height 367 mm.
  3. Terminal type M8.
  4. Maximum charge current 80 A.
  5. Internal resistance 0.36 mohm.
  6. Maintenance-free construction, long float life, low self-discharge and low-temperature performance are stated.

Using it in design

  • Divide the UPS DC bus voltage by 2 V to find the cell count of the string; the page gives no string compatibility.
  • Compare the 80 A maximum charge current with the current limit of the UPS charger.
  • Check the 211 x 176 x 367 mm cell dimensions against rack internal dimensions and terminal connection clearance.
  • Use the 0.36 mohm internal resistance as input to short-circuit current and voltage drop calculations.

Who should read it

Electrical engineers designing UPS battery strings from 2 V cells and teams cataloguing battery data.

Publication details

Authors
Panna Battery
Publisher
Panna Battery
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Panna Battery Panna GSMF400 industrial stationary cell. Panna Battery. https://pannagroupbd.com/product/gsmf400

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.