Faran online UPS catalogue, Titan Plus
Original title Faran online UPS catalogue, Titan Plus, PDF pp.1–2
Faran
A 12-page online UPS catalogue from Iranian brand Faran whose first two pages describe the Titan Plus high-frequency double-conversion single-phase series: 1 kVA / 900 W, 2 kVA / 1800 W, 3 kVA / 2700 W, 6 kVA / 5400 W and 10 kVA / 9000 W, with input power factor of at least 0.99 and AC-mode efficiency of at least 92% at 6-10 kVA.
On this page
Overview
The catalogue presents the online UPS products of the Faran brand with Persian introduction pages and English technical tables; the document is hosted on a distributor site. The first section is given to the Titan Plus series and later pages cover other series such as the rack-mount Vigor RT. Titan Plus is a double-conversion online UPS using high-frequency PWM. The introduction page lists the wide 110-300 V input range, active PFC, smart battery management, cold start from battery, EMI/RFI filters, ECO mode and an EPO input; RS-232 is standard and USB and SNMP are options.
The technical table gives five capacities, all at power factor 0.9. Rated voltage is set from the LCD at 208/220/230/240 VAC. The input voltage range is 110-300 VAC at half load and 160-300 VAC at full load; frequency is 40-70 Hz with auto sensing. Output voltage regulation is ±1%, frequency in battery mode is 50/60 Hz ±0.2 Hz and crest factor is 3:1. Voltage distortion is at most 2% on linear load and below 5% on non-linear load. Transfer from AC mode to battery mode takes 0 ms.
The table gives the two power groups in separate columns. In the 1-3 kVA group AC-mode efficiency is at least 90%, battery mode at least 87% and ECO mode at least 94%; transfer from inverter to bypass typically takes 4 ms, and the unit goes to bypass after 30 seconds at 105-150% overload and after 300 ms above 150%. In the 6-10 kVA group the efficiencies are at least 92%, 91% and 98%; transfer to bypass takes 0 ms, and the unit goes to bypass after 3 minutes at 105-125% and after 30 seconds at 125-150%.
Each capacity comes in two versions: S is the standard model with internal batteries and H is the long backup time model with external batteries. The DC bus is 36 V at 1 kVA, 96 V at 2 and 3 kVA and 240 V at 6 and 10 kVA; the standard models hold 3, 8, 8, 20 and 20 blocks of 9 Ah respectively. Charge current on the standard model is 1 A and recharge to 90% capacity takes 8 hours. Net weights run from 10.1 kg to 70.8 kg for the S version and 5.6 kg to 22.8 kg for H. Capacity is derated to 70% in frequency converter (CUCF) mode and to 90% when output is set to 208 VAC.
Key points
- Capacities: 1 kVA / 900 W, 2 kVA / 1800 W, 3 kVA / 2700 W, 6 kVA / 5400 W, 10 kVA / 9000 W; S standard (internal batteries) and H long backup versions.
- Input: 208/220/230/240 VAC, 110-300 VAC at half load, 160-300 VAC at full load, 40-70 Hz, power factor ≥ 0.99.
- Output: ±1% regulation, THD ≤ 2% on linear and < 5% on non-linear load, crest factor 3:1, AC to battery transfer 0 ms.
- Efficiency (1-3 kVA): AC ≥ 90%, battery ≥ 87%, ECO ≥ 94%; (6-10 kVA): AC ≥ 92%, battery ≥ 91%, ECO ≥ 98%.
- Overload (6-10 kVA): bypass after 3 minutes at 105-125% and after 30 seconds at 125-150%; (1-3 kVA): bypass after 30 seconds at 105-150% and after 300 ms above 150%.
- DC bus: 36 V (1 kVA), 96 V (2-3 kVA), 240 V (6-10 kVA); internal batteries 3, 8, 8, 20 and 20 blocks of 9 Ah.
- Charging: 1 A on the standard model; 8 hours to 90% capacity.
- Dimensions (WxDxH): 1 kVA 144 x 357 x 215 mm; 2-3 kVA 190 x 452 x 341 mm; 6-10 kVA 262 x 514 x 455 mm (H) and 262 x 514 x 735 mm (S).
- Net weight (S): 10.1, 20.5, 25.7, 64.1 and 70.8 kg; (H): 5.6, 11.0, 11.6, 22.1 and 22.8 kg.
- Derating: 70% in CUCF mode, 90% at 208 VAC output; ambient 0-40 °C, 20-90% humidity non-condensing.
Using it in design
- Compare the load against the W value: at power factor 0.9 the 10 kVA model carries 9 kW, falling to 90% (8.1 kW) at 208 VAC output.
- Prefer the 6-10 kVA group for critical IT load, where transfer to bypass is 0 ms; compare the typical 4 ms transfer of the 1-3 kVA group with load hold-up time.
- With a 1 A charge current and 8-hour recharge on the standard model, record in the operations plan that autonomy drops on repeated outages; choose the H version with an external battery set for long autonomy.
- Use the efficiency floors for the heat load: at 9 kW load and 92% efficiency the loss is about 0.78 kW.
- Check floor and shelf loading with the S version weight; the 10 kVA standard model weighs 70.8 kg and stands 735 mm high.
- Design the battery string for the 36, 96 or 240 V bus of the chosen capacity and select the external battery cabinet breaker accordingly.
Who should read it
Electrical designers selecting a 1-10 kVA single-phase online UPS, engineers planning edge and branch IT rooms and teams assessing suppliers in the Iranian market.
Document contents
- Titan Plus: Online High frequency UPS introduction (Persian)
- Technical Specifications: Capacity
- Input
- Output
- Efficiency
- Battery
- Alarm
- Environment
- Management
- Physical
- Vigor RT and other online series
Publication details
- Authors
- Faran
- Publisher
- Faran
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Faran Faran online UPS catalogue, Titan Plus, PDF pp.1–2. Faran. https://kianups.ir/wp-content/uploads/2022/06/Online-UPS_2.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.