Faratel DSS technical sheet
Original title Faratel DSS technical sheet, distributor Noortoos copy, PDF p.2
Faratel
A two-page sheet from Iranian manufacturer Faratel describing six models of its DSS (Digital Smart Sine) line-interactive, pure sine-wave UPS series: 1500 VA / 1500 W, 2000 VA / 2000 W, 3000 VA / 2100 W and 3000 VA / 3000 W, with efficiency above 95% on mains and a switch time of 4-8 ms.
On this page
Overview
The sheet covers the DSS series that Faratel designs for computer systems, medical devices, telecommunication and other power-sensitive loads; the document is hosted on the site of distributor Noortoos and has English and Persian sections. The series is based on line-interactive technology and delivers a pure sine-wave output independent of the input, including during a mains failure. A smart microprocessor system checks the unit's operation and detects faults. Units can be installed in tower or rack position, with USB and RS232 communication.
The technical table gives six models: DSS1500P-RT, DSS1500PW and DSS1500X-RT (1500 VA / 1500 W), DSS2000X-RT (2000 VA / 2000 W), DSS3000X-RT-48V (3000 VA / 2100 W) and DSS3000X-RT (3000 VA / 3000 W). Output power factor is 0.7 on the 48 V 3000 VA model and 1 on the others. The input voltage range depends on load: 148-270 VAC up to 70% load and 170-270 VAC at 70-100% load. Maximum input current is 10, 13 and 20 A by rating; rated output current is 6.8, 9.09 and 13.63 A.
Output voltage is 220 VAC ±10% in normal mode and 220 VAC ±1% in battery mode; frequency follows the input in normal mode and is 50 Hz ±0.01 Hz on battery. Voltage distortion on non-linear load is below 5% or 6% depending on model. Overload capability is 105-125% of nominal power for 10 seconds. Batteries are maintenance-free sealed lead-acid with a bus voltage of 48 VDC or 96 VDC depending on model; maximum charge current is 4 A or 6 A and recharge to 90% takes 4-10 hours depending on battery capacity.
The series includes models with internal batteries and models for external batteries only; the X-suffix models are designed for external battery connection. Efficiency on mains is above 95%, switch time is 4-8 ms and noise is below 40 dB. Operating conditions are 0-40 °C, 0-80% non-condensing humidity and 1000 m above sea level per IEC 62040. Net weights lie roughly between 15 and 18.5 kg. Because of the line-interactive design the output stays within a ±10% band in normal mode, which is the main limit separating the series from double-conversion UPSs.
Key points
- Models: DSS1500P-RT, DSS1500PW, DSS1500X-RT (1500 VA / 1500 W); DSS2000X-RT (2000 VA / 2000 W); DSS3000X-RT-48V (3000 VA / 2100 W); DSS3000X-RT (3000 VA / 3000 W).
- Technology: line-interactive, pure sine-wave output, single phase; tower or rack mounting.
- Input: 148-270 VAC at 0-70% load, 170-270 VAC at 70-100% load; maximum input current 10, 13 and 20 A.
- Output: 220 VAC ±10% in normal mode, 220 VAC ±1% and 50 Hz ±0.01 Hz in battery mode; rated current 6.8 A, 9.09 A and 13.63 A.
- Output power factor 1; 0.7 on the DSS3000X-RT-48V.
- Overload: 105-125% of nominal power for 10 seconds.
- Battery: maintenance-free sealed lead-acid, 48 VDC or 96 VDC; maximum charge current 4 A or 6 A; 4-10 hours to 90% charge.
- Efficiency on mains > 95%; switch time 4-8 ms; noise < 40 dB.
- Environment: 0-40 °C, 0-80% humidity non-condensing, 1000 m altitude.
Using it in design
- Use the series for network access, security and auxiliary system loads; given the ±10% output band in normal mode and the 4-8 ms switch time, choose a double-conversion (VFI) UPS for critical server load.
- Separate the two models in the 3000 VA class: DSS3000X-RT carries 3000 W, DSS3000X-RT-48V only 2100 W; compare the load against the W value.
- Protect the supply circuit for the maximum input current (10, 13 or 20 A); it is higher than the output current because it includes charging.
- For long autonomy choose the X-suffix external-battery models and calculate recharge time against the 4 A or 6 A charge-current limit; with large battery sets the time approaches 10 hours.
- On weak-grid sites, compare the 170 VAC lower limit at full load with site voltage records; each excursion below it brings the battery in.
- For sites above 1000 m, request derating information from the manufacturer.
Who should read it
IT infrastructure engineers selecting a small UPS in the 1.5-3 kVA class, designers of network and security systems and teams assessing suppliers in the Iranian market.
Document contents
- DSS UPS: Digital Smart Sine UPS introduction
- Features (Persian)
- Model and Technology
- Input
- Output
- Battery
- Efficiency, Switch time and Auditory noise
- Environmental conditions
- Dimensions and Weight
Publication details
- Authors
- Faratel
- Publisher
- Faratel
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Faratel Faratel DSS technical sheet, distributor Noortoos copy, PDF p.2. Faratel. https://noortoos.ir/wp-content/uploads/DSS.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.