Kenika MS-10KVA NV official technical specifications

Kenika (PT Kent Power Dinamika Indonesia)

The MS-10KVA NV product page from Indonesian brand Kenika (PT Kent Power Dinamika Indonesia) describes a 10 kVA / 10 kW double-conversion on-line UPS with three-phase input and three-phase output: overall efficiency 95.5%, input power factor of 0.99 or better, THDi below 4% and parallel operation of up to 4 units.

On this page

Overview

The page presents the Kenika MS-10KVA NV with a description in Indonesian and a specification table in English. The unit is a DSP-controlled double-conversion on-line UPS; with unity output power factor, the 10 kVA rating equals 10 kW. The manufacturer recommends it for sensitive loads such as laboratory instruments, medical equipment and servers. Highlighted features include active power factor correction on all phases, a maintenance bypass, emergency power off (EPO), ECO mode, a 50/60 Hz frequency conversion mode and a 4.3-inch LCD touchscreen.

Nominal input and output voltage is given as 360/380/400/415 VAC (3 phases, neutral and protective earth). The input voltage range is 110-300 VAC at 50% load and 176-276 VAC at 100% load, and the frequency range is 40-70 Hz. Input current distortion is below 4% at full linear load. Output voltage regulation in battery mode is ±1%, voltage distortion is 2% or less on linear load and 5% or less on non-linear load, and the crest ratio is 3:1 maximum. Transfer time is stated as 0 ms both from AC mode to battery mode and from inverter to bypass.

The overload steps are 60 minutes at 100-110%, 10 minutes at 111-125% and 1 minute at 126-150%; above 150% the unit trips immediately. The standard battery set is 20 blocks of 12 V 9 Ah, giving 2-3 minutes at full load; the optional long-backup set of 40 blocks gives 10 minutes at 70% load. Charging current is adjustable from 1 to 12 A. Dimensions are 340 x 980 x 1150 mm, net weight is 47 kg and the standard batteries weigh 56 kg in total. Operating temperature is 0-40 °C, the altitude limit is 1500 m and noise is 65 dB at 1 metre.

Key points

  1. Capacity 10 kVA / 10 kW; 3-phase input, 3-phase output; output power factor 1.
  2. Nominal voltage 360/380/400/415 VAC (3P+N+PE); input range 110-300 VAC at 50% load, 176-276 VAC at 100% load; 40-70 Hz.
  3. Input power factor 0.99 or higher at 100% load; THDi below 4% at full linear load.
  4. Overall efficiency 95.5%; output THD 2% or less on linear load, 5% or less on non-linear load.
  5. Overload: 100-110% for 60 minutes, 111-125% for 10 minutes, 126-150% for 1 minute, above 150% immediately.
  6. Transfer time: 0 ms AC mode to battery mode, 0 ms inverter to bypass.
  7. Standard battery 20 x 12 V 9 Ah (2-3 minutes at full load); optional 40 x 12 V 9 Ah (10 minutes at 70% load); charging current adjustable 1-12 A.
  8. Dimensions (W x D x H) 340 x 980 x 1150 mm; net weight 47 kg, gross 58 kg; standard battery weight 56 kg.
  9. Parallel operation of up to 4 units; shared battery pack in parallel configuration and optional dual AC input.
  10. Communication RS-232, RS-485 and USB as standard; SNMP card optional; noise 65 dB at 1 metre.

Using it in design

  • For small three-phase system rooms up to 10 kW, select the model directly against the load in kW, and use parallel operation of up to 4 units for N+1 redundancy.
  • The standard battery gives only 2-3 minutes at full load; if generator start-up takes longer, plan the 40-block set or an external battery cabinet.
  • Use 95.5% efficiency for heat load: losses are about 0.47 kW at a 10 kW load.
  • Compare the 176-276 VAC full-load input window with the utility's voltage quality; at lower voltages the unit stays on mains only up to 50% load.
  • For sites above the 1500 m altitude limit, request the derating value from the manufacturer.
  • Carry the 980 mm depth and a total weight of over 100 kg with batteries into layout and floor loading.

Who should read it

Electrical designers selecting small three-phase UPSs and teams cataloguing products sold in South-East Asia.

Document contents

  1. Description
  2. Features
  3. Note
  4. Specifications: Input, Output, Battery, Display, Transfer Time, System, Environment, Management

Publication details

Authors
Kenika (PT Kent Power Dinamika Indonesia)
Publisher
Kenika (PT Kent Power Dinamika Indonesia)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Kenika (PT Kent Power Dinamika Indonesia) Kenika MS-10KVA NV official technical specifications. Kenika (PT Kent Power Dinamika Indonesia). https://kenika.com/index.php?product_id=1438&route=product%2Fproduct

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.