Koblenz 30015 OL USB/R datasheet

Original title Koblenz 30015 OL USB/R original datasheet, distributor PCH Mayoreo copy, pp.1–2

Koblenz

The 30015 OL USB/R datasheet from Mexican manufacturer Koblenz describes a 3000 VA / 2700 W, 120 V single-phase double-conversion on-line UPS for 19-inch rack mounting: zero transfer time from mains to battery, 2 minutes 38 seconds of runtime at full load and heat dissipation of 655 BTU/hour.

On this page

Overview

The three-page Spanish-language datasheet covers the Koblenz 30015 OL USB/R and is hosted in a distributor's technical-sheet archive. The unit is a double-conversion on-line UPS designed for critical voice, data, network, server, security and manufacturing applications. It is rated 3000 VA / 2700 W at a power factor of 0.9, with single-phase 120 V input and output with ground at 60 Hz. Highlighted features include an ECO function, hot-swap battery replacement, runtime scalable through additional battery banks, EPO and programmable output contacts.

Output voltage is 120 V ±1%, the waveform is a pure sine wave and the crest factor is 3:1. Harmonic distortion is 3% or less on linear load and 6% at most on non-linear load. Transfer time is zero from AC mode to battery mode and typically 4 ms from inverter to bypass. Output connections are two NEMA 5-20R receptacles and one NEMA 5-30R; the input plug is a NEMA L5-30P on a 1.8 m cord. The input voltage range is given as 50-150 Vac at 50% load and 85-150 Vac at 100% load.

The internal battery set consists of six sealed, maintenance-free 12 V 9 Ah VRLA blocks. Runtime is 11 minutes 8 seconds at half load and 2 minutes 38 seconds at full load; recharge to 90% takes 4 hours, and up to two external battery banks can be added. Management is through a USB and RS-232 port, an optional SNMP card and the ViewPower software. Surge suppression is 450 joules, with compliance to UL 1449 declared. The operating environment is 0-40 °C at 20-90% relative humidity, noise is below 50 dBA at one metre and heat dissipation is 655 BTU/hour.

Key points

  1. Capacity 3000 VA / 2700 W; power factor 0.9; single-phase 120 V, 60 Hz; double-conversion on-line.
  2. Transfer time: zero from mains to battery, typically 4 ms from inverter to bypass.
  3. Output 120 V ±1%; THD 3% or less on linear load, 6% maximum on non-linear load; crest factor 3:1.
  4. Input range: 50-150 Vac at 50% load, 85-150 Vac at 100% load; input plug NEMA L5-30P.
  5. Output receptacles: 2 x NEMA 5-20R and 1 x NEMA 5-30R.
  6. Battery: 6 x 12 V 9 Ah VRLA, hot-swappable; up to 2 external battery banks.
  7. Runtime: 11:08 minutes at half load, 2:38 minutes at full load; recharge to 90% in 4 hours.
  8. Heat dissipation 655 BTU/hour; noise below 50 dBA at one metre; operation 0-40 °C.
  9. Surge suppression 450 joules; UL 1449 compliance; USB/RS-232, optional SNMP, EPO port.

Using it in design

  • Consider it for in-rack network and server loads up to 2.7 kW on 120 V, 60 Hz systems; the model cannot be used in 230 V, 50 Hz facilities.
  • Compare the 2 minutes 38 seconds of full-load runtime with generator start-up time, and add up to two external battery banks if it falls short.
  • Add 655 BTU/hour (about 192 W) to the cabinet heat-load calculation.
  • Design the supply circuit with a 30 A receptacle and protection to suit the NEMA L5-30P plug, and plan load distribution across the 5-20R and 5-30R outputs.
  • For maintenance continuity, write hot-swap battery replacement into the operating procedure and wire the EPO port into the emergency shutdown circuit.

Who should read it

Designers selecting rack-mount UPSs for small system rooms on North American and Mexican voltage standards, and teams cataloguing products.

Document contents

  1. Características del producto
  2. General
  3. Salida
  4. Entrada
  5. Batería
  6. Administración
  7. Alarmas audibles
  8. Protección
  9. Ambiental

Publication details

Authors
Koblenz
Publisher
Koblenz
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Koblenz Koblenz 30015 OL USB/R original datasheet, distributor PCH Mayoreo copy, pp.1–2. Koblenz. https://fichastecnicas.pchmayoreo.com/99053042310-K.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.