Neelkanth / Neel Power UPS technical specifications, output rating table
Neelkanth Power Solutions
Online UPS page from Mumbai-based Neelkanth Power Solutions: single- and three-phase range from 1 to 500 kVA, inverter efficiency above 95 percent, overall efficiency above 92 percent, output power factor 0.8.
On this page
Overview
The page presents Neelkanth's true online double-conversion, microcontroller-based UPS range, which it says is built with foreign collaboration. Single-phase models are 1, 2, 3, 7.5, 15 and 20 kVA; three-phase models are 10, 20, 30, 40, 50, 60, 75, 100, 120, 150, 200, 250, 300, 400 and 500 kVA. Targets include servers, workstations and CAD/CAM systems sensitive to mains irregularities, as well as CNC machines and industrial applications.
Listed features include PWM and IGBT technology, a built-in static bypass switch, a programmable battery-low alarm and an RS-232 interface for machine interlock. Rectifier protections cover input over and under voltage, DC over voltage, charging over-current, single-phase failure and reverse phase sequence; inverter protections cover output over voltage, overload, short circuit, DC under voltage and over temperature. An LCD or LED display shows input and output voltage, current, frequency and battery data.
In the technical table the input is 230 V AC (+15 percent, -20 percent) for single phase and 415 V three-phase four-wire for three phase, with a frequency range of 47 to 53 Hz. At the output, voltage regulation is 1 percent for unbalanced load, frequency is 50 Hz ± 0.1 percent, and THD is below 3 percent on linear load and below 5 percent on nonlinear load. Overload withstands 110 percent for 30 minutes, 125 percent for 10 minutes and 150 percent for 60 seconds. Transient response is 5 percent on a load step, recovering to 1 percent within 5 ms.
Physically the enclosure is IP 31 (IP 42 optional), with bottom cable entry and forced-air cooling. The operating environment is 0 to 45 °C and up to 95 percent relative humidity. Noise is below 60 dB up to 100 kVA and below 75 dB up to 500 kVA. Reference standards are IEC 146-IV, EN 50091-1 and EN 50091-2. The page is a manufacturer product page and its own copyright line reads 2010.
Key points
- Single-phase capacities: 1, 2, 3, 7.5, 15, 20 kVA; three-phase: 15 steps from 10 to 500 kVA.
- Inverter efficiency above 95 percent; overall efficiency above 92 percent.
- Input: single phase 230 V AC (+15 / -20 percent), three phase 415 V three-phase four-wire; frequency 47-53 Hz.
- Output power factor 0.8; crest factor 3:1; regulation 1 percent for unbalanced load; frequency 50 Hz ± 0.1 percent.
- THD below 3 percent on linear load and below 5 percent on nonlinear load.
- Overload: 110 percent for 30 min, 125 percent for 10 min, 150 percent for 60 s.
- Load-step transient 5 percent; recovery to 1 percent within 5 ms.
- Enclosure IP 31 (IP 42 optional), 0-45 °C, up to 95 percent RH; noise below 60 dB up to 100 kVA and below 75 dB up to 500 kVA.
- The altitude limit is written as 300 m above mean sea level.
Using it in design
- Because output power factor is 0.8, take kW capacity as 80 percent of the kVA value and check this limit against modern high-power-factor server loads.
- Use the overload curve (110, 125, 150 percent) as input to protection and bypass selectivity studies.
- For sites above 300 m, ask the manufacturer for derating values; the document gives only this altitude limit.
- Reserve front and rear clearances for bottom cable entry and forced-air cooling in the layout.
- State in the specification how the referenced EN 50091 standards relate to the current IEC 62040 series.
Who should read it
Electrical designers procuring UPS units in the Indian subcontinent and teams building product catalogues.
Document contents
- UPS system features
- Efficiency
- Protection
- Metering
- Controls
- Physical
- Environment
- Reference standards
- Optional features
- Technical specifications: input and output
Publication details
- Authors
- Neelkanth Power Solutions
- Publisher
- Neelkanth Power Solutions
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Neelkanth Power Solutions Neelkanth / Neel Power UPS technical specifications, output rating table. Neelkanth Power Solutions. https://www.neelpower.com/u_p_s.php
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.