Soltec ALP Series Three-Phase UPS Specifications, 10-60 kVA
Original title Soltec ALP technical specifications, 3-phase output 10–60kVA table
Soltec
Soltec's product page for the transformer-based on-line ALP series lists the 10-60 kVA three-phase in/three-phase out models with 0.8 output power factor, 90-92% overall efficiency and 0 ms static switch transfer.
On this page
Overview
The page presents the Taiwanese manufacturer Soltec's ALP family of three-phase UPSs from 10 to 800 kVA. The table used here covers the 10, 20, 30, 40, 50 and 60 kVA models (ALP-10K to ALP-60K). The design is marked by true galvanic isolation at input and output, modular plug and play construction, cold start, multi-CPU control and a wide input range.
The rectifier input is 380/220, 400/230 or 415/240 V (3-phase, 4-wire) with a +/-20% voltage window and 50/60 Hz +/-7% frequency window. Rectifier efficiency is 99%, and power walk-in takes 15 seconds from 15% to 100%. The inverter has a sine output, a 0.8 output power factor, THD under 3% on linear load and a 120 deg +/-0.5 deg phase shift at 100% unbalanced load.
Overload capability is continuous below 110%, 110-124% for 15 minutes, 125-149% for 5 minutes and 150% and above for 30 seconds. Inverter efficiency at 100% load is 92%, 93.5% and 94% across the kVA steps, and overall efficiency is 90%, 91% and 92%. The static switch transfers from mains to inverter in 0 ms. The cabinet is 550 x 1600 x 800 mm (W x H x D), weight without battery is 300 to 630 kg, and the battery is 29 maintenance-free 12 V lead-acid blocks.
The page makes no commitment about production or site suitability; values may change without notice and special specifications can be built on request.
Key points
- Six models: ALP-10K, 20K, 30K, 40K, 50K and 60K, all 3-phase in/3-phase out.
- Input voltage 380/220, 400/230, 415/240 V; input window +/-20%, frequency 50/60 Hz +/-7%.
- Output power factor 0.8; THD under 3% on linear load; free-running output frequency +/-0.1 Hz.
- Overload: 110-124% for 15 min, 125-149% for 5 min, 150% and above for 30 s.
- Inverter efficiency 92% / 93.5% / 94% and overall efficiency 90% / 91% / 92% (380/400/415 V, 3P4W, 100% load).
- Static switch range is 173-277 Vac (L-N), mains-to-inverter transfer 0 ms.
- Weight without battery is 300, 400, 470, 520, 560 and 630 kg; dimensions 550 x 1600 x 800 mm.
- Noise is 63 to 65 dBA at 1 m; operating temperature 0-40 C, altitude below 1500 m.
Using it in design
- The transformer-based (galvanically isolated) design gives separate earthing between input and output and helps fault-current design; transformer losses are already in the overall efficiency.
- The 15 s walk-in time should be considered in generator sizing and in the inrush assessment at the input.
- With a 0.8 output power factor the 60 kVA model delivers 48 kW; for modern unity-PF server loads size on kW, not kVA.
- Check floor loading and cabinet layout for 300-630 kg without battery plus a 29-block battery.
- Use the overload time bands in protection and selectivity studies.
Who should read it
Electrical designers selecting mid-size UPSs and specification engineers evaluating a transformer-based on-line architecture.
Document contents
- Features
- Input (rectifier)
- Battery
- Inverter
- Static switch
- Overall characteristics
- Communication interface
Publication details
- Authors
- Soltec
- Publisher
- Soltec
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Soltec Soltec ALP technical specifications, 3-phase output 10–60kVA table. Soltec. http://soltec.com.tw/f/en_product_online_alp.asp
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.