Technical guideFree to readYear not stated

TRV MACAN Tower/Rack UPS Technical Catalogue

Original title TRV MACAN tower/rack technical catalogue, PDF pp.2 and 4

TRV Electronics

TRV Electronics' MACAN single-phase on-line double-conversion UPS covers 1-10 kVA in 12 models (6 tower, 6 rack) with output power factor 1.0, 0 ms transfer and over 94% efficiency in ECO mode.

On this page

Overview

The catalogue gives the tower (MAC-1000, 1500, 2000, 3000, 6000, 10K) and 19-inch rack (MAC-1000-RM to MAC-10K-RM) versions of TRV Electronics' MACAN UPS family in two tables. All models are single phase, on-line double conversion with pure sine output, and capacities in VA and W are identical: 1000/1000, 1500/1500, 2000/2000, 3000/3000, 6000/6000 and 10000/10000. The output power factor is therefore 1.0. Transfer time is 0 ms and ECO-mode efficiency is above 94%.

Nominal input voltage is 208/220/230/240 Vac, frequency 50/60 Hz (auto-sensing), and input power factor is above 0.97. The voltage window depends on load: 120-140 VAC with load under 25%, 140-160 VAC under 50%, 160-180 VAC under 75% and 180-276 VAC at full load. Output voltage is one of the same four values +/-2% and frequency +/-0.25 Hz; THD is under 2.5% on linear load (3% on some rack models) and crest factor is 3:1. In line mode overload is tolerated at 105-120% for 30 s and 121-150% for 10 s, and in battery mode at 101-109% for 10 s and 110-120% for 3 s. The internal bypass is automatic and manual, output is cut immediately on short circuit, and surge protection is IEC 61000-4-5 level 3.

Batteries are AGM VRLA 12 V blocks of 5, 7 and 9 Ah: 2, 4, 6, 6, 20 and 20 on the tower models and 3, 3, 6, 6, 20 and 20 on the rack models. Recharge to 90% takes 4 hours, and an external battery module is optional (the larger rack models have no internal battery and run only on external batteries). Tower weights run from 10.4 to 95 kg and rack weights from 14.7 to 29 kg. Operation is 0-40 C, altitude under 2000 m, noise under 40 dB or under 55 dB; communication is RS-232 and USB Type B, with optional SNMP.

Key points

  1. 12 models: MAC-1000, 1500, 2000, 3000, 6000, 10K (tower) and -RM rack versions of the same capacities.
  2. VA and W ratings are equal (1000 to 10000); output power factor 1.0; ECO-mode efficiency over 94%.
  3. Input 208/220/230/240 Vac; 50/60 Hz auto; input PF >0.97; 180-276 VAC at full load.
  4. Output +/-2%, 50/60 Hz +/-0.25 Hz; THD <2.5% (linear load), crest factor 3:1; transfer 0 ms.
  5. Overload in line mode 105-120% for 30 s, 121-150% for 10 s; in battery mode 101-109% for 10 s, 110-120% for 3 s.
  6. Battery AGM VRLA 12 V, 5/7/9 Ah, 2 to 20 blocks; recharge to 90% in 4 hours; external battery module optional.
  7. Tower weight 10.4-95 kg, rack weight 14.7-29 kg; rack is 428 mm wide and 84 mm high.
  8. Operation 0-40 C, altitude <2000 m, RS-232 and USB Type B; SNMP optional.

Using it in design

  • With output PF 1.0 the VA rating equals the W rating, so the kVA/kW difference does not need to be managed for modern server load.
  • Evaluate the low-input windows (120 VAC only with load under 25%) together with load factor under weak-mains conditions.
  • In the rack version, separate models with and without internal battery; plan external battery modules and rack space for the large models.
  • Verify overload times (especially 3-10 s in battery mode) for loads with high inrush.
  • Rack height is 84 mm (2U), so allow for the 425 or 635 mm rack depth.

Who should read it

Designers and suppliers selecting single-phase on-line UPSs for small and medium server rooms.

Document contents

  1. Tower version technical table
  2. Rack version technical table

Publication details

Authors
TRV Electronics
Publisher
TRV Electronics
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TRV Electronics TRV MACAN tower/rack technical catalogue, PDF pp.2 and 4. TRV Electronics. https://trv.com.ar/wp-content/uploads/2025/05/MACAN-DESCRIPCION-_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.