Weli Science GT Series 1-3K Online UPS Technical Sheet

Original title Weli Science GT series 1–3K online UPS technical sheet, PDF p.1

Weli Science

The Weli Science GT series is a 1000-3000 VA double-conversion on-line UPS; the GT-1K, GT-2K and GT-3K have 0.8 output power factor, 0.99 input power factor and 4 ms inverter-to-bypass transfer.

On this page

Overview

The document presents the Weli Science (Taiwan) GT series on one page. Models are GT-1K (1000 VA/800 W), GT-2K (2000 VA/1600 W) and GT-3K (3000 VA/2400 W). The unit is double-conversion on-line with a wide input voltage range, 0.99 input power factor, 0.8 output power factor, automatic 50/60 Hz frequency sensing, programmable output sockets, an ECO saving mode, cold start and generator compatibility. The pure sine output is described as suitable for any load except laser printers.

Input is single phase two-wire and accepts 80-160 VAC for 110 V and 175-300 VAC for 220 V; frequency range is 40-70 Hz. In battery mode output voltage regulation is +/-3%, frequency 50 Hz +/-0.25 Hz or 60 Hz +/-0.3 Hz, and crest factor 3:1. On overload it holds 100-110% for 10 minutes, 110-150% for 30 seconds and above 130% for 200 ms before moving to bypass, and returns to the UPS when the overload clears. There is no break at mains loss or return, and inverter-to-bypass transfer is typically 4 ms. Overall AC-to-AC efficiency is 85-90%.

The battery is 12 V/7 Ah x3 (GT-1K), 12 V/7 Ah x6 (GT-2K) and 12 V/9 Ah x6 (GT-3K), with two-stage charging reaching 90% in 4 hours. Product size is 397 x 145 x 220 mm and 421 x 190 x 318 mm (D x W x H), and net weight with battery is 13, 26 and 28 kg. Noise is under 45 dBA at 1 m and operation is 0-40 C. USB or RS-232 communication is standard and an SNMP card is optional. The product is BSMI and CE approved.

Key points

  1. Three models: GT-1K 1000 VA/800 W, GT-2K 2000 VA/1600 W, GT-3K 3000 VA/2400 W.
  2. Input PF >=0.99; output PF 0.8; input window 80-160 VAC for 110 V and 175-300 VAC for 220 V; 40-70 Hz.
  3. Battery-mode voltage regulation +/-3%, frequency 50 Hz +/-0.25 Hz or 60 Hz +/-0.3 Hz; crest factor 3:1.
  4. Overload: 100-110% for 10 min, 110-150% for 30 s, above 130% bypass after 200 ms.
  5. Transfer: no break on mains loss; inverter to bypass typically 4 ms.
  6. AC-to-AC overall efficiency 85-90%; ECO mode available.
  7. Battery 12 V/7 Ah x3, 12 V/7 Ah x6, 12 V/9 Ah x6; 90% charge in 4 hours; two-stage charging.
  8. Net weight with battery 13, 26 and 28 kg; noise <45 dBA; BSMI and CE.

Using it in design

  • With a 0.8 output power factor the 1 kVA model gives only 800 W; select load by watts.
  • The 110 V and 220 V input windows are given separately; verify site voltage stays in the relevant window.
  • Use the overload-to-bypass timing (200 ms above 130%) for high-inrush loads and protection studies.
  • On generator-fed sites, consider the benefit of the wide input window and 0.99 input PF.
  • Flag the manufacturer's laser printer exception in the load list.

Who should read it

Designers and suppliers selecting double-conversion UPSs for small and medium loads.

Document contents

  1. Features
  2. Input
  3. Output
  4. Overload and transfer time
  5. Efficiency
  6. Battery
  7. Display panel
  8. Size and weight
  9. Operating environment
  10. Communication

Publication details

Authors
Weli Science
Publisher
Weli Science
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Weli Science Weli Science GT series 1–3K online UPS technical sheet, PDF p.1. Weli Science. https://taiwan.weliscience.com.tw/rwd1406/store/f4/GT%20series%201-3K.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.