Rise Power Systems RPP Technical Datasheet Rev 2

Rise Power Systems

A two-page manufacturer datasheet that collects the electrical ratings, protection, metering and mechanical data of a 400 A and 600 A remote power panel (RPP) in one place.

On this page

Overview

The Rev 2 datasheet (23 October 2026) describes an RPP platform with three-phase panelboard distribution: 400 A and 600 A configurations, up to 84 poles, a maximum of 480 VAC line to line, 60 Hz, and 3-phase 4-wire plus ground on both input and output. The neutral bus is 150% on the 400 A model and 100% on the 600 A model as standard; an optional 200% neutral must be specified at order.

On the input side a main breaker is standard and main-lug-only (MLO) is optional. Breaker platforms are Schneider Electric and ABB, and device selection must match the approved panelboard configuration. Assembly short-circuit current rating (SCCR) is a value to be confirmed for each system voltage and approved breaker combination; the sheet does not give a single number.

The optional surge protective device (SPD) is rated 200 kA SCCR, 130 kA maximum surge current per phase and 20 kA nominal discharge current (In). The 200 kA figure is the SPD component rating, not the cabinet SCCR. The Cortex PQM metering platform claims Class 0.2 accuracy, but installed accuracy depends on the selected current transformers; communications are Modbus TCP/IP only.

Mechanically the cabinet is 24 x 12 x 84 in (609.6 x 304.8 x 2133.6 mm), NEMA 1 indoor, with a hinged deadfront, top and/or bottom cable entry and natural-convection cooling. UL 62368-1 / cETLus is named as a listing target. Weight, anchorage and installation clearances require the approved configuration drawing, and seismic evaluation is a project-specific engineering task.

Key points

  1. Platform: 400 A and 600 A, up to 84 poles, up to 480 VAC line to line, 60 Hz, 3-phase 4-wire plus ground.
  2. Neutral bus: 150% standard on the 400 A model, 100% on the 600 A model; optional 200% specified at order.
  3. Standard breaker platforms are Schneider Electric and ABB; main breaker standard, MLO optional.
  4. Assembly SCCR is confirmed per voltage and breaker combination.
  5. SPD: 200 kA SCCR (component rating), 130 kA maximum surge current per phase, 20 kA In.
  6. Cortex PQM claims Class 0.2 (ANSI C12.20 / IEC 62053); installed accuracy depends on CTs. Modbus TCP/IP only; optional 10.1 in, 1280 x 800 display.
  7. Operating temperature 0 to 40 °C, storage -40 to 60 °C; cabinet 609.6 x 304.8 x 2133.6 mm.
  8. Optional shunt trip, auxiliary contacts and infrared (IR) inspection window.

Using it in design

  • Do not read the SPD's 200 kA as the cabinet SCCR; compare the design fault current with the assembly SCCR of the approved configuration.
  • For loads with high neutral current (harmonics), check whether the 100% neutral of the 600 A model is enough and specify the 200% neutral at order if not.
  • Use the 24 x 12 x 84 in envelope for preliminary sizing only; wait for the approved drawing for cable entry, anchorage, weight and service clearance.
  • Where metering accuracy matters (billing, PUE), specify the CT class as well, and carry the Modbus TCP/IP-only interface into BMS integration.
  • For seismic-zone projects, add the project-specific seismic evaluation to the specification.

Who should read it

Electrical engineers designing row-end and in-hall distribution, and teams writing RPP specifications.

Document contents

  1. 01 Electrical Ratings
  2. 02 Input Protection and Branch Distribution
  3. 03 Optional Surge Protection
  4. 04 Mechanical and Environmental Specifications
  5. 05 Cortex Metering and Monitoring
  6. 06 Accessories and Engineered Options
  7. 07 Dimensional Envelope Reference

Publication details

Authors
Rise Power Systems
Publisher
Rise Power Systems
Year
2026
Document number
Rev 2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document. Metadata and original short summary only; no full text reproduced in library.

Citation

Rise Power Systems (2026). Rise Power Systems RPP Technical Datasheet Rev 2. Rise Power Systems. Rev 2. https://risepowersystems.com/wp-content/uploads/Rise_RPP_Technical_Datasheet_Rev2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.