Operating Instructions for Cast Resin Transformers (Bedienungsanleitung Giessharztransformatoren)
Original title Bedienungsanleitung Gießharztransformatoren
RPT Ruhstrat Power Technology GmbH
A German-language manufacturer guide (05-2019) from RPT Ruhstrat Power Technology covering transport, installation, connections, ventilation, commissioning and planned maintenance of cast resin transformers.
On this page
Overview
After safety instructions, reference standards and the rating plate, the guide covers transport, receipt and storage (lifting, moving, storing). The installation chapter covers installations with and without enclosure, low- and high-voltage connections, tightening torques, siting, ventilation, overvoltage protection and temperature monitoring. An IP00 transformer gives no safe protection against contact, so it must be installed in a protective enclosure, a fence or a room accessible only through lockable doors.
For ventilation, losses at rated operation must be removed from the room without exceeding the ambient temperature stated on the data sheet. The room has a fresh-air inlet S low down and a warm-air outlet S' high on the opposite wall. For a 20 C annual mean, S = 0.185 x (TL / square root of H) m2 (TL is the sum of no-load and short-circuit losses in W, H the height between the openings in m) and S' = S x 1.15. If the room is undersized, forced ventilation of 3.5-4 m3 per minute per kW of losses is recommended. Cross-flow fans last about 20,000 hours and are advised to switch on above 90 C and off below 80 C.
Commissioning checks earthing (PE conductor at least 16 mm2 copper, 35 mm2 aluminium, 50 mm2 steel), HV and LV connections, cleaning, tap change and winding insulation measurement separately. Insulation is measured with open terminals: 5000 V for 60 s HV/LV to earth about 20 megohm or more, and 2500 V for 60 s 10 megohm or more. Energizing the transformer at no load is recommended.
The maintenance table includes checking temperature sensors and evaluation devices every six months and after unusual events, winding cleaning (yearly, dry compressed air at most 3 bar), moisture removal after long standstill, connection torque (yearly), winding centring and insulation measurement. Maintenance records are kept. An appendix has a fault guide and an exploded drawing. The document is manufacturer-specific and not a universal installation standard.
Key points
- Tightening torques (electrical, steel): M6 10-15, M8 30-40, M10 50-60, M12 60-70, M14 90-100, M16 120-130 N-m; brass M6 5-10 ... M16 80-90 N-m.
- Wall clearances: up to 12 kV A at least 125 mm, B at least 60 mm; up to 24 kV A 225 mm, B 120 mm; up to 36 kV A 320 mm, B 200 mm.
- Ventilation openings: S = 0.185 x (TL / square root of H) m2, S' = 1.15 x S (for 20 C annual mean).
- Forced ventilation of 3.5-4 m3/min per kW of losses; fans on at 90 C, off below 80 C; fan life about 20,000 hours.
- Temperature monitoring settings (warning / trip): insulation class H (180 C) 140 / 155 C, F (155 C) 130 / 140 C, B (130 C) 110 / 120 C.
- PE conductor at least 16 mm2 copper, 35 mm2 aluminium, 50 mm2 steel.
- Insulation resistance: 5000 V for 60 s HV/LV to earth at least about 20 megohm; 2500 V for 60 s 10 megohm.
- Cleaning: inspection within 6 months on new installations; yearly cleaning with dry compressed air at most 3 bar.
- Sensor and evaluation device check every six months; connection torque yearly.
Using it in design
- Size the transformer room's low inlet and high opposite outlet with the S and S' formulas; if inadequate, provide forced ventilation (3.5-4 m3/min per kW).
- Verify wall clearances A and B by voltage class on the layout.
- Set PTC or Pt100 sensor warning and trip thresholds in the relay by insulation class.
- Add winding insulation measurement, earthing cross-section, torque check and no-load energization to the commissioning procedure.
- Include cleaning, sensor test and torque check intervals and record keeping in the maintenance programme.
Who should read it
Electrical engineers and maintenance teams installing, commissioning and operating cast resin transformers.
Document contents
- Safety instructions
- Reference standards
- Rating plate
- Transport, receipt and storage
- Installation
- Commissioning
- Maintenance
- Additional information
- Notes
Publication details
- Authors
- RPT Ruhstrat Power Technology GmbH
- Publisher
- RPT Ruhstrat Power Technology GmbH
- Year
- 2019
- Document number
- 05-2019 | 01
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
RPT Ruhstrat Power Technology GmbH (2019). Bedienungsanleitung Gießharztransformatoren. RPT Ruhstrat Power Technology GmbH. 05-2019 | 01. https://ruhstrat.com/wp-content/uploads/2019/10/Bedienungsanleitung_GHT_DE_Web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.