Technical guideFree to read2024

Schleifenbauer Example Catalogue PDUs 2024

Schleifenbauer

A 140-page manufacturer catalogue of Schleifenbauer example rack PDUs, covering basic, metered, monitored, switched and managed classes, customisation options, fuse and surge protection topics and the approach to PUE measurement.

On this page

Overview

The catalogue describes Schleifenbauer's approach of adapting the PDU to the customer's IT infrastructure: from stock components any configuration can be made within a maximum of 4 weeks, from a single piece and without extra cost. The manufacturer says it has produced more than 120,000 different custom PDU types. For that reason the catalogue products are 'example PDUs': an example of each type is shown, and the customer picks the nearest part number and states the changes (adding or removing a socket, colour, extra protection, phase distribution).

The content is divided into five product classes: basic (non-intelligent), metered, monitored, switched and managed PDUs, plus inline meter PDUs. The basic PDU examples are listed as 13 part numbers in 16 A and 32 A, single and three phase, vertical (0U), horizontal (1.5U) and double-depth horizontal types; for example 223DVNN1101 is a 230 VAC 16 A single-phase 3.6 kVA 0U PDU with 8 x C13 and 1 x C19 outlets measuring 340 x 65 x 52.5 mm. Quoted enclosure dimensions exclude cable strain relief, mounting and cable bend space. Example part numbers describe published configurations; customisation flexibility does not make every possible combination a separate catalogue model.

The technical specification section gives common values: input 230/400 VAC single or three phase 16/32 A; halogen-free (LSZH) mains lead; remote measurement of total energy (kWh), true RMS current, voltage, power and power factor, accuracy below 1% (IEC 50470:3 Class C); ambient temperature 0-60 degrees C; electronics consumption below 3 W; profile size 65 x 52.5 mm. Fuse options are MCB, thermal fuse, glass cartridge and hydraulic-magnetic; surge protection is a hot-swappable module from Dehn. Communication is Ethernet, SNMP, Modbus and API, and with hybrid, Ethernet and bridge modes more than 50 PDUs can be managed on a single IP address.

The PUE section defines PUE as total facility power divided by IT equipment power and notes that most data centres in practice have a PUE of around 1.5 to 2.5. The catalogue recommends metering colocation customer racks with PDUs to separate them from facility consumption. The databus is redundant, so a single cable cut does not affect readout or control. The manufacturer states availability of at least 99.982% and an RMA rate below 0.5% since 2008. Technical chapters also cover fuse selection, surge protection, near-zero-voltage switching, a rack calculator and a custom PDU bracket.

Key points

  1. Any configuration is made within 4 weeks, from one piece, at no extra cost; the manufacturer states it has produced more than 120,000 different custom PDU types.
  2. Catalogue part numbers are example configurations; customisation flexibility does not make every possible combination a separate catalogue model.
  3. Five product classes: basic, metered, monitored, switched, managed; plus inline meter PDUs.
  4. Basic PDU examples consist of 13 part numbers: 16 A and 32 A, single and three phase, vertical 0U, horizontal 1.5U and double-depth horizontal.
  5. Example 223DVNN1101: 230 VAC 16 A single phase, 3.6 kVA, 8 x C13 + 1 x C19, 340 x 65 x 52.5 mm; dimensions exclude cable strain relief, mounting and cable bend space.
  6. Input 230/400 VAC single or three phase 16/32 A; LSZH mains lead; remote measurement accuracy below 1% (IEC 50470:3 Class C); electronics consumption below 3 W; ambient temperature 0-60 degrees C.
  7. Fuse types MCB, thermal fuse, glass cartridge and hydraulic-magnetic; surge protection by Dehn, hot-swappable module.
  8. In bridge mode more than 50 PDUs are managed on one IP address; the databus has ring redundancy.
  9. PUE = total facility power / IT equipment power; most data centres in practice sit at 1.5-2.5; the manufacturer states availability of at least 99.982%.

Using it in design

  • When selecting a rack PDU, separate the basic, metered, monitored, switched and managed classes by need; for colocation and PUE metering choose metered or a higher class.
  • Take the example part number as a starting point and tell the supplier which outlets, phase distribution and protection features to change; do not multiply custom configurations as separate models in the catalogue.
  • In rack layout, account for the fact that quoted dimensions exclude cable strain relief, mounting and cable bend space (leave extra clearance for 0U and 1.5U layouts).
  • Specify the fuse type (MCB, thermal, glass cartridge, hydraulic-magnetic) and the Dehn surge module according to load and line protection needs.
  • For PUE and customer rack metering, write PDU accuracy (below 1%, IEC 50470:3 Class C) and communication mode (hybrid, Ethernet, bridge) into the monitoring architecture.

Who should read it

Electrical engineers and IT infrastructure managers selecting PDUs for rack and colocation data centres.

Document contents

  1. Introduction
  2. Power usage effectiveness (PUE)
  3. Example basic PDUs (non-intelligent)
  4. Example metered PDUs
  5. Example monitored PDUs
  6. Example switched PDUs
  7. Example managed PDUs
  8. Inline meter PDUs
  9. Overview of example PDUs
  10. Customisation
  11. Configuration layout: phases, ampere, fuse and branches
  12. Lock cables
  13. What the item number means
  14. Customer cases
  15. Which type of fuse should be used in a rack PDU
  16. Surge protection in your data centre
  17. Near zero voltage switching
  18. Rack calculator
  19. Custom PDU bracket
  20. Hybrid and Ethernet mode
  21. Bridged and colocation mode
  22. Technical specifications and glossary of terms

Publication details

Authors
Schleifenbauer
Publisher
Schleifenbauer
Year
2024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Schleifenbauer (2024). Schleifenbauer Example Catalogue PDUs 2024. Schleifenbauer. https://www.schleifenbauer.eu/wp-content/uploads/2024/04/Example-Catalogue-Schleifenbauer-PDUs-2024-LR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.