Technical guideFree to readYear not stated

Electrical Installation Guide: conductor voltage drop and short-circuit current

Schneider Electric

Chapter G of Schneider Electric's online installation guide explains how to compute steady AC cable voltage drop and prospective three-phase fault current from resistance and reactance. It supports preliminary sizing calculations and does not replace a coordinated protection study.

On this page

Overview

The voltage-drop formula for a balanced three-phase circuit is sqrt(3) x current x cable length x (R cos(phi) + X sin(phi)); a two-conductor circuit uses a multiplier of 2 instead of sqrt(3). Because both resistance and reactance appear, power factor cos(phi) and cable cross-section together decide the result: at low power factor the reactive term can outweigh the resistive term, especially with large cables.

The three-phase fault-current estimate divides the phase-to-phase voltage by sqrt(3) times the upstream per-phase impedance. Series resistances and reactances from the source to the fault point are first summed separately and only then is the magnitude of the combined impedance found; adding the impedances arithmetically would give a wrong result. The method allows a quick estimate of the expected fault level at switchboards and sub-boards.

The page supports preliminary electrical calculations with stated circuit assumptions, but it does not replace a coordinated protection study covering device ratings, selectivity and thermal withstand. The topic relates to IEC 60364; circuit type, phase balance, power factor, conductor temperature and the upstream fault assumption must be recorded explicitly, and device ratings and conductor impedance taken from the relevant manufacturer data.

Key points

  1. Steady-state voltage drop in a balanced three-phase circuit: sqrt(3) x I x L x (R cos(phi) + X sin(phi)).
  2. A two-conductor circuit uses the same formula with a multiplier of 2 instead of sqrt(3).
  3. Three-phase fault current = phase-to-phase voltage / (sqrt(3) x upstream per-phase impedance).
  4. Series resistances and reactances are summed separately before the impedance magnitude is found.
  5. The method is for preliminary sizing; it does not replace a coordinated protection study.
  6. Related standard: IEC 60364.

Using it in design

  • Make circuit type (3-phase or two-conductor), cos(phi) and conductor temperature explicit inputs to the cable voltage-drop calculation.
  • In the short-circuit calculation sum R and X separately and take the magnitude afterwards; do not add impedances arithmetically.
  • Show the upstream fault assumption in the result report.
  • Take device ratings and conductor impedance from manufacturer data and label results as 'preliminary'.

Who should read it

Design engineers doing preliminary electrical sizing who need quick estimates of voltage drop and fault level.

Related standards

  • IEC 60364

Publication details

Authors
Schneider Electric
Publisher
Schneider Electric
Year
Year not stated
Document number
Electrical Installation Guide, Chapter G
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Schneider Electric Electrical Installation Guide: conductor voltage drop and short-circuit current. Schneider Electric. Electrical Installation Guide, Chapter G. https://www.electrical-installation.org/enwiki/Sizing_and_protection_of_conductors

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.