White paperFree to read2012

Data Center Projects: Advantages of Using a Reference Design

Schneider Electric · Patrick Donovan

Schneider Electric WP 147 explains what a data centre reference design is, what it should contain and why starting from one beats a blank-sheet custom design.

On this page

Overview

A reference design consists of a system blueprint, a list of attributes including system-level performance specifications, and ideally a detailed bill of materials. It may cover a whole data centre or a subsection such as an IT pod, IT room, power plant or cooling plant. Graphical documents include electrical, mechanical and IT one-line diagrams, floor layouts showing dimensions and clearances of racks, PDUs, CRAC/CRAHs, UPSs, generators, switchboards and ATSs, and 3D spatial views.

The attribute summary lists estimated cost, IT load capacity, estimated annualized PUE, density capability, power and cooling redundancy, and heat rejection method, so alternatives can be compared like for like. The bill of materials identifies product name, description, part number and quantity for each component, and whether the reference-design vendor supplies it. Effective reference designs are modular and scalable, efficiency-maximizing, balanced across power, cooling and rack capacities, and detailed.

At minimum a reference design is selected from three inputs: total expected IT load, level of redundancy for power and cooling, and density. Local engineering is still needed for permitting and code compliance, localization, cable and pipe schedules, floor and roof loading constraints and water drainage. Fire suppression, physical security and the building structure may not be covered.

The benefits claimed are faster planning, quicker buildable designs and more predictable, reliable operation, and the paper notes that heavy customization erodes them. It offers no numeric benchmark; its value is as a checklist of what a reference design must contain and what it leaves open.

Key points

  1. A reference design is a system blueprint, an attribute list with system-level performance specifications and ideally a detailed BOM; it may cover a whole site or a subsection such as an IT pod, room, power plant or cooling plant.
  2. Graphics: electrical, mechanical and IT one-lines; layouts with dimensions and clearances of racks, PDUs, CRAC/CRAHs, UPSs, generators, switchboards, ATSs; 3D views.
  3. Attribute summary: estimated cost, IT load capacity, estimated annualized PUE, density capability, power and cooling redundancy, heat rejection method.
  4. BOM: product name, description, part number, quantity and whether the reference-design vendor supplies it.
  5. Selection needs at minimum three inputs: total IT load, redundancy level for power and cooling, density.
  6. Engineering is still needed for permits and codes, localization, cable and pipe schedules, floor/roof loading and drainage.
  7. Fire suppression, physical security and building structure may not be covered.
  8. Effective reference designs are modular and scalable, efficiency-maximizing, balanced and detailed.

Using it in design

  • Document each reference design’s IT kW range, power and cooling redundancy (N/N+1/2N), kW/rack, annual PUE, heat-rejection type and estimated cost, together with one-lines, layouts and equipment schedules listing part number, quantity and supplier.
  • Filter templates by the three selection inputs.
  • Record departures from the reference design and check their effect on capacity balance.
  • Add a completion checklist surfacing items reference designs leave open: permits, cable/pipe schedules, structural loading, drainage, fire suppression, security.

Who should read it

Planners who want to start a design from a template and teams building a reference-design library.

Publication details

Authors
Patrick Donovan
Publisher
Schneider Electric
Year
2012
Document number
WP 147
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Patrick Donovan (2012). Data Center Projects: Advantages of Using a Reference Design. Schneider Electric. WP 147. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-7XMT5M_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.