Continuous Metering and Monitoring of PUE in Data Centers
Schneider Electric · Wendy Torell
A Schneider Electric white paper (WP 204, 2016) on planning a permanent PUE metering scheme instead of relying on models or one-off audits.
On this page
Overview
The paper explains how to plan permanent PUE metering rather than rely on models or one-off audits, which miss weather and load variation. The steps are choosing a Green Grid reporting level, tracing circuits so every IT and non-IT load is identified, deciding where embedded meters suffice and where new ones are needed, installing meters in a live facility, and aggregating data in a DCIM/EPMS. Levels differ by IT-load meter location: Level 1 at UPS output, Level 2 at PDU output, Level 3 at IT equipment input, for example metered rack PDUs.
Data frequency depends on the level: Level 1 requires monthly measurement while Level 3 requires 15 minutes or less, and 15 minutes is the recommended minimum frequency. Non-IT loads such as air handlers on the UPS output inflate the measured IT load at Level 1 and artificially improve PUE. IT-load metering cost ranges from free with embedded meters to $300 per kW of IT load. Generators are suggested for estimation rather than metering because they are often shared and are not a big PUE driver.
Shared-building cases get detailed treatment. In the panel examples a mostly-data-center panel needs 3 meters (input minus two office breakers) while a mostly-office panel needs 4 (the sum of four CRAH breakers). A shared chiller is apportioned with supply/return temperature sensors and a flow meter on both the main and data center loops, multiplying chiller electrical power by the ratio of data center to chiller heat rejection. Split-core current sensors are less accurate than solid-core but suit live installs; ultrasonic flow meters avoid draining piping but cost far more. The dashboard should show PUE, percent IT load and a subsystem energy breakdown so poor PUE from light loading is not mistaken for poor design.
Key points
- Level 1 meters IT at UPS output, Level 2 at PDU output, Level 3 at IT equipment input.
- Level 1 needs monthly data, Level 3 every 15 minutes or less; 15 minutes is the recommended minimum frequency.
- Non-IT loads on UPS output inflate IT load at Level 1 and flatter PUE.
- IT-load metering costs from free to $300 per kW of IT load.
- Panel example: 3 meters for a mostly-data-center panel, 4 for a mostly-office panel.
- Shared chiller: sensors and flow meters on both loops; chiller power times heat-rejection ratio.
- Estimate generators rather than metering them.
- Split-core CTs are less accurate but suit live installs; ultrasonic flow meters are much more expensive.
Using it in design
- Mark utility, UPS-output, PDU-output, rack-input and mechanical meters on the single-line diagram and compare coverage with Green Grid levels.
- Warn when non-IT loads are fed from UPS output while PUE is metered at Level 1; detect double counting when a metered panel feeds another metered panel.
- Flag shared chillers or generators with no apportioning method (ratio, subtract, thermal metering, model).
- Default to 15-minute logging; the dashboard spec includes PUE, % IT load and subsystem breakdown.
Who should read it
Design and operations engineers planning PUE monitoring and meter layouts.
Related standards
- ISO/IEC 30134-2
- EN 50600-4-2
- ASHRAE Datacom Series Book 11
Publication details
- Authors
- Wendy Torell
- Publisher
- Schneider Electric
- Year
- 2016
- Document number
- WP 204
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Wendy Torell (2016). Continuous Metering and Monitoring of PUE in Data Centers. Schneider Electric. WP 204. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WTOL-936RKM_EN